Certifications

• Overview

• Device Certification

• Certified Product Catalog

• Certification Tool

• Professional Certification

• Annual LonMark Awards


  Related Information
 

Device Certification - LonMark conformance instructions.

Design Guidelines - Technical information for developing open interoperable LonMark products.

Technical Corner - Provides answers to commonly asked technical questions.

LonMark Members who manufacture products used in Open Systems



LonMark-Certified Product Catalog

 XL12 FCU + Light 

New Search

 

Company Name: Honeywell International
Standard Program ID: 8 0000C 5501 03 04 28
LonMark Version: 3.3
Category: HVAC
LonMark Format: 8
Manufacturer ID: 0000C - Honeywell International (12)
Device Class: 5501 - SCC - Fan Coil
Usage Class: 03 - Commercial
Media Channel: 04 - TP/FT-10
SPID Model Number: 28
XL12 FCU + Light  
Datasheet: hon_xl12fculight.pdf
XIF/DRFs Download: 80000C5501030428.zip
XIF available: Yes, included in the above ZIP file
DRFs available: Yes, included in the above ZIP file
LonMark Profiles
Supported (qty):
0000 - Node Object (1)
0003 - Open Loop Actuator Object (2)
1060 - Occupancy Sensor (1)
3040 - Lamp Actuator (3)
8501 - SCC-Fan Coil (1)
Clock Rate: 10 MHz
Agency Approvals: CE
Product Availability: World Wide except America
Sales Information: http://europe.hbc.honeywell.com/products/index.html(opens into a new window)
Product Description: The Excel 12 FCU + Light application is used for integrated room control. The application controls one FCU and 3 lights. FCU functionality:- 3 sequences configurable for HEAT, COOL and CHANGEOVER. - Minimum / maximum control limits to guarantee a minimum / maximum temperature. 2 additional temperature sensors may be used for limit control.- Support of 0...10V actuators, thermal actuators, floating actuators, PWM and Staged Output via triac or relay outputs - 3-stage fan via triac or relay outputs - Digital input for condensation, occupancy sensor, window contact etc. Light functionality: Excel 12 controls up to three lights. Up to two of these lights may be dimmable or constant light control.- ON / OFF switching dependent on: + Effective occupancy mode (occupied / standby / unoccupied). Effective occupancy is determined by occupancy sensor, schedule and override input. + Detected light level (LON sensor or hard wired sensor) - Manual switching (hard wired push buttons or LON wall module) - Dimming / constant light control via analog outputs (this requires an HFD (High Frequency Unit) unit for dimming with 1...10Vdc input). - Grouping of lights, e.g. switch three lights via a single push button.- Soft ON/OFF switching for dimmable lamps Free inputs / outputs: - Otherwise unused inputs may be utilized for monitoring via the LonWorks network (1 x temperature, 1 x percentage and 3 x binary. - Up to 2 unused binary outputs may be switched via the LON network. Example: An Excel 500 controller may be used to monitor the humidity in a room and switch on a dehumidifier via the digital output of the Excel 12.
Product Contact: Dieter FOITH
Product Marketing Manager - Europe
Tel: +49 7031 637 249
Fax: +49 7031 637 547
dieter.foith(a)honeywell.com
 
Use “BACK” button to return to search results.

 
 
 
© 2007-2017 LonMark International. Terms of Use | Privacy Policy (“Cookie”) cookie settings: view/edit

  Certifications


The number of applications for LonMark certification is growing rapidly. To make sure your products are on-track for certification, design conformance into them by following the LonMark Interoperability Guidelines v3.4.

see Device Certification

The Proficiency Testing Program for Qualified Open Systems Installers, Professionals and Integrators provides a worldwide standard of proficiency for individuals that install, integrate and maintain systems utilizing LonMark certified products.

see Professional Certification