Format:
A 4-bit, single hexadecimal value defining the structure of the Program Identifier.
The most-significant bit of the Format being SET determines that the program identifier is a Standard Program Identifier (SPID) instead of being texual or other program identifier format.
The upper bit is set for SPIDs, so Formats 8 - 15 (0x8 - 0xF) are reserved for SPIDs. Format 8 is reserved for LonMark International-certified devices. SPID Format 9 is used for devices that will not be LonMark certified, or for devices that will be certified but are still in development or have not yet completed the certification process. SPID formats 10 - 15 (0xA - 0xF) are reserved for future use. Text program ID formats are used by network interfaces and legacy devices; and, with the exception of network interfaces, should not be used for new devices. Echelon Corporation's NodeBuilder tool can be used to create applications with SPID format 8 or 9, can be used to create network interfaces using text program IDs, and it is also compatible with legacy applications using text program IDs.
Manufacturer Identifier:
Five (5) hex-digits that are unique to each LonWorks device manufacturer. The most-significant bit identifies the MID as a standard MID (upper bit clear) or a temporary MID (upper bit set). Standard MIDs are assigned to manufacturers when they join LonMark International (upon request), and are also published by LonMark International so that the device manufacturer of a LonMark International-certified device is easily identified. Standard MIDs are never reused or reassigned. Temporary MIDs are available to anyone, by request, by filling out a simple form at www.lonmark.org/mid.
Device Class:
Four (4) hexadecimal digits identifying the primary function of the device. This value is drawn from a registry of pre-defined Device Class definitions. If an appropriate Device Class designation is not available, LonMark International may assign one if a profile is created or if it is deemed necessary. Please send your requests to cert@lonmark.org.
Device SubClass:
Eight bits identifying whether the device has a changeable interface (1 bit), whether the usage is defined by the profile (1 bit), and six (6) bits to specify the usage.
The most-significant bit specifies whether the device has a changeable interface. The next bit specifies whether the remainder of the usage field specifies a standard usage or a functional-profile specific usage. The standard usage values are drawn from a registry of pre-defined usage definitions. If an appropriate usage designation is not available one may be assigned upon request. If the second bit is set, a custom set of usage values is specified by the primary functional profile for the device.
Channel Type:
Two hexadecimal digits identifying the channel type supported by the device's LonWorks transceiver. The channel-type values are drawn from a registry of pre-defined channel-type definitions.
Model Number:
Eight (8) bits identifying the specific product model. Model numbers are assigned by the product manufacturer and must be unique within the device class, usage, and channel type for the manufacturer. The same hardware may be used for multiple model numbers depending on the program that is loaded into the hardware. The model number within the program ID does not have to conform to the manufacturer's model number. The bits can be used anyway seen fit by the manufacturer.
|
|
|
|
|
|
|
|
|

|

Standard Program Identifier (SPID) Master List
|
|
|
|

Contents File Information
 Manufacturers
 Device Classes
 Usage (Device SubClasses)
 Channel Types
 top

File InformationData File Version:
100 XML File-Change Date:
20150412T094400Z XML File-Format Version:
4 SPID XML-Elements Version:
1.
0
top

Manufacturers(Manufacturers in
gray text are no longer in the LonMark database, and no contact information is available for those companies)
| ABB Gebäudetechnik AG |
{MID:
104}
|
| ABB Oy |
{MID:
32}
|
| ABB Metering SVM |
{MID:
39}
|
| Acutherm |
{MID:
91}
|
| Adic Co., Ltd. |
{MID:
161}
|
| AGH University of Science and Technology |
{MID:
251}
|
| Agtatec AG |
{MID:
171}
|
| AirTest Technologies, Inc. |
{MID:
229}
|
| Alco Controls (Copeland Corp.) |
{MID:
83}
|
| Alstom Transport SA |
{MID:
137}
|
| ALYA International Inc. |
{MID:
65}
|
| Aquametro AG |
{MID:
168}
|
| APANET Green System Sp.z.o.o. |
{MID:
249}
|
| ATMI GmbH (MST Technology GmbH) |
{MID:
63}
|
| Auslon |
{MID:
51}
|
| Axsys Automation |
{MID:
160}
|
| BadgerMeter Inc. (Data Industrial Corporation) |
{MID:
202}
|
| BELIMO Automation AG |
{MID:
97}
|
| Building Automation Products, Inc. |
{MID:
214}
|
| Blue Earth, Inc. |
{MID:
238}
|
| C&K Systems, Inc. |
{MID:
93}
|
| Camille Bauer AG |
{MID:
54}
|
| Capelon AB |
{MID:
185}
|
| Capelon AB (CeTeLaB) |
{MID:
144}
|
| CAREL S.p.A. |
{MID:
148}
|
| Carrier Corporation |
{MID:
178}
|
| CIAC |
{MID:
145}
|
| Citylone |
{MID:
233}
|
| CNA Engineers Pte Ltd. (Hygreen Systems Pte. Ltd.) |
{MID:
99}
|
| Coactive Networks, Inc. |
{MID:
89}
|
| Comelta |
{MID:
27}
|
| Computer Process Controls |
{MID:
81}
|
| Continental Control Sys |
{MID:
34}
|
| Control Solutions, Inc. |
{MID:
23}
|
| Control Techniques |
{MID:
211}
|
| Cristal Controls Ltd. |
{MID:
66}
|
| CTI Products, Inc. |
{MID:
96}
|
| Cummins Engine Co. |
{MID:
74}
|
| Cypress Semiconductor |
{MID:
175}
|
| D&H Elektronik Anlagenbau |
{MID:
64}
|
| Daikin Applied |
{MID:
135}
|
| Danfoss |
{MID:
8}
|
| DCI Co., Ltd. |
{MID:
118}
|
| Delmatic Ltd. |
{MID:
45}
|
| Develco Elektronik ApS |
{MID:
69}
|
| DEVTECH M2M PTE LTD |
{MID:
253}
|
| Distech Controls Inc. |
{MID:
131}
|
| Distech Controls SAS |
{MID:
103}
|
| Douglas Lighting Controls |
{MID:
68}
|
| Draeger Safety AG & Co. KGaA |
{MID:
203}
|
| Drucegrove Ltd. |
{MID:
192}
|
| Eaton Electrical Inc. (MEM 250) |
{MID:
26}
|
| Eaton-Williams Group Ltd. (Vapac Humidity Control) |
{MID:
117}
|
| Echelon Corporation |
{MID:
1}
|
| Ecosian |
{MID:
248}
|
| Efficient Building Automation Corp. (Circon) |
{MID:
24}
|
| Electronic Theatre Controls, Inc. |
{MID:
209}
|
| ELKA-Elektronik GmbH |
{MID:
222}
|
| ELM Ltd. |
{MID:
46}
|
| Enel.it S.p.A. |
{MID:
116}
|
| Energy Controls International |
{MID:
100}
|
| Enermet Oy |
{MID:
61}
|
| ERCO Leuchten GmbH |
{MID:
143}
|
| EWE TEL GmbH (Nodus GmbH) |
{MID:
90}
|
| Examples |
{MID:
1048575}
|
| Faiveley S.A. |
{MID:
151}
|
| FieldServer Technologies |
{MID:
149}
|
| Firecom, Inc. |
{MID:
124}
|
| Flashnet SRL |
{MID:
252}
|
| Fr. Sauter AG |
{MID:
101}
|
| Fuji Electric FA Components & Systems Co., Ltd. |
{MID:
80}
|
| Fuji Electric Systems, Co., Ltd. |
{MID:
198}
|
| Functional Devices, Inc. |
{MID:
207}
|
| GD Midea Heating&Ventilating Equipment Co.,Ltd. |
{MID:
235}
|
| GE Water Technologies (Osmonics/Lakewood) |
{MID:
44}
|
| Gebrüder Trox GmbH |
{MID:
70}
|
| Gentec Inc. |
{MID:
174}
|
| Gesytec GmbH |
{MID:
73}
|
| Gorenje d.d. |
{MID:
206}
|
| Grayhill Inc. |
{MID:
14}
|
| Grundfos Management A/S |
{MID:
85}
|
| Guangdong Rongwen Energy Science and Technology Group Co., Ltd. |
{MID:
247}
|
| Gulf Security Technology Co. Ltd. |
{MID:
210}
|
| Hach Company |
{MID:
41}
|
| HalenSmart Company Limited |
{MID:
150}
|
| Heat-Timer Corporation |
{MID:
18}
|
| Helvar |
{MID:
5}
|
| HERMOS Informatik GmbH |
{MID:
163}
|
| Hitachi Ltd. |
{MID:
205}
|
| Honeywell International, Inc. (12) |
{MID:
12}
|
| Honeywell International, Inc. (12) - Field Programmed |
{MID:
131084}
|
| Honeywell International, Inc. (55) |
{MID:
55}
|
| Honeywell International, Inc. (E-Mon) |
{MID:
241}
|
| Honeywell International, Inc. (Analytics) |
{MID:
59}
|
| Hoshizaki America |
{MID:
240}
|
| Hubbell Building Automation, Inc. |
{MID:
199}
|
| Hubbell Incorporated (Delaware) Wiring Device-Kellems |
{MID:
36}
|
| Hüppelux (Hüppe Form) |
{MID:
108}
|
| Hunter Douglas |
{MID:
231}
|
| HyCal |
{MID:
28}
|
| Hyundai Autonet Co., Ltd. |
{MID:
139}
|
| IBM |
{MID:
3}
|
| IDEC Corporation |
{MID:
132}
|
| IEC Intelligent Technologies |
{MID:
9}
|
| Infranet Partners Limited |
{MID:
169}
|
| Intellicom Innovation AB |
{MID:
176}
|
| Intermoco Ltd. (Australon Enterprises) |
{MID:
125}
|
| iPLON GmbH |
{MID:
60}
|
| ISDE |
{MID:
225}
|
| ISH |
{MID:
11}
|
| Janitza electronic GmbH |
{MID:
193}
|
| Johnson Controls, Inc. |
{MID:
17}
|
| Johnson Controls/ESUSA |
{MID:
33}
|
| Kaba Benzing GmbH (10) |
{MID:
10}
|
| Kaba Benzing GmbH (52) |
{MID:
52}
|
| Kaifa Technology Co. Ltd. |
{MID:
184}
|
| Kamstrup A/S |
{MID:
173}
|
| Kele & Associates |
{MID:
84}
|
| Kieback & Peter GmbH & Co KG |
{MID:
164}
|
| KITZ Corporation |
{MID:
111}
|
| Knorr Brake Corp. |
{MID:
127}
|
| Kongsberg anaLogic AS |
{MID:
130}
|
| Landert-Motoren AG (Tormax) |
{MID:
75}
|
| Legrand |
{MID:
120}
|
| Lennox Industries |
{MID:
232}
|
| Levec, Inc. |
{MID:
77}
|
| Leviton Manufacturing Co. |
{MID:
13}
|
| LG Electronics |
{MID:
204}
|
| Lighthouse Industries Ltd. |
{MID:
50}
|
| Linton Systems |
{MID:
43}
|
| Lochinvar Corporation |
{MID:
182}
|
| Lonix Ltd |
{MID:
255}
|
| LonMark Technical Staff |
{MID:
159}
|
| LonMark - AFS1 |
{MID:
1047948}
|
| LOYTEC electronics GmbH |
{MID:
215}
|
| LS Industrial Systems Co., Ltd. |
{MID:
218}
|
| Luminator |
{MID:
138}
|
| LUXMATE Controls GmbH |
{MID:
106}
|
| M+W Zander Facility Engineering GmbH |
{MID:
200}
|
| Mangelberger Elektrotechnik GmbH |
{MID:
245}
|
| Matrix Controls Pte. Ltd. |
{MID:
107}
|
| McQuay International |
{MID:
37}
|
| MEIKOSHA Co., Ltd. |
{MID:
126}
|
| Mentzel & Krutmann GmbH |
{MID:
58}
|
| Microlab Sistemi S.r.l. |
{MID:
166}
|
| MicroTask |
{MID:
187}
|
| Mitsubishi Electric Corp. |
{MID:
162}
|
| Motorola, Inc. |
{MID:
2}
|
| MSR-Electronic-GmbH |
{MID:
35}
|
| M-SYSTEM CO., LTD. |
{MID:
223}
|
| Nanjing Lianhong Automation Co. Ltd. |
{MID:
219}
|
| Network-Controls Pte. Ltd. |
{MID:
146}
|
| NeuroLogic Research Corporation |
{MID:
98}
|
| NICO Technology, Inc. |
{MID:
181}
|
| OAS, Inc. |
{MID:
186}
|
| Occitaline |
{MID:
254}
|
| Oiles Corporation |
{MID:
194}
|
| Onicon Incorporated |
{MID:
208}
|
| ORAS Oy |
{MID:
62}
|
| Orion C&I Corporation |
{MID:
190}
|
| Osaki Electric Co., Ltd. |
{MID:
196}
|
| Panasonic Electric Works Co., Ltd. |
{MID:
113}
|
| Paragon Controls |
{MID:
226}
|
| PentaControl AG (Bircher Gebäudetechnik AG) |
{MID:
40}
|
| PDL Industries Ltd. |
{MID:
140}
|
| Philips Lighting B.V. |
{MID:
47}
|
| Phoenix Controls Corporation |
{MID:
212}
|
| PIC Electronics |
{MID:
228}
|
| Plexus Technology Limited |
{MID:
141}
|
| Power Measurement Ltd. |
{MID:
30}
|
| Programmed Water Technologies / Sloan Valve (56) |
{MID:
56}
|
| Programmed Water Technologies / Sloan Valve (183) |
{MID:
183}
|
| Programmed Water Technologies / Sloan Valve (243) |
{MID:
243}
|
| PureChoice, Inc. |
{MID:
188}
|
| Quantum Automation Pte Ltd. |
{MID:
217}
|
| Quark Communications Inc. |
{MID:
195}
|
| Raypak, Inc. (Rheem) |
{MID:
180}
|
| Regin AB |
{MID:
122}
|
| Richards-Zeta Building Intelligence |
{MID:
53}
|
| Riken Keiki Co., Ltd. |
{MID:
72}
|
| Rockwell Automation |
{MID:
136}
|
| Safegard Systems Ltd. (NT Software Ltd) |
{MID:
48}
|
| Samson AG |
{MID:
115}
|
| Samsung Electronics Co., Ltd. |
{MID:
191}
|
| Samsung Heavy Industries Co., Ltd. |
{MID:
110}
|
| Samsung SDS |
{MID:
234}
|
| Schlumberger (SILD) |
{MID:
4}
|
| Schneider Electric (Andover) |
{MID:
16}
|
| Schneider Electric (CSI) |
{MID:
31}
|
| Schneider Electric (Lexel Group) |
{MID:
6}
|
| Schneider Electric (Lexel/Merten) |
{MID:
224}
|
| Schneider Electric (Moeller/SVEA) |
{MID:
21}
|
| Schneider Electric (Merten/SVEA) |
{MID:
227}
|
| Schneider Electric (Power) |
{MID:
20}
|
| Schneider Electric (TAC AB) |
{MID:
19}
|
| Schneider Electric (TAC LLC) |
{MID:
22}
|
| Schneider Electric (Viconics Electronics Inc.) |
{MID:
197}
|
| Seaboard Process Controls, Inc. |
{MID:
49}
|
| Secyourit GmbH |
{MID:
246}
|
| Shanghai ChangXiang Computer Co., Ltd |
{MID:
179}
|
| Shikoku Instrumentation Co., Ltd. |
{MID:
177}
|
| Siemens BT |
{MID:
25}
|
| Siemens BT (Korea) |
{MID:
114}
|
| Siemens BT (North America and Asia-Pacific) |
{MID:
129}
|
| Siemens BT (Staefa Controls USA) |
{MID:
105}
|
| Simon, S.A. |
{MID:
242}
|
| Siteco Control GmbH |
{MID:
220}
|
| Smart Controls |
{MID:
15}
|
| Solidyne Corp. |
{MID:
201}
|
| Somfy |
{MID:
82}
|
| Sontay Open Systems, Ltd. |
{MID:
92}
|
| SPI Systems Ltd. |
{MID:
216}
|
| SPEGA - Spelsberg Gebaudeautomation GmbH + Co. KG |
{MID:
230}
|
| Stifab Farex AB |
{MID:
170}
|
| STV Automation - A Division of STV Electronic GmbH |
{MID:
250}
|
| Surf Networks, Inc. |
{MID:
172}
|
| SysMik GmbH Dresden |
{MID:
94}
|
| Telda Electronics |
{MID:
102}
|
| Terasaki Electric Co., Ltd. |
{MID:
165}
|
| The Watt Stopper |
{MID:
167}
|
| Theben HTS AG |
{MID:
239}
|
| TMI |
{MID:
7}
|
| Toshiba Corporation |
{MID:
76}
|
| Toshiba Info Systems (Japan) |
{MID:
78}
|
| Toshiba Lighting & Technology Corporation |
{MID:
133}
|
| Trane |
{MID:
42}
|
| Trend Control Systems Ltd (Novar Trend) |
{MID:
29}
|
| Tridium, Inc. |
{MID:
142}
|
| Trustbridge |
{MID:
244}
|
| TSI Incorporated |
{MID:
71}
|
| UTC HVAC |
{MID:
257}
|
| VaCom Technologies |
{MID:
213}
|
| Vacon Plc |
{MID:
189}
|
| Vaisala Oy |
{MID:
38}
|
| Valvcon Corporation |
{MID:
147}
|
| Veris Industries |
{MID:
237}
|
| Viessmann Werke GmbH u. Co. |
{MID:
128}
|
| Vossloh-Schwabe Deutschland GmbH |
{MID:
236}
|
| Voyant Solutions, LLC |
{MID:
221}
|
| Wabtec Corporation |
{MID:
121}
|
| WAGO |
{MID:
112}
|
| WAREMA electronic GmbH |
{MID:
87}
|
| Watanabe Electric Industry Co., Ltd. |
{MID:
123}
|
| Yamatake Corporation |
{MID:
95}
|
| Yaskawa Electric America |
{MID:
57}
|
| Yokogawa Electric Corporation |
{MID:
67}
|
| ZDANIA Sp. z o.o. Ltd |
{MID:
256}
|
| York International |
{MID:
119}
|
| Zone Controls |
{MID:
86}
|
| zzz - reserved-0004F |
{MID:
79}
|
| zzz - reserved-00058 |
{MID:
88}
|
| zzz - reserved-0006D |
{MID:
109}
|
| zzz - reserved-00086 |
{MID:
134}
|
| zzz - reserved-0FF00 |
{MID:
65280}
|
top

Device Classes(Device Classes that have hyperlinks for their numbers are also Functional Profiles that can be viewed by clicking the link. Device Classes marked with “*” are not valid for new designs.)
50.00 -
Access/Intrusion/Monitoring 50.10 --- Intercom 50.11 --- Alphanumeric LCD/Led Display 50.12 --- PS/2 Interface 50.20 --- Motorized Strike Plate 50.30 --- Reader 50.31 -------- Legic Reader 50.32 -------- Barcode Reader 50.33 -------- Magcard Reader 50.34 -------- Inductive Reader 50.35 -------- Identifier Sensor 50.40 --- Logic Cylinder 50.50 --- Remote Door Manager 50.51 -------- Entry/Exit 50.60 --- Event Memory 50.70 --- Elevator Access Controller 50.80 --- Arming Station 50.90 --- Telephone Controls 50.91 -------- Modem Controller 50.92 -------- Telephone Directory
170.00 -
Automated Food Service 172.00 --- Beverage Control and Monitoring 172.10 -------- Heated-Beverage Control and Monitoring 172.11 ---------------- Coffee-Making Control and Monitoring 172.20 -------- Cooled-Beverage Control and Monitoring
20.00 -
Energy Management 20.10 --- Load-Shed Module (LSM) 20.11 -------- Load-Shed Module with power sensor 20.12 -------- Load-Shed Module with energy monitoring 20.20 --- Circuit Breaker 20.30 --- Scheduler with Presets 21.00 --- 3-Phase Energy Meter 21.01 -------- 3-Phase Demand Power Meter 21.02 -------- 3-Phase Demand Ammeter 21.03 -------- 3-Phase Power Meter 21.04 -------- 3-Phase Ammeter 21.05 -------- 3-Phase Voltmeter 21.10 --- Utility Data Logger Register 21.50 --- Multi-Phase Energy Meter 21.51 -------- Multi-Phase Demand Power Meter 21.52 -------- Multi-Phase Demand Ammeter 21.53 -------- Multi-Phase Power Meter 21.54 -------- Multi-Phase Ammeter 21.55 -------- Multi-Phase Voltmeter 22.00 --- Automated Meter Reader (AMR) 22.01 -------- Utility Meter
110.00 -
Fire & Smoke Devices 110.01 --- Fire Smoke Damper Actuator 110.02 --- Smoke (Intelligent) Fire Initiator 110.03 --- Smoke (Conventional) Fire Initiator 110.04 --- Thermal Fire Initiator 110.05 --- Pull-Station Fire Initiator 110.06 --- Audible Fire Indicator 110.07 --- Visible Fire Indicator 110.08 --- Manual Call Point 110.09 --- Fireman Call Point 110.10 --- Universal Fire Initiator 110.11 --- Universal Fire Indicator
70.00 -
Gateways 70.10 --- Telephone Gateway 70.11 -------- Alphanumeric Notifier 70.20 --- Internet Gateway 70.21 -------- Internet Web Server 70.22 -------- Internet Information Server 70.30 --- PLC Interface 71.00 --- BMS Gateway 71.10 --- Fire & Smoke Gateways 71.30 --- Industrial Gateways 72.10 --- Refrigeration Gateways 72.20 --- Energy Management Gateways 72.30 --- Lighting Gateways 72.40 --- Vertical/Conveyor Transportation Gateways 72.50 --- Access/Intrusion/Monitoring Gateways 72.80 --- HVAC Gateways 72.90 --- Transportation Gateways 72.91 -------- Signage/Enunciation/Display Systems
07.00 -
Generic Actuators
06.00 -
Generic Controllers
08.00 -
Generic Human-Machine Interfaces (HMIs) 08.10 --- Remote Control 08.11 -------- IR Remote Control 08.12 -------- RF Remote Control 08.20 --- Panel Interface 08.21 -------- Touch-Screen Panel 08.22 -------- LCD/LED Panel HMI
80.00 -
HVAC 80.10 --- VAV Controller 80.11 -------- Dual-Duct VAV Controller 80.20 --- Fan Coil Unit Controller 80.30 --- Roof Top Unit Controller 80.40 --- Chiller 80.50 --- Heat Pump * 80.51 -------- Heat Pump with Temperature Control 80.60 --- Thermostat 80.70 --- Chilled Ceiling Controller 80.80 --- Unit Ventilator Controller 80.90 --- Space Comfort Control Command Module 81.00 --- SCC - Template for Controller-based nodes * 81.10 --- Damper Actuator 81.11 -------- Modulating Damper Actuator 81.20 --- Pump Controller 81.30 --- Valve Controls 81.31 -------- Valve Positioner (HVAC) Profile-Specific Usage:
00 -- Programmed Actuator Characteristic
01 -- Programmed Actuator Characteristic with Emergency Mode function
20 -- Calculated Actuator Characteristic
21 -- Calculated Actuator Characteristic with Emergency Mode function 81.35 -------- Linear Valve Actuator 82.00 --- Plant Controller 83.00 --- Burner and Boiler Controllers 83.01 -------- Boiler Controller 84.00 --- Product Controllers 85.00 --- SCC - Generic 85.01 -------- SCC - Fan Coil 85.02 -------- SCC - Variable Air Volume 85.03 -------- SCC - Heat Pump 85.04 -------- SCC - Rooftop Unit 85.05 -------- SCC - Unit Ventilator 85.06 -------- SCC - Chilled Ceiling 85.07 -------- SCC - Radiator 85.08 -------- SCC - Air-Handling Unit 85.09 -------- SCC - Self-Contained Unit 85.10 -------- SCC - (reserved, 85.10) 85.29 -------- SCC - (reserved, 85.29) 85.40 --- Wall Unit 85.50 --- Unit Heater 86.00 --- Air Handling 86.10 -------- Discharge-Air Controller 86.20 -------- Air Handling Critical-Safety Devices 86.21 ---------------- Fume Hood Face-Velocity Controller 86.22 ---------------- Room Direct-Pressure Controller
05.00 -
I/O 05.01 --- Multi-I/O module 05.03 --- Multi-Output Module 05.10 --- 8-Channel configurable I/O 05.11 --- 8-Channel voltage input 05.12 --- 8-Channel current input 05.13 --- 8-Channel digital input 05.14 --- 4 Digital input, 4 digital output 05.15 --- 8-Channel Digital Output 05.16 --- 8-Channel switch input 05.20 --- Analog Input 05.21 --- Analog Output 05.22 --- Extended Analog Input 05.23 --- Extended Analog Output 05.24 --- Generic Analog Input 05.25 --- Generic Analog Output 05.30 --- 6-Channel configurable I/O 05.31 --- 4 Digital input, 2 digital output 05.32 --- 6 Analog outputs U/I 05.40 --- Digital I/O 05.41 --- 7 Digital input, 4 digital output 05.42 --- Digital Input 05.43 --- Digital output 05.48 --- Digital Input Node 05.50 --- 2-Channel configurable I/O 05.51 --- 2-Channel digital input 05.52 --- 2-Channel digital output 05.53 --- 2 Digital input, 2 digital output 05.54 --- 2 Analog input 05.55 --- 2 Analog output 05.60 --- 4-Channel configurable I/O 05.61 --- 4-Channel digital input 05.62 --- 4-Channel digital output 05.63 --- 4 Analog input 05.64 --- 4 Analog output 05.70 --- 12-Channel configurable I/O 05.71 --- 12 Digital inputs Vdc 05.72 --- 12 Digital outputs Vdc 05.73 --- 12 Digital inputs 100-250 Vac 05.74 --- 12 Digital input 12-48 Vac/dc opto iso 05.75 --- 12 Analog inputs U/I/Pt100 05.80 --- Multi-Channel I/O 05.83 --- Multiple Digital Inputs 100-250 Vac
130.00 -
Industrial 131.10 --- Generator Set 131.20 --- Automatic Transfer Switch 132.10 --- Programmable Controller 135.00 --- Filtration Systems 135.10 -------- Gas Filtration 135.11 ---------------- Fan-Filter Unit 135.20 -------- Liquid Filtration 135.30 -------- Solid Filtration 138.10 --- Remote Miniature Circuit Breaker 138.11 --- Circuit Breaker - Other 138.20 --- PLC Gateway for specific device * 138.30 --- Power Supplies 138.31 -------- Power Supply (less than 5V) 138.32 -------- Power Supply (less than 15V) 138.33 -------- Power Supply (less than 50V) 138.34 -------- Power Supply (less than 100V) 138.35 -------- Power Supply (less than 200V) 138.36 -------- Power Supply (less than 500V) 138.37 -------- Power Supply (less than 1000V)
30.00 -
Lighting 30.10 --- Dimmer 1-10V 30.11 -------- 8-Channel dimmer 1-10V 30.12 -------- 3-Channel dimmer 1-10V 30.20 --- Transistor Dimmer 30.30 --- Thyristor Dimmer 30.40 --- Lamp Actuator 30.41 --- ISI Lamp Actuator 30.50 --- Constant Light Controller 30.71 --- Occupancy controller 32.00 --- Switch Profile-Specific Usage:
00 -- Discrete Output (ON/OFF)
01 -- Discrete Output (ON/OFF) with Feedback Input
02 -- Discrete Output (ON/OFF) with Setting Control
03 -- Discrete Output (ON/OFF) with Feedback Input and Setting Control
20 -- Variable Output
21 -- Variable Output with Feedback Input
22 -- Variable Output with Setting Control
23 -- Variable Output with Feedback Input and Setting Control 32.01 -------- 4-Switch relay 32.02 -------- Multi-switch/multi-sensor 32.03 -------- Switch/sensor 32.50 --- Scene Panel 32.51 --- Scene Controller 32.52 --- Partition Wall Controller 32.53 --- ISI Keypad 33.00 --- Real-Time Keeper 33.01 -------- Real-Time-Based Scheduler 34.00 --- Lighting Controller 34.01 -------- Lighting Panel Controller 35.00 --- Outdoor Lighting 35.12 -------- Outdoor Luminair Controller 35.14 -------- Smart Luminair Controller
60.00 -
Motor Controls 60.10 --- Variable-Speed Motor Drive 61.00 --- Sunblind Motor * 61.01 -------- Sunblind Motor Controller * 61.10 --- Sunblind Actuator Profile-Specific Usage:
00 -- Feedback Output
01 -- Control (daisy chain) Output
02 -- Feedback Output and Control (daisy chain) Output 61.11 --- Sunblind Controller 61.12 --- ISI Sunblind Actuator Profile-Specific Usage:
00 -- Feedback Output
01 -- Control (daisy chain) Output
02 -- Feedback Output and Control (daisy chain) Output 54.10 --- AC Drive (v3.0 Products Only) *
01.00 -
Network Infrastructure 01.01 --- ISO/IEC 14908-1 Router 01.02 --- Network Interfaces 01.03 --- Network Managers 01.04 --- Data Logger 01.05 --- Microprocessor Interfaces 01.10 --- Foreign System Connection Sensor 01.20 --- Scheduler 01.30 --- Diagnostic Tools 01.31 -------- Channel Diagnostics 01.32 ---------------- Channel Monitor 01.36 -------- Device Monitor 01.37 -------- Channel Continuity Monitor 01.40 --- Generic Controller 01.60 --- Device Manager
04.00 -
Programmables 04.01 --- Programer 04.10 --- Static Programmable 04.50 --- Dynamic Programmable
100.00 -
Refrigeration 100.10 --- Defrost Controller 100.11 --- Evaporator Controller 100.12 --- Refrigeration Thermostat Controller 100.13 --- Railheat Controller
180.00 -
Semiconductor Fabrication 180.10 --- Semiconductor Sensors 180.11 -------- Semiconductor Sensor-AI 180.12 -------- Semiconductor Sensor-AI-AT 180.13 -------- Semiconductor Sensor-AI-MF 180.14 -------- Semiconductor Sensor-AI-Aux 180.15 -------- Semiconductor Sensor-AI-Counter 180.16 -------- Semiconductor Sensor-AI-LCS 180.17 -------- Semiconductor Sensor-AI-SLS 180.18 -------- Semiconductor Sensor-BI 180.19 -------- Semiconductor Sensor-BI-TH 180.20 -------- Semiconductor Sensor-BI-TH-EP 180.30 --- Semiconductor Actuators 180.31 -------- Semiconductor Actuator-AO 180.32 -------- Semiconductor Actuator-AO-MF 180.33 -------- Semiconductor Actuator-BO 180.34 -------- Semiconductor Actuator-EO 180.50 --- Semiconductor Controllers 180.51 -------- Semiconductor Controller 180.70 --- Semiconductor I/O 180.71 -------- Semiconductor Single-Input Single-Output 180.72 -------- Semiconductor Single-Input Single-Output Setpoint 180.80 --- Semiconductor Assemblies 180.81 -------- Semiconductor Assembly 180.82 -------- Semiconductor Assembly-MFM 180.83 -------- Semiconductor Assembly-MFC 180.84 -------- Semiconductor Assembly-ISPM1 180.85 -------- Semiconductor Assembly-ISPM2 180.86 -------- Semiconductor Assembly-ISPM3 180.87 -------- Semiconductor Assembly-ISPM4 180.88 -------- Semiconductor Assembly-ISPM5 180.89 -------- Semiconductor Assembly-ISPM6 180.90 -------- Semiconductor Assembly-ISPM7 180.91 -------- Semiconductor Assembly-ISPM8 180.92 -------- Semiconductor Assembly-ISPM9 180.93 -------- Semiconductor Assembly-ISPM48 180.94 -------- Semiconductor Assembly-EP1 180.95 -------- Semiconductor Assembly-EP2 180.96 -------- Semiconductor Assembly-EP3 180.97 -------- Semiconductor Assembly-EP4
10.00 -
Sensors 10.10 --- Light Sensor 10.15 --- Global Solar Radiation Sensor 10.20 --- Time Sensor 10.30 --- Pressure Sensor 10.40 --- Temperature Sensor 10.41 -------- Temperature & Humidity 10.42 --- Frost Sensor 10.50 --- Relative Humidity 10.51 --- Rain Sensor 10.60 --- Occupancy Sensor 10.61 --- ISI Occupancy Sensor 10.70 --- CO2 Sensor 10.80 --- Gas Concentration Sensor 10.81 --- PH Sensor 10.82 --- Conductivity Sensor 10.83 --- Air-Velocity Sensor 10.90 --- Multi-Function Sensor
90.00 -
Transportation 90.10 --- Door Controls 91.00 --- Audio Systems 91.10 -------- Railway Audio Systems 91.11 ---------------- Railcar Audio Controller 91.12 ---------------- Railcar Audio Sensor 95.00 --- Electric Vehicles 95.10 -------- Billing Systems 95.20 -------- Electric Vehicle Supply Equipment 95.21 ---------------- EVSE Single, Domestic 95.22 ---------------- EVSE Multiple, Domestic 95.25 ---------------- EVSE, Commercial 95.30 ---------------- EVSE, Retail
140.00 -
Vertical/Conveyer Transportation (Elevator) 140.10 --- Elevator/Lift Indicators 140.11 -------- Elevator/Lift Position Indicator and Message Display 140.12 -------- Elevator/Lift Hall Lantern 140.13 -------- Elevator/Lift Arrival Gong 140.14 -------- Elevator/Lift Car-Direction Lantern 140.40 --- Vertical/Conveyer Transportation System Interfaces 140.41 -------- Elevator/Lift Fire-Systems Port 140.60 --- Vertical/Conveyer-Transportation Communication Devices 140.61 -------- Elevator/Lift Voice Announcer
150.00 -
Whitegoods 150.10 --- Clothes 150.11 -------- Clothes Washer, Domestic 150.12 -------- Clothes Dryer, Domestic 150.13 -------- Clothes Iron, Domestic 150.14 -------- Clothes Press, Domestic 150.15 -------- Clothes Steamer, Domestic 150.30 --- Cooking 150.31 -------- Oven, Domestic 150.32 -------- Specialty Oven, Domestic 150.33 -------- Microwave or IR Oven, Domestic 150.34 -------- Electric or Inductive Range, Domestic 150.35 -------- Gas Range, Domestic 150.50 --- Storage 150.51 -------- Refrigerator, Domestic 150.52 -------- Deep Freezer, Domestic 150.53 -------- Beverage Cabinet, Domestic 150.54 -------- Dry Cabinet, Domestic 150.70 --- Miscellaneous 150.71 -------- Dishwasher, Domestic 150.72 -------- In-Sink Disposal, Domestic 150.73 -------- Trash Compactor, Domestic
40.00 -
Wiring Devices 40.10 --- 1-Pushbutton 40.11 --- 2-Pushbutton 40.12 --- 3-Pushbutton 40.13 --- 4-Pushbutton 40.50 --- Rotary control 41.00 --- AC Load Relay 42.00 --- Controlled Receptacle 43.10 --- Hardwired Gas Detection Shutdown 43.11 --- Hardwired Fire Alarm Shutdown 43.12 --- Hardwired Recirculation 43.13 --- Hardwired Full Ventilation 43.14 --- Hardwired Safety Instrumented System - SIS
* (Device Classes marked are not valid for new designs)
top

Usage (Device Subclass)Commercial {
3}
Connectivity {
1}
General {
10}
Industrial {
2}
Industrial/Commercial {
4}
Medical {
9}
Network Management {
0}
Programmable {
63}
Residential {
5}
Residential/Commercial {
6}
Telecommunications {
8}
Transportation {
7}
Utility {
11}
top

Channel Types(Channels in
gray text are
not approved for use as the externally available channel on a Certified device)
| FO-20L |
{ID:
152}
|
ANSI/CEA-709.4 |
| FO-20S |
{ID:
24}
|
ANSI/CEA-709.4 |
| IP-852 |
{ID:
154}
|
ISO/IEC 14908-4 |
| PL-10 |
{ID:
9}
|
LonMark Interoperability Guidelines |
| PL-20A |
{ID:
15}
|
LonMark Interoperability Guidelines |
| PL-20C |
{ID:
16}
|
ISO/IEC 14908-3 |
| PL-20N |
{ID:
17}
|
ISO/IEC 14908-3 |
| PL-30 |
{ID:
18}
|
LonMark Interoperability Guidelines |
| TP/FT-10 |
{ID:
4}
|
ISO/IEC 14908-2 |
| TP/RS485-39 |
{ID:
5}
|
ANSI/TIA/EIA-485-A |
| TP/XF-1250 |
{ID:
3}
|
LonMark Interoperability Guidelines |
| TP/XF-78 |
{ID:
1}
|
LonMark Interoperability Guidelines |
| Backplane |
{ID:
255} |
Echelon Corporation |
| Custom |
{ID:
30} |
|
| DC-1250 |
{ID:
29} |
Echelon Corporation |
| DC-1250/SECD |
{ID:
145} |
Echelon Corporation |
| DC-2500/SECD |
{ID:
146} |
Echelon Corporation |
| DC-625 |
{ID:
28} |
Echelon Corporation |
| DC-78 |
{ID:
27} |
Echelon Corporation |
| IP-10L |
{ID:
25} |
Echelon Corporation |
| IP-10W |
{ID:
26} |
Echelon Corporation |
| IP-852.1 |
{ID:
0} |
ANSI/CEA-852.1 |
| IR-10 |
{ID:
23} |
Echelon Corporation |
| IR-20 |
{ID:
22} |
|
| Pyxos-FT |
{ID:
254} |
Echelon Corporation |
| RF-10 |
{ID:
7} |
Echelon Corporation |
| RF-20 |
{ID:
21} |
|
| TP/FT (reserved) |
{ID:
6} |
|
| TP/RS485-1250 |
{ID:
11} |
ANSI/TIA/EIA-485-A |
| TP/RS-485-625 |
{ID:
10} |
ANSI/TIA/EIA-485-A |
| TP/RS485-78 |
{ID:
12} |
ANSI/TIA/EIA-485-A |
top

See the LonMark Application Layer Interoperability Guidelines for more information about SPIDs.
|
|
|
|
|
|
|
|
| Download the XML File |
 |
 |
 |
For the actual spidData.xml file, click the image above, then choose to save the file when prompted.
Please note that your Development or Network-Management Tool may require this XML file be placed in C:\LONWORKS\TYPES or a different directory.
Please check your tool's documentation to see how it may support this file.
|
|
|
|