A 4-bit, single hexadecimal value defining the structure of the Program Identifier.

The most-significant bit of the Format being SET determines that the program identifier is a Standard Program Identifier (SPID) instead of being texual or other program identifier format.

The upper bit is set for SPIDs, so Formats 8 - 15 (0x8 - 0xF) are reserved for SPIDs. Format 8 is reserved for LonMark International-certified devices. SPID Format 9 is used for devices that will not be LonMark certified, or for devices that will be certified but are still in development or have not yet completed the certification process. SPID formats 10 - 15 (0xA - 0xF) are reserved for future use. Text program ID formats are used by network interfaces and legacy devices; and, with the exception of network interfaces, should not be used for new devices. Echelon Corporation's NodeBuilder tool can be used to create applications with SPID format 8 or 9, can be used to create network interfaces using text program IDs, and it is also compatible with legacy applications using text program IDs.


Manufacturer Identifier:

Five (5) hex-digits that are unique to each LonWorks device manufacturer. The most-significant bit identifies the MID as a standard MID (upper bit clear) or a temporary MID (upper bit set). Standard MIDs are assigned to manufacturers when they join LonMark International (upon request), and are also published by LonMark International so that the device manufacturer of a LonMark International-certified device is easily identified. Standard MIDs are never reused or reassigned. Temporary MIDs are available to anyone, by request, by filling out a simple form at www.lonmark.org/mid.


Device Class:

Four (4) hexadecimal digits identifying the primary function of the device. This value is drawn from a registry of pre-defined Device Class definitions. If an appropriate Device Class designation is not available, LonMark International may assign one if a profile is created or if it is deemed necessary. Please send your requests to cert@lonmark.org.


Device SubClass:

Eight bits identifying whether the device has a changeable interface (1 bit), whether the usage is defined by the profile (1 bit), and  six (6) bits to specify the usage.

The most-significant bit specifies whether the device has a changeable interface. The next bit specifies whether the remainder of the usage field specifies a standard usage or a functional-profile specific usage. The standard usage values are drawn from a registry of pre-defined usage definitions. If an appropriate usage designation is not available one may be assigned upon request. If the second bit is set, a custom set of usage values is specified by the primary functional profile for the device.


Channel Type:

Two hexadecimal digits identifying the channel type supported by the device's LonWorks transceiver. The channel-type values are drawn from a registry of pre-defined channel-type definitions.


Model Number:

Eight (8) bits identifying the specific product model. Model numbers are assigned by the product manufacturer and must be unique within the device class, usage, and channel type for the manufacturer. The same hardware may be used for multiple model numbers depending on the program that is loaded into the hardware. The model number within the program ID does not have to conform to the manufacturer's model number.  The bits can be used anyway seen fit by the manufacturer.





Standard Program Identifier (SPID) Master List

 

Contents

File Information
Manufacturers
Device Classes
Usage (Device SubClasses)
Channel Types

top


File Information

Data File Version: 96
XML File-Change Date: 20141208T081800Z
XML File-Format Version: 4
SPID XML-Elements Version: 1. 0

top


Manufacturers

(Manufacturers in gray text are no longer in the LonMark database, and no contact information is available for those companies)

ABB Gebäudetechnik AG   {MID: 104}
ABB Oy   {MID: 32}
ABB Metering SVM   {MID: 39}
Acutherm   {MID: 91}
Adic Co., Ltd.   {MID: 161}
AGH University of Science and Technology   {MID: 251}
Agtatec AG   {MID: 171}
AirTest Technologies, Inc.   {MID: 229}
Alco Controls (Copeland Corp.)   {MID: 83}
Alstom Transport SA   {MID: 137}
ALYA International Inc.   {MID: 65}
Aquametro AG   {MID: 168}
APANET Green System Sp.z.o.o.   {MID: 249}
ATMI GmbH (MST Technology GmbH)   {MID: 63}
Auslon   {MID: 51}
Axsys Automation   {MID: 160}
BadgerMeter Inc. (Data Industrial Corporation)   {MID: 202}
BELIMO Automation AG   {MID: 97}
Building Automation Products, Inc.   {MID: 214}
Blue Earth, Inc.   {MID: 238}
C&K Systems, Inc.   {MID: 93}
Camille Bauer AG   {MID: 54}
Capelon AB   {MID: 185}
Capelon AB (CeTeLaB)   {MID: 144}
CAREL S.p.A.   {MID: 148}
Carrier Corporation   {MID: 178}
CIAC   {MID: 145}
Citylone   {MID: 233}
CNA Engineers Pte Ltd. (Hygreen Systems Pte. Ltd.)   {MID: 99}
Coactive Networks, Inc.   {MID: 89}
Comelta   {MID: 27}
Computer Process Controls   {MID: 81}
Continental Control Sys   {MID: 34}
Control Solutions, Inc.   {MID: 23}
Control Techniques   {MID: 211}
Cristal Controls Ltd.   {MID: 66}
CTI Products, Inc.   {MID: 96}
Cummins Engine Co.   {MID: 74}
Cypress Semiconductor   {MID: 175}
D&H Elektronik Anlagenbau   {MID: 64}
Daikin Applied   {MID: 135}
Danfoss   {MID: 8}
DCI Co., Ltd.   {MID: 118}
Delmatic Ltd.   {MID: 45}
Develco Elektronik ApS   {MID: 69}
Distech Controls Inc.   {MID: 131}
Distech Controls SAS   {MID: 103}
Douglas Lighting Controls   {MID: 68}
Draeger Safety AG & Co. KGaA   {MID: 203}
Drucegrove Ltd.   {MID: 192}
Eaton Electrical Inc. (MEM 250)   {MID: 26}
Eaton-Williams Group Ltd. (Vapac Humidity Control)   {MID: 117}
Echelon Corporation   {MID: 1}
Ecosian   {MID: 248}
Efficient Building Automation Corp. (Circon)   {MID: 24}
Electronic Theatre Controls, Inc.   {MID: 209}
ELKA-Elektronik GmbH   {MID: 222}
ELM Ltd.   {MID: 46}
Enel.it S.p.A.   {MID: 116}
Energy Controls International   {MID: 100}
Enermet Oy   {MID: 61}
ERCO Leuchten GmbH   {MID: 143}
EWE TEL GmbH (Nodus GmbH)   {MID: 90}
Examples   {MID: 1048575}
Faiveley S.A.   {MID: 151}
FieldServer Technologies   {MID: 149}
Firecom, Inc.   {MID: 124}
Flashnet SRL   {MID: 252}
Fr. Sauter AG   {MID: 101}
Fuji Electric FA Components & Systems Co., Ltd.   {MID: 80}
Fuji Electric Systems, Co., Ltd.   {MID: 198}
Functional Devices, Inc.   {MID: 207}
GD Midea Heating&Ventilating Equipment Co.,Ltd.   {MID: 235}
GE Water Technologies (Osmonics/Lakewood)   {MID: 44}
Gebrüder Trox GmbH   {MID: 70}
Gentec Inc.   {MID: 174}
Gesytec GmbH   {MID: 73}
Gorenje d.d.   {MID: 206}
Grayhill Inc.   {MID: 14}
Grundfos Management A/S   {MID: 85}
Guangdong Rongwen Energy Science and Technology Group Co., Ltd.   {MID: 247}
Gulf Security Technology Co. Ltd.   {MID: 210}
Hach Company   {MID: 41}
HalenSmart Company Limited   {MID: 150}
Heat-Timer Corporation   {MID: 18}
Helvar   {MID: 5}
HERMOS Informatik GmbH   {MID: 163}
Hitachi Ltd.   {MID: 205}
Honeywell International, Inc. (12)   {MID: 12}
Honeywell International, Inc. (12) - Field Programmed   {MID: 131084}
Honeywell International, Inc. (55)   {MID: 55}
Honeywell International, Inc. (E-Mon)   {MID: 241}
Honeywell International, Inc. (Analytics)   {MID: 59}
Hoshizaki America   {MID: 240}
Hubbell Building Automation, Inc.   {MID: 199}
Hubbell Incorporated (Delaware) Wiring Device-Kellems   {MID: 36}
Hüppelux (Hüppe Form)   {MID: 108}
Hunter Douglas   {MID: 231}
HyCal   {MID: 28}
Hyundai Autonet Co., Ltd.   {MID: 139}
IBM   {MID: 3}
IDEC Corporation   {MID: 132}
IEC Intelligent Technologies   {MID: 9}
Infranet Partners Limited   {MID: 169}
Intellicom Innovation AB   {MID: 176}
Intermoco Ltd. (Australon Enterprises)   {MID: 125}
iPLON GmbH   {MID: 60}
ISDE   {MID: 225}
ISH   {MID: 11}
Janitza electronic GmbH   {MID: 193}
Johnson Controls, Inc.   {MID: 17}
Johnson Controls/ESUSA   {MID: 33}
Kaba Benzing GmbH (10)   {MID: 10}
Kaba Benzing GmbH (52)   {MID: 52}
Kaifa Technology Co. Ltd.   {MID: 184}
Kamstrup A/S   {MID: 173}
Kele & Associates   {MID: 84}
Kieback & Peter GmbH & Co KG   {MID: 164}
KITZ Corporation   {MID: 111}
Knorr Brake Corp.   {MID: 127}
Kongsberg anaLogic AS   {MID: 130}
Landert-Motoren AG (Tormax)   {MID: 75}
Legrand   {MID: 120}
Lennox Industries   {MID: 232}
Levec, Inc.   {MID: 77}
Leviton Manufacturing Co.   {MID: 13}
LG Electronics   {MID: 204}
Lighthouse Industries Ltd.   {MID: 50}
Linton Systems   {MID: 43}
Lochinvar Corporation   {MID: 182}
LonMark Technical Staff   {MID: 159}
LonMark - AFS1   {MID: 1047948}
LOYTEC electronics GmbH   {MID: 215}
LS Industrial Systems Co., Ltd.   {MID: 218}
Luminator   {MID: 138}
LUXMATE Controls GmbH   {MID: 106}
M+W Zander Facility Engineering GmbH   {MID: 200}
Mangelberger Elektrotechnik GmbH   {MID: 245}
Matrix Controls Pte. Ltd.   {MID: 107}
McQuay International   {MID: 37}
MEIKOSHA Co., Ltd.   {MID: 126}
Mentzel & Krutmann GmbH   {MID: 58}
Microlab Sistemi S.r.l.   {MID: 166}
MicroTask   {MID: 187}
Mitsubishi Electric Corp.   {MID: 162}
Motorola, Inc.   {MID: 2}
MSR-Electronic-GmbH   {MID: 35}
M-SYSTEM CO., LTD.   {MID: 223}
Nanjing Lianhong Automation Co. Ltd.   {MID: 219}
Network-Controls Pte. Ltd.   {MID: 146}
NeuroLogic Research Corporation   {MID: 98}
NICO Technology, Inc.   {MID: 181}
OAS, Inc.   {MID: 186}
Oiles Corporation   {MID: 194}
Onicon Incorporated   {MID: 208}
ORAS Oy   {MID: 62}
Orion C&I Corporation   {MID: 190}
Osaki Electric Co., Ltd.   {MID: 196}
Panasonic Electric Works Co., Ltd.   {MID: 113}
Paragon Controls   {MID: 226}
PentaControl AG (Bircher Gebäudetechnik AG)   {MID: 40}
PDL Industries Ltd.   {MID: 140}
Philips Lighting B.V.   {MID: 47}
Phoenix Controls Corporation   {MID: 212}
PIC Electronics   {MID: 228}
Plexus Technology Limited   {MID: 141}
Power Measurement Ltd.   {MID: 30}
Programmed Water Technologies / Sloan Valve (56)   {MID: 56}
Programmed Water Technologies / Sloan Valve (183)   {MID: 183}
Programmed Water Technologies / Sloan Valve (243)   {MID: 243}
PureChoice, Inc.   {MID: 188}
Quantum Automation Pte Ltd.   {MID: 217}
Quark Communications Inc.   {MID: 195}
Raypak, Inc. (Rheem)   {MID: 180}
Regin AB   {MID: 122}
Richards-Zeta Building Intelligence   {MID: 53}
Riken Keiki Co., Ltd.   {MID: 72}
Rockwell Automation   {MID: 136}
Safegard Systems Ltd. (NT Software Ltd)   {MID: 48}
Samson AG   {MID: 115}
Samsung Electronics Co., Ltd.   {MID: 191}
Samsung Heavy Industries Co., Ltd.   {MID: 110}
Samsung SDS   {MID: 234}
Schlumberger (SILD)   {MID: 4}
Schneider Electric (Andover)   {MID: 16}
Schneider Electric (CSI)   {MID: 31}
Schneider Electric (Lexel Group)   {MID: 6}
Schneider Electric (Lexel/Merten)   {MID: 224}
Schneider Electric (Moeller/SVEA)   {MID: 21}
Schneider Electric (Merten/SVEA)   {MID: 227}
Schneider Electric (Power)   {MID: 20}
Schneider Electric (TAC AB)   {MID: 19}
Schneider Electric (TAC LLC)   {MID: 22}
Schneider Electric (Viconics Electronics Inc.)   {MID: 197}
Seaboard Process Controls, Inc.   {MID: 49}
Secyourit GmbH   {MID: 246}
Shanghai ChangXiang Computer Co., Ltd   {MID: 179}
Shikoku Instrumentation Co., Ltd.   {MID: 177}
Siemens BT   {MID: 25}
Siemens BT (Korea)   {MID: 114}
Siemens BT (North America and Asia-Pacific)   {MID: 129}
Siemens BT (Staefa Controls USA)   {MID: 105}
Simon, S.A.   {MID: 242}
Siteco Control GmbH   {MID: 220}
Smart Controls   {MID: 15}
Solidyne Corp.   {MID: 201}
Somfy   {MID: 82}
Sontay Open Systems, Ltd.   {MID: 92}
SPI Systems Ltd.   {MID: 216}
SPEGA - Spelsberg Gebaudeautomation GmbH + Co. KG   {MID: 230}
Stifab Farex AB   {MID: 170}
STV Automation - A Division of STV Electronic GmbH   {MID: 250}
Surf Networks, Inc.   {MID: 172}
SysMik GmbH Dresden   {MID: 94}
Telda Electronics   {MID: 102}
Terasaki Electric Co., Ltd.   {MID: 165}
The Watt Stopper   {MID: 167}
Theben HTS AG   {MID: 239}
TMI   {MID: 7}
Toshiba Corporation   {MID: 76}
Toshiba Info Systems (Japan)   {MID: 78}
Toshiba Lighting & Technology Corporation   {MID: 133}
Trane   {MID: 42}
Trend Control Systems Ltd (Novar Trend)   {MID: 29}
Tridium, Inc.   {MID: 142}
Trustbridge   {MID: 244}
TSI Incorporated   {MID: 71}
VaCom Technologies   {MID: 213}
Vacon Plc   {MID: 189}
Vaisala Oy   {MID: 38}
Valvcon Corporation   {MID: 147}
Veris Industries   {MID: 237}
Viessmann Werke GmbH u. Co.   {MID: 128}
Vossloh-Schwabe Deutschland GmbH   {MID: 236}
Voyant Solutions, LLC   {MID: 221}
Wabtec Corporation   {MID: 121}
WAGO   {MID: 112}
WAREMA electronic GmbH   {MID: 87}
Watanabe Electric Industry Co., Ltd.   {MID: 123}
Yamatake Corporation   {MID: 95}
Yaskawa Electric America   {MID: 57}
Yokogawa Electric Corporation   {MID: 67}
York International   {MID: 119}
Zone Controls   {MID: 86}
zzz - reserved-0004F   {MID: 79}
zzz - reserved-00058   {MID: 88}
zzz - reserved-0006D   {MID: 109}
zzz - reserved-00086   {MID: 134}
zzz - reserved-0FF00   {MID: 65280}

top


Device Classes

(Device Classes that have hyperlinks for their numbers are also Functional Profiles that can be viewed by clicking the link.  Device Classes marked with “*” are not valid for new designs.)


50.00 - Access/Intrusion/Monitoring
50.10 --- Intercom
50.11 --- Alphanumeric LCD/Led Display
50.12 --- PS/2 Interface
50.20 --- Motorized Strike Plate
50.30 --- Reader
50.31 -------- Legic Reader
50.32 -------- Barcode Reader
50.33 -------- Magcard Reader
50.34 -------- Inductive Reader
50.35 -------- Identifier Sensor
50.40 --- Logic Cylinder
50.50 --- Remote Door Manager
50.51 -------- Entry/Exit
50.60 --- Event Memory
50.70 --- Elevator Access Controller
50.80 --- Arming Station
50.90 --- Telephone Controls
50.91 -------- Modem Controller
50.92 -------- Telephone Directory


170.00 - Automated Food Service
172.00 --- Beverage Control and Monitoring
172.10 -------- Heated-Beverage Control and Monitoring
172.11 ---------------- Coffee-Making Control and Monitoring
172.20 -------- Cooled-Beverage Control and Monitoring


20.00 - Energy Management
20.10 --- Load-Shed Module (LSM)
20.11 -------- Load-Shed Module with power sensor
20.12 -------- Load-Shed Module with energy monitoring
20.20 --- Circuit Breaker
20.30 --- Scheduler with Presets
21.00 --- 3-Phase Energy Meter
21.01 -------- 3-Phase Demand Power Meter
21.02 -------- 3-Phase Demand Ammeter
21.03 -------- 3-Phase Power Meter
21.04 -------- 3-Phase Ammeter
21.05 -------- 3-Phase Voltmeter
21.10 --- Utility Data Logger Register
21.50 --- Multi-Phase Energy Meter
21.51 -------- Multi-Phase Demand Power Meter
21.52 -------- Multi-Phase Demand Ammeter
21.53 -------- Multi-Phase Power Meter
21.54 -------- Multi-Phase Ammeter
21.55 -------- Multi-Phase Voltmeter
22.00 --- Automated Meter Reader (AMR)
22.01 -------- Utility Meter


110.00 - Fire & Smoke Devices
110.01 --- Fire Smoke Damper Actuator
110.02 --- Smoke (Intelligent) Fire Initiator
110.03 --- Smoke (Conventional) Fire Initiator
110.04 --- Thermal Fire Initiator
110.05 --- Pull-Station Fire Initiator
110.06 --- Audible Fire Indicator
110.07 --- Visible Fire Indicator
110.08 --- Manual Call Point
110.09 --- Fireman Call Point
110.10 --- Universal Fire Initiator
110.11 --- Universal Fire Indicator


70.00 - Gateways
70.10 --- Telephone Gateway
70.11 -------- Alphanumeric Notifier
70.20 --- Internet Gateway
70.21 -------- Internet Web Server
70.22 -------- Internet Information Server
70.30 --- PLC Interface
71.00 --- BMS Gateway
71.10 --- Fire & Smoke Gateways
71.30 --- Industrial Gateways
72.10 --- Refrigeration Gateways
72.20 --- Energy Management Gateways
72.30 --- Lighting Gateways
72.40 --- Vertical/Conveyor Transportation Gateways
72.50 --- Access/Intrusion/Monitoring Gateways
72.80 --- HVAC Gateways
72.90 --- Transportation Gateways
72.91 -------- Signage/Enunciation/Display Systems


07.00 - Generic Actuators


06.00 - Generic Controllers


08.00 - Generic Human-Machine Interfaces (HMIs)
08.10 --- Remote Control
08.11 -------- IR Remote Control
08.12 -------- RF Remote Control
08.20 --- Panel Interface
08.21 -------- Touch-Screen Panel
08.22 -------- LCD/LED Panel HMI


80.00 - HVAC
80.10 --- VAV Controller
80.11 -------- Dual-Duct VAV Controller
80.20 --- Fan Coil Unit Controller
80.30 --- Roof Top Unit Controller
80.40 --- Chiller
80.50 --- Heat Pump *
80.51 -------- Heat Pump with Temperature Control
80.60 --- Thermostat
80.70 --- Chilled Ceiling Controller
80.80 --- Unit Ventilator Controller
80.90 --- Space Comfort Control Command Module
81.00 --- SCC - Template for Controller-based nodes *
81.10 --- Damper Actuator
81.11 -------- Modulating Damper Actuator
81.20 --- Pump Controller
81.30 --- Valve Controls
81.31 -------- Valve Positioner (HVAC)
               Profile-Specific Usage:
                00 -- Programmed Actuator Characteristic
                01 -- Programmed Actuator Characteristic with Emergency Mode function
                20 -- Calculated Actuator Characteristic
                21 -- Calculated Actuator Characteristic with Emergency Mode function
81.35 -------- Linear Valve Actuator
82.00 --- Plant Controller
83.00 --- Burner and Boiler Controllers
83.01 -------- Boiler Controller
84.00 --- Product Controllers
85.00 --- SCC - Generic
85.01 -------- SCC - Fan Coil
85.02 -------- SCC - Variable Air Volume
85.03 -------- SCC - Heat Pump
85.04 -------- SCC - Rooftop Unit
85.05 -------- SCC - Unit Ventilator
85.06 -------- SCC - Chilled Ceiling
85.07 -------- SCC - Radiator
85.08 -------- SCC - Air-Handling Unit
85.09 -------- SCC - Self-Contained Unit
85.10 -------- SCC - (reserved, 85.10)
85.29 -------- SCC - (reserved, 85.29)
85.40 --- Wall Unit
85.50 --- Unit Heater
86.00 --- Air Handling
86.10 -------- Discharge-Air Controller
86.20 -------- Air Handling Critical-Safety Devices
86.21 ---------------- Fume Hood Face-Velocity Controller
86.22 ---------------- Room Direct-Pressure Controller


05.00 - I/O
05.01 --- Multi-I/O module
05.03 --- Multi-Output Module
05.10 --- 8-Channel configurable I/O
05.11 --- 8-Channel voltage input
05.12 --- 8-Channel current input
05.13 --- 8-Channel digital input
05.14 --- 4 Digital input, 4 digital output
05.15 --- 8-Channel Digital Output
05.16 --- 8-Channel switch input
05.20 --- Analog Input
05.21 --- Analog Output
05.22 --- Extended Analog Input
05.23 --- Extended Analog Output
05.24 --- Generic Analog Input
05.25 --- Generic Analog Output
05.30 --- 6-Channel configurable I/O
05.31 --- 4 Digital input, 2 digital output
05.32 --- 6 Analog outputs U/I
05.40 --- Digital I/O
05.41 --- 7 Digital input, 4 digital output
05.42 --- Digital Input
05.43 --- Digital output
05.48 --- Digital Input Node
05.50 --- 2-Channel configurable I/O
05.51 --- 2-Channel digital input
05.52 --- 2-Channel digital output
05.53 --- 2 Digital input, 2 digital output
05.54 --- 2 Analog input
05.55 --- 2 Analog output
05.60 --- 4-Channel configurable I/O
05.61 --- 4-Channel digital input
05.62 --- 4-Channel digital output
05.63 --- 4 Analog input
05.64 --- 4 Analog output
05.70 --- 12-Channel configurable I/O
05.71 --- 12 Digital inputs Vdc
05.72 --- 12 Digital outputs Vdc
05.73 --- 12 Digital inputs 100-250 Vac
05.74 --- 12 Digital input 12-48 Vac/dc opto iso
05.75 --- 12 Analog inputs U/I/Pt100
05.80 --- Multi-Channel I/O
05.83 --- Multiple Digital Inputs 100-250 Vac


130.00 - Industrial
131.10 --- Generator Set
131.20 --- Automatic Transfer Switch
132.10 --- Programmable Controller
135.00 --- Filtration Systems
135.10 -------- Gas Filtration
135.11 ---------------- Fan-Filter Unit
135.20 -------- Liquid Filtration
135.30 -------- Solid Filtration
138.10 --- Remote Miniature Circuit Breaker
138.11 --- Circuit Breaker - Other
138.20 --- PLC Gateway for specific device *
138.30 --- Power Supplies
138.31 -------- Power Supply (less than 5V)
138.32 -------- Power Supply (less than 15V)
138.33 -------- Power Supply (less than 50V)
138.34 -------- Power Supply (less than 100V)
138.35 -------- Power Supply (less than 200V)
138.36 -------- Power Supply (less than 500V)
138.37 -------- Power Supply (less than 1000V)


30.00 - Lighting
30.10 --- Dimmer 1-10V
30.11 -------- 8-Channel dimmer 1-10V
30.12 -------- 3-Channel dimmer 1-10V
30.20 --- Transistor Dimmer
30.30 --- Thyristor Dimmer
30.40 --- Lamp Actuator
30.41 --- ISI Lamp Actuator
30.50 --- Constant Light Controller
30.71 --- Occupancy controller
32.00 --- Switch
               Profile-Specific Usage:
                00 -- Discrete Output (ON/OFF)
                01 -- Discrete Output (ON/OFF) with Feedback Input
                02 -- Discrete Output (ON/OFF) with Setting Control
                03 -- Discrete Output (ON/OFF) with Feedback Input and Setting Control
                20 -- Variable Output
                21 -- Variable Output with Feedback Input
                22 -- Variable Output with Setting Control
                23 -- Variable Output with Feedback Input and Setting Control
32.01 -------- 4-Switch relay
32.02 -------- Multi-switch/multi-sensor
32.03 -------- Switch/sensor
32.50 --- Scene Panel
32.51 --- Scene Controller
32.52 --- Partition Wall Controller
32.53 --- ISI Keypad
33.00 --- Real-Time Keeper
33.01 -------- Real-Time-Based Scheduler
34.00 --- Lighting Controller
34.01 -------- Lighting Panel Controller
35.00 --- Outdoor Lighting
35.12 -------- Outdoor Luminair Controller
35.14 -------- Smart Luminair Controller


60.00 - Motor Controls
60.10 --- Variable-Speed Motor Drive
61.00 --- Sunblind Motor *
61.01 -------- Sunblind Motor Controller *
61.10 --- Sunblind Actuator
               Profile-Specific Usage:
                00 -- Feedback Output
                01 -- Control (daisy chain) Output
                02 -- Feedback Output and Control (daisy chain) Output
61.11 --- Sunblind Controller
61.12 --- ISI Sunblind Actuator
               Profile-Specific Usage:
                00 -- Feedback Output
                01 -- Control (daisy chain) Output
                02 -- Feedback Output and Control (daisy chain) Output
54.10 --- AC Drive (v3.0 Products Only) *


01.00 - Network Infrastructure
01.01 --- ISO/IEC 14908-1 Router
01.02 --- Network Interfaces
01.03 --- Network Managers
01.04 --- Data Logger
01.05 --- Microprocessor Interfaces
01.10 --- Foreign System Connection Sensor
01.20 --- Scheduler
01.30 --- Diagnostic Tools
01.31 -------- Channel Diagnostics
01.32 ---------------- Channel Monitor
01.36 -------- Device Monitor
01.37 -------- Channel Continuity Monitor
01.40 --- Generic Controller
01.60 --- Device Manager


04.00 - Programmables
04.01 --- Programer
04.10 --- Static Programmable
04.50 --- Dynamic Programmable


100.00 - Refrigeration
100.10 --- Defrost Controller
100.11 --- Evaporator Controller
100.12 --- Refrigeration Thermostat Controller
100.13 --- Railheat Controller


180.00 - Semiconductor Fabrication
180.10 --- Semiconductor Sensors
180.11 -------- Semiconductor Sensor-AI
180.12 -------- Semiconductor Sensor-AI-AT
180.13 -------- Semiconductor Sensor-AI-MF
180.14 -------- Semiconductor Sensor-AI-Aux
180.15 -------- Semiconductor Sensor-AI-Counter
180.16 -------- Semiconductor Sensor-AI-LCS
180.17 -------- Semiconductor Sensor-AI-SLS
180.18 -------- Semiconductor Sensor-BI
180.19 -------- Semiconductor Sensor-BI-TH
180.20 -------- Semiconductor Sensor-BI-TH-EP
180.30 --- Semiconductor Actuators
180.31 -------- Semiconductor Actuator-AO
180.32 -------- Semiconductor Actuator-AO-MF
180.33 -------- Semiconductor Actuator-BO
180.34 -------- Semiconductor Actuator-EO
180.50 --- Semiconductor Controllers
180.51 -------- Semiconductor Controller
180.70 --- Semiconductor I/O
180.71 -------- Semiconductor Single-Input Single-Output
180.72 -------- Semiconductor Single-Input Single-Output Setpoint
180.80 --- Semiconductor Assemblies
180.81 -------- Semiconductor Assembly
180.82 -------- Semiconductor Assembly-MFM
180.83 -------- Semiconductor Assembly-MFC
180.84 -------- Semiconductor Assembly-ISPM1
180.85 -------- Semiconductor Assembly-ISPM2
180.86 -------- Semiconductor Assembly-ISPM3
180.87 -------- Semiconductor Assembly-ISPM4
180.88 -------- Semiconductor Assembly-ISPM5
180.89 -------- Semiconductor Assembly-ISPM6
180.90 -------- Semiconductor Assembly-ISPM7
180.91 -------- Semiconductor Assembly-ISPM8
180.92 -------- Semiconductor Assembly-ISPM9
180.93 -------- Semiconductor Assembly-ISPM48
180.94 -------- Semiconductor Assembly-EP1
180.95 -------- Semiconductor Assembly-EP2
180.96 -------- Semiconductor Assembly-EP3
180.97 -------- Semiconductor Assembly-EP4


10.00 - Sensors
10.10 --- Light Sensor
10.15 --- Global Solar Radiation Sensor
10.20 --- Time Sensor
10.30 --- Pressure Sensor
10.40 --- Temperature Sensor
10.41 -------- Temperature & Humidity
10.42 --- Frost Sensor
10.50 --- Relative Humidity
10.51 --- Rain Sensor
10.60 --- Occupancy Sensor
10.61 --- ISI Occupancy Sensor
10.70 --- CO2 Sensor
10.80 --- Gas Concentration Sensor
10.81 --- PH Sensor
10.82 --- Conductivity Sensor
10.83 --- Air-Velocity Sensor
10.90 --- Multi-Function Sensor


90.00 - Transportation
90.10 --- Door Controls
91.00 --- Audio Systems
91.10 -------- Railway Audio Systems
91.11 ---------------- Railcar Audio Controller
91.12 ---------------- Railcar Audio Sensor
95.00 --- Electric Vehicles
95.10 -------- Billing Systems
95.20 -------- Electric Vehicle Supply Equipment
95.21 ---------------- EVSE Single, Domestic
95.22 ---------------- EVSE Multiple, Domestic
95.25 ---------------- EVSE, Commercial
95.30 ---------------- EVSE, Retail


140.00 - Vertical/Conveyer Transportation (Elevator)
140.10 --- Elevator/Lift Indicators
140.11 -------- Elevator/Lift Position Indicator and Message Display
140.12 -------- Elevator/Lift Hall Lantern
140.13 -------- Elevator/Lift Arrival Gong
140.14 -------- Elevator/Lift Car-Direction Lantern
140.40 --- Vertical/Conveyer Transportation System Interfaces
140.41 -------- Elevator/Lift Fire-Systems Port
140.60 --- Vertical/Conveyer-Transportation Communication Devices
140.61 -------- Elevator/Lift Voice Announcer


150.00 - Whitegoods
150.10 --- Clothes
150.11 -------- Clothes Washer, Domestic
150.12 -------- Clothes Dryer, Domestic
150.13 -------- Clothes Iron, Domestic
150.14 -------- Clothes Press, Domestic
150.15 -------- Clothes Steamer, Domestic
150.30 --- Cooking
150.31 -------- Oven, Domestic
150.32 -------- Specialty Oven, Domestic
150.33 -------- Microwave or IR Oven, Domestic
150.34 -------- Electric or Inductive Range, Domestic
150.35 -------- Gas Range, Domestic
150.50 --- Storage
150.51 -------- Refrigerator, Domestic
150.52 -------- Deep Freezer, Domestic
150.53 -------- Beverage Cabinet, Domestic
150.54 -------- Dry Cabinet, Domestic
150.70 --- Miscellaneous
150.71 -------- Dishwasher, Domestic
150.72 -------- In-Sink Disposal, Domestic
150.73 -------- Trash Compactor, Domestic


40.00 - Wiring Devices
40.10 --- 1-Pushbutton
40.11 --- 2-Pushbutton
40.12 --- 3-Pushbutton
40.13 --- 4-Pushbutton
40.50 --- Rotary control
41.00 --- AC Load Relay
42.00 --- Controlled Receptacle
43.10 --- Hardwired Gas Detection Shutdown
43.11 --- Hardwired Fire Alarm Shutdown
43.12 --- Hardwired Recirculation
43.13 --- Hardwired Full Ventilation
43.14 --- Hardwired Safety Instrumented System - SIS

* (Device Classes marked are not valid for new designs)

top


Usage (Device Subclass)

Commercial { 3}
Connectivity { 1}
General { 10}
Industrial { 2}
Industrial/Commercial { 4}
Medical { 9}
Network Management { 0}
Programmable { 63}
Residential { 5}
Residential/Commercial { 6}
Telecommunications { 8}
Transportation { 7}
Utility { 11}

top


Channel Types

(Channels in gray text are not approved for use as the externally available channel on a Certified device)

FO-20L   {ID: 152}    ANSI/CEA-709.4
FO-20S   {ID: 24}    ANSI/CEA-709.4
IP-852   {ID: 154}    ISO/IEC 14908-4
PL-10   {ID: 9}    LonMark Interoperability Guidelines
PL-20A   {ID: 15}    LonMark Interoperability Guidelines
PL-20C   {ID: 16}    ISO/IEC 14908-3
PL-20N   {ID: 17}    ISO/IEC 14908-3
PL-30   {ID: 18}    LonMark Interoperability Guidelines
TP/FT-10   {ID: 4}    ISO/IEC 14908-2
TP/RS485-39   {ID: 5}    ANSI/TIA/EIA-485-A
TP/XF-1250   {ID: 3}    LonMark Interoperability Guidelines
TP/XF-78   {ID: 1}    LonMark Interoperability Guidelines
Backplane {ID: 255}    Echelon Corporation
Custom {ID: 30}   
DC-1250 {ID: 29}    Echelon Corporation
DC-1250/SECD {ID: 145}    Echelon Corporation
DC-2500/SECD {ID: 146}    Echelon Corporation
DC-625 {ID: 28}    Echelon Corporation
DC-78 {ID: 27}    Echelon Corporation
IP-10L {ID: 25}    Echelon Corporation
IP-10W {ID: 26}    Echelon Corporation
IP-852.1 {ID: 0}    ANSI/CEA-852.1
IR-10 {ID: 23}    Echelon Corporation
IR-20 {ID: 22}   
Pyxos-FT {ID: 254}    Echelon Corporation
RF-10 {ID: 7}    Echelon Corporation
RF-20 {ID: 21}   
TP/FT (reserved) {ID: 6}   
TP/RS485-1250 {ID: 11}    ANSI/TIA/EIA-485-A
TP/RS-485-625 {ID: 10}    ANSI/TIA/EIA-485-A
TP/RS485-78 {ID: 12}    ANSI/TIA/EIA-485-A

top


See the LonMark Application Layer Interoperability Guidelines for more information about SPIDs.


 
 
 
© 2007-2014 LonMark International. Terms of Use | Privacy Policy (“Cookie”) cookie settings: view/edit

  Download the XML File
spidData.xml File


For the actual spidData.xml file, click the image above, then choose to save the file when prompted.

Please note that your Development or Network-Management Tool may require this XML file be placed in C:\LONWORKS\TYPES or a different directory.

Please check your tool's documentation to see how it may support this file.