SCPTcoolSetpt

Overview:

Cooling setpoint..  The default setpoint for the leaving chilled water temperature in cooling mode when the default behavior selector is set to zero. 

This input configuration network variable establishes the default setpoint for the leaving chilled water temperature, when the SCPTdefltBehave configuration property is set equal to zero (0) or is not defined. When the SCPTdefltBehave configuration property is set equal to one (1), the manufacturer-specified values are used instead.


Details:

Resource Set: Standard 00:00:00:00:00:00:00:00-0
Index: 75
Obsolete: no
Size: 2
Programmatic Name: SCPTcoolSetpt
Minimum: -40,00
Maximum: 48,80
Default: 7,20
Neuron C Type:
SNVT_temp_p
Formats:

SCPTcoolSetpt#SI:  text("%f", *1+0(0:854))

SCPTcoolSetpt#US:  text("%f", *1.8+32(0:855))

Used by:

SFPTchiller