SFPTenergyModeSelection

Energy mode selection..   

A detailed description of the function profile with all inputs and outputs as well as the configuration parameters can be found at the VDI - Verein der Deutschen Ingineure. The Web Link is:

VDI - Room control functions (RA functions)
 

Network Variables

Configuration Properties

nviBmsEnergLevel
nviRoomOccup
nviWindowPos
nvoCalcEnergMode

cpMaxSendTime

cpMaxReceiveTime

 

Details:

Resource Set: Standard 00:00:00:00:00:00:00:00-0
Index: 145
Obsolete: no
Key: 16518
Inheriting: no


Mandatory Network Variables

nviBmsEnergLevelEnergy level from building management system.:    
Member Number: 1
Base type:
SNVT_occupancy
Direction: input
Service: any
nviRoomOccupOccupancy:    
Member Number: 2
Base type:
SNVT_occupancy
Direction: input
Service: any
nviWindowPosWindow state.:    
Member Number: 3
Base type:
SNVT_switch
Direction: input
Service: any
nvoCalcEnergModeCalculated energy mode.:    
Member Number: 4
Base type:
SNVT_occupancy
Direction: output
Service: any


Mandatory Configuration Properties

cpMaxSendTimeMaximum send time.:   The maximum period of time between consecutive transmissions of the current value. 
Member Number: 2
Base type:
SCPTmaxSendTime
Applies to nvoCalcEnergMode
Array: not permitted
Default: 300,0


Optional Configuration Properties

cpMaxReceiveTimeMaximum receive time.:   The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.  
Member Number: 1
Base type:
SCPTmaxRcvTime
Applies to nviWindowPos
Array: not permitted
Default: 60,0