SFPThvacRelativeHumiditySensor

HVAC Relative Humidity Sensor..  Relative humidity sensor designed for HVAC applications. 
 

Network Variables

Configuration Properties

nvoHVACRH

nvo8bitRH
nvoFloatRH

nciMaxSendTime
nciMinSendTime
nciRHMinDelta

nciRHOffset

 

Details:

Resource Set: Standard 00:00:00:00:00:00:00:00-0
Index: 11
Obsolete: no
Key: 1050
Inheriting: no
Principal Variable nvoHVACRH


Mandatory Network Variables

nvoHVACRHRelative humidity.:   The relative humidity using the level-percent data type. 
Member Number: 1
Base type:
SNVT_lev_percent
Direction: output
Service: any


Optional Network Variables

nvo8bitRHRelative humidity.:   The relative humidity using the short fixed point data type. 
Member Number: 2
Base type:
SNVT_lev_cont
Direction: output
Service: any
nvoFloatRHRelative humidity.:   The relative humidity using floating point data type. 
Member Number: 3
Base type:
SNVT_lev_cont_f
Direction: output
Service: any


Mandatory Configuration Properties

nciMaxSendTimeMaximum send time.:   Controls the maximum period of time before the output values are transmitted. 
Member Number: 1
Base type:
SCPTmaxSendTime
Applies to SFPThvacRelativeHumiditySensor
Array: not permitted
Default: 300,0
nciMinSendTimeMinimum send time.:   Controls the minimum period of time between output value transmissions. 
Member Number: 2
Base type:
SCPTminSendTime
Applies to SFPThvacRelativeHumiditySensor
Array: not permitted
Default: 5,0
nciRHMinDeltaSend on delta.:   The minimum change required to force transmission of the output value. 
Member Number: 3
Base type:
SCPTminDeltaRH
Applies to nvoHVACRH
Array: not permitted


Optional Configuration Properties

nciRHOffsetRelative humidity offset.:   Used to calibrate external hardware with additive offset after transformation. 
Member Number: 4
Base type:
SCPToffsetRH
Applies to nvoHVACRH
Array: not permitted