SFPTpriorityControl

Priority control..   

A detailed description of the function profile with all inputs and outputs as well as the configuration parameters can be found at the VDI - Verein der Deutschen Ingineure. The Web Link is:

VDI - Room control functions (RA functions)
 

Network Variables

Configuration Properties

nviAutoCmd
nviMaintCmd
nviManCmd
nviWeathProtCmd
nviWindowPos
nvoPrioSunblCmd

cpPriorityOrder

cpMaxReceiveTimeWeathProtCmd
cpMaxReceiveTimeWindowPos
cpMaxSendTime

 

Details:

Resource Set: Standard 00:00:00:00:00:00:00:00-0
Index: 138
Obsolete: no
Key: 16511
Inheriting: no


Mandatory Network Variables

nviWindowPosWindow position.:    
Member Number: 1
Base type:
SNVT_switch
Direction: input
Service: any
nviWeathProtCmdPositioning command from weather protection.:    
Member Number: 2
Base type:
SNVT_setting
Direction: input
Service: any
nviMaintCmdMaintenance position setting command.:    
Member Number: 3
Base type:
SNVT_setting
Direction: input
Service: any
nviManCmdManual position setting command.:    
Member Number: 4
Base type:
SNVT_setting
Direction: input
Service: any
nviAutoCmdAutomatic position setting command.:    
Member Number: 5
Base type:
SNVT_setting
Direction: input
Service: any
nvoPrioSunblCmdPriority sunblind command.:    
Member Number: 6
Base type:
SNVT_setting
Direction: output
Service: any


Mandatory Configuration Properties

cpPriorityOrderUNVT Flag.:   Defines whether the NV is of SNVT (=0) or UNVT (=1) 
Member Number: 1
Base type:
SCPTnvPriority
Applies to SFPTpriorityControl
Array: not permitted
Default: 0 0


Optional Configuration Properties

cpMaxSendTimeMaximum send time.:   The maximum period of time between consecutive transmissions of the current value. 
Member Number: 2
Base type:
SCPTmaxSendTime
Applies to nvoPrioSunblCmd
Array: not permitted
Default: 20,0
cpMaxReceiveTimeWeathProtCmdMaximum receive time.:   The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.  
Member Number: 3
Base type:
SCPTmaxRcvTime
Applies to nviWeathProtCmd
Array: not permitted
Default: 0,0
cpMaxReceiveTimeWindowPosMaximum receive time.:   The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.  
Member Number: 4
Base type:
SCPTmaxRcvTime
Applies to nviWindowPos
Array: not permitted
Default: 0,0