SFPTtemperatureControl

Temperature control..   

A detailed description of the function profile with all inputs and outputs as well as the configuration parameters can be found at the VDI - Verein der Deutschen Ingineure. The Web Link is:

VDI - Room control functions (RA functions)
 

Network Variables

Configuration Properties

nviCalcCtrlFunc
nviCalcEnergMode
nviCalcTempSetpts
nviRoomTemp
nvoCalcDrivePos

nviCalcFanSpeed
nvoDriveLockPos

cpMaxReceiveTimeRoomTemp
cpMaxSendTimeCalcDrivePos

cpMaxReceiveTimeCalcFanSpeed
cpMaxSendTimeDriveLockPos

 

Details:

Resource Set: Standard 00:00:00:00:00:00:00:00-0
Index: 152
Obsolete: no
Key: 16522
Inheriting: no


Mandatory Network Variables

nviCalcCtrlFuncCalculated control function.:    
Member Number: 1
Base type:
SNVT_hvac_mode
Direction: input
Service: any
nviCalcEnergModeCalculated energy mode.:    
Member Number: 2
Base type:
SNVT_occupancy
Direction: input
Service: any
nviCalcTempSetptsCalculated temperture setpoints.:    
Member Number: 3
Base type:
SNVT_temp_setpt_2
Direction: input
Service: any
nviRoomTempTemperature:    
Member Number: 4
Base type:
SNVT_temp_p
Direction: input
Service: any
nvoCalcDrivePosCalculated drive position.:   Level percent. SNVT_switch should be used instead of SNVT_lev_percent, with the exception of network variables that are used to communicate a percentage value and that require the additional resolution provided by SNVT_lev_percent; or for network variable members of functional profiles that are designed primarily for interfacing with SNVT_lev_percent members of other profiles.  
Member Number: 5
Base type:
SNVT_lev_percent
Direction: output
Service: any


Optional Network Variables

nviCalcFanSpeedCalculated fan speed.:    
Member Number: 6
Base type:
SNVT_switch
Direction: input
Service: any
nvoDriveLockPosDrive lock position.:   Level percent. SNVT_switch should be used instead of SNVT_lev_percent, with the exception of network variables that are used to communicate a percentage value and that require the additional resolution provided by SNVT_lev_percent; or for network variable members of functional profiles that are designed primarily for interfacing with SNVT_lev_percent members of other profiles.  
Member Number: 7
Base type:
SNVT_lev_percent
Direction: output
Service: any


Mandatory Configuration Properties

cpMaxSendTimeCalcDrivePosMaximum send time.:   The maximum period of time between consecutive transmissions of the current value. 
Member Number: 1
Base type:
SCPTmaxSendTime
Applies to nvoCalcDrivePos
Array: not permitted
Default: 300,0
cpMaxReceiveTimeRoomTempMaximum receive time.:   The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.  
Member Number: 3
Base type:
SCPTmaxRcvTime
Applies to nviRoomTemp
Array: not permitted
Default: 900,0


Optional Configuration Properties

cpMaxSendTimeDriveLockPosMaximum send time.:   The maximum period of time between consecutive transmissions of the current value. 
Member Number: 5
Base type:
SCPTmaxSendTime
Applies to nvoDriveLockPos
Array: not permitted
Default: 300,0
cpMaxReceiveTimeCalcFanSpeedMaximum receive time.:   The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.  
Member Number: 6
Base type:
SCPTmaxRcvTime
Applies to nviCalcFanSpeed
Array: not permitted
Default: 30,0