SFPTvolumeFlowControl

Volume flow control..   

A detailed description of the function profile with all inputs and outputs as well as the configuration parameters can be found at the VDI - Verein der Deutschen Ingineure. The Web Link is:

VDI - Room control functions (RA functions)
 

Network Variables

Configuration Properties

nviBMSPressMode
nviSensAirFlow
nviSetptAirFlow
nvoCalcDrivePos

nvoExtrDrivePos

cpMaxReceiveTime
cpMaxSendTimeCalcDrivePos
cpMultiplierOffsetFlow

cpControlResponse
cpMaxSendTimeExtrDrivePos

 

Details:

Resource Set: Standard 00:00:00:00:00:00:00:00-0
Index: 157
Obsolete: no
Key: 16530
Inheriting: no


Mandatory Network Variables

nviBMSPressModeBMS Pressure mode.:    
Member Number: 1
Base type:
SNVT_hvac_emerg
Direction: input
Service: any
nviSetptAirFlowSetpoints air temperature.:    
Member Number: 2
Base type:
SNVT_lev_percent
Direction: input
Service: any
nviSensAirFlowSensor air flow.:    
Member Number: 3
Base type:
SNVT_flow
Direction: input
Service: any
nvoCalcDrivePosCalculated drive position.:    
Member Number: 4
Base type:
SNVT_lev_percent
Direction: output
Service: any


Optional Network Variables

nvoExtrDrivePosPercentage level.:   Level percent. SNVT_switch should be used instead of SNVT_lev_percent, with the exception of network variables that are used to communicate a percentage value and that require the additional resolution provided by SNVT_lev_percent; or for network variable members of functional profiles that are designed primarily for interfacing with SNVT_lev_percent members of other profiles.  
Member Number: 5
Base type:
SNVT_lev_percent
Direction: input
Service: any


Mandatory Configuration Properties

cpMultiplierOffsetFlowAir flow offset.:   Offset value used to calculate the active airflow setpoint by adding nciFlowOffset to nviAirFlowSetpt. 
Member Number: 1
Base type:
SCPToffsetFlow
Applies to SFPTvolumeFlowControl
Array: not permitted
Default: 0
cpMaxReceiveTimeMaximum receive time.:   The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.  
Member Number: 2
Base type:
SCPTmaxRcvTime
Applies to nviSetptAirFlow
Array: not permitted
Default: 0,0
cpMaxSendTimeCalcDrivePosMaximum send time.:   The maximum period of time between consecutive transmissions of the current value. 
Member Number: 3
Base type:
SCPTmaxSendTime
Applies to nvoCalcDrivePos
Array: not permitted
Default: 0,0


Optional Configuration Properties

cpMaxSendTimeExtrDrivePosMaximum send time.:   The maximum period of time between consecutive transmissions of the current value. 
Member Number: 4
Base type:
SCPTmaxSendTime
Applies to nvoExtrDrivePos
Array: not permitted
Default: 0,0
cpControlResponse:    
Member Number: 5
Base type:
SCPTpiCoefficients
Applies to SFPTvolumeFlowControl
Array: not permitted
Default: 0,00 0