SFPTairTemperatureSensor

Air temperature sensor..   

A detailed description of the function profile with all inputs and outputs as well as the configuration parameters can be found at the VDI - Verein der Deutschen Ingineure. The Web Link is:

VDI - Room control functions (RA functions)
 

Network Variables

Configuration Properties

nvoSensAirTemp

cpMaxSendTime
cpMinDeltaTemp
cpMinSendTime

cpTmpOffset

 

Details:

Resource Set: Standard 00:00:00:00:00:00:00:00-0
Index: 111
Obsolete: no
Key: 16104
Inheriting: no


Mandatory Network Variables

nvoSensAirTempAir temperature.:    
Member Number: 1
Base type:
SNVT_temp_p
Direction: output
Service: any


Mandatory Configuration Properties

cpMaxSendTimeMaximum send time.:   The maximum period of time between consecutive transmissions of the current value. 
Member Number: 2
Base type:
SCPTmaxSendTime
Applies to nvoSensAirTemp
Array: not permitted
Default: 0,0
cpMinDeltaTempMinimum delta temperature.:   The minimum change in temperature required to be treated as significant. 
Member Number: 3
Base type:
SCPTminDeltaTemp
Applies to nvoSensAirTemp
Array: not permitted
Minimum: 0,00
Default: 0,00
cpMinSendTimeMinimum send time.:   The minimum period of time between consecutive transmissions of the current value. 
Member Number: 4
Base type:
SCPTminSendTime
Applies to nvoSensAirTemp
Array: not permitted
Default: 0,0


Optional Configuration Properties

cpTmpOffsetTemperature offset.:   Temperature offset for calibration. 
Member Number: 1
Base type:
SCPTtempOffset
Applies to SFPTairTemperatureSensor
Array: not permitted
Default: 0,00