SCPTminDeltaTemp

Overview:

Minimum delta temperature..  The minimum change in temperature required to be treated as significant. 

This configuration property sets the minimum temperature change required before the associated output network variable is updated.


Details:

Resource Set: Standard 00:00:00:00:00:00:00:00-0
Index: 64
Obsolete: no
Size: 2
Programmatic Name: SCPTminDeltaTemp
Minimum: 0,00
Default: 0,00
Neuron C Type:
SNVT_temp_p
Formats:

SCPTminDeltaTemp#SI:  text("%f", *1+0(0:854))

SCPTminDeltaTemp#US:  text("%f", *1.8+0(0:855))

Used by:

SFPTairTemperatureSensor  SFPTdamperActuator  SFPThvacTempSensor  SFPTsccCommandModule  SFPTthermostat