SFPTgeneratorSet

Generator Set..  Used to control a generator set (genset) for power generation in primary or secondary systems. 
 

Network Variables

Configuration Properties

nviFaultResetCmd
nviStartCmd
nvoFaultStatus
nvoRunStatus

nviShutdownCmd
nvoBattery
nvoCurrent
nvoEngineRunTime
nvoEngineSpeed
nvoEngineStarts
nvoEngineTemp
nvoFrequency
nvoGenEnergy
nvoNFPA110Annun
nvoOilPressure
nvoPowerFactor
nvoRealPower
nvoVoltageLL
nvoVoltageLN

nciMaxSendTime

nciLocation
nciMaxSendTimeNV03
nciMaxSendTimeNV13
nciMaxSendTimeNV14
nciMaxSendTimeNV15
nciMaxSendTimeNV16
nciMaxSendTimeNV17
nciMaxSendTimeNV19

 

Details:

Resource Set: Standard 00:00:00:00:00:00:00:00-0
Index: 56
Obsolete: no
Key: 13110
Inheriting: no


Mandatory Network Variables

nviStartCmdStart Command Input.:   start and stop the generator set. 
Member Number: 1
Base type:
SNVT_switch
Direction: input
Service: any
nviFaultResetCmdFault Reset Command Input.:   reset or clear a generator set fault. 
Member Number: 2
Base type:
SNVT_switch
Direction: input
Service: any
nvoRunStatusRun Status Output.:   running at rated speed and voltage and is ready to accept load. 
Member Number: 3
Base type:
SNVT_switch
Direction: output
Service: acknowledged
nvoFaultStatusFault Status Output.:   report the presence of a generator set fault. 
Member Number: 4
Base type:
SNVT_switch
Direction: output
Service: acknowledged


Optional Network Variables

nviShutdownCmdShutdown Command Input.:   emergency, unconditional shutdown/disable of run. 
Member Number: 5
Base type:
SNVT_switch
Direction: input
Service: any
nvoNFPA110AnnunNFPA 110 Annunciation Output.:   report state of National Fire Protection Agency (USA) genset faults (NFPA s.110) 
Member Number: 6
Base type:
SNVT_state
Direction: output
Service: acknowledged
nvoFrequencyFrequency Output.:   output frequency of the generator set. 
Member Number: 7
Base type:
SNVT_freq_hz
Direction: output
Service: acknowledged
nvoVoltageLLLine-to-Line Voltage Output.:   line-to-line output voltage(s) of the generator set. 
Member Number: 8
Base type:
SNVT_volt_ac
Direction: output
Service: acknowledged
nvoVoltageLNLine-to-Neutral Voltage Output.:   line-to-neutral output voltage(s) of the generator set. 
Member Number: 9
Base type:
SNVT_volt_ac
Direction: output
Service: acknowledged
nvoCurrentLine Current Output.:   output line current(s) of the generator set. 
Member Number: 10
Base type:
SNVT_amp_ac
Direction: output
Service: acknowledged
nvoPowerFactorPower Factor Output.:   power factor of the generator set. 
Member Number: 11
Base type:
SNVT_pwr_fact
Direction: output
Service: acknowledged
nvoRealPowerReal Power Output.:   real power output as a floating type ( in Watts) 
Member Number: 12
Base type:
SNVT_power_f
Direction: output
Service: acknowledged
nvoGenEnergyGenerated Energy Output.:   total (cumulative) electrical energy (WHR) generated by genset. 
Member Number: 13
Base type:
SNVT_elec_whr_f
Direction: output
Service: acknowledged
nvoEngineSpeedEngine Speed Output.:   engine speed of the generator set. 
Member Number: 14
Base type:
SNVT_rpm
Direction: output
Service: acknowledged
nvoEngineTempEngine Temperature Output.:   engine temperature of the generator set. 
Member Number: 15
Base type:
SNVT_temp
Direction: output
Service: acknowledged
nvoOilPressureEngine Oil Pressure Output.:   engine oil pressure of the generator set. 
Member Number: 16
Base type:
SNVT_press
Direction: output
Service: acknowledged
nvoBatteryBattery Voltage Output.:   starting battery voltage of the engine. 
Member Number: 17
Base type:
SNVT_volt
Direction: output
Service: acknowledged
nvoEngineStartsEngine Starts Output.:   total number of successful engine starts. 
Member Number: 18
Base type:
SNVT_count
Direction: output
Service: acknowledged
nvoEngineRunTimeEngine Run Time Output.:   total (cumulative) run time of the engine. 
Member Number: 19
Base type:
SNVT_time_f
Direction: output
Service: acknowledged


Mandatory Configuration Properties

nciMaxSendTimeMaximum send time.:   The maximum period of time between consecutive transmissions of the current value. 
Member Number: 2
Base type:
SCPTmaxSendTime
Applies to SFPTgeneratorSet
Array: not permitted
Default: 0,0


Optional Configuration Properties

nciLocationLocation:   Provides descriptive physical location information related to the object. 
Member Number: 1
Base type:
SCPTlocation
Applies to SFPTgeneratorSet
Array: not permitted
Default: 00*31
nciMaxSendTimeNV03Maximum send time.:   The maximum period of time between consecutive transmissions of the current value. 
Member Number: 3
Base type:
SCPTmaxSendTime
Applies to nvoRunStatus
Array: not permitted
Default: 0,0
nciMaxSendTimeNV13Maximum send time.:   The maximum period of time between consecutive transmissions of the current value. 
Member Number: 4
Base type:
SCPTmaxSendTime
Applies to nvoGenEnergy
Array: not permitted
Default: 0,0
nciMaxSendTimeNV14Maximum send time.:   The maximum period of time between consecutive transmissions of the current value. 
Member Number: 5
Base type:
SCPTmaxSendTime
Applies to nvoEngineSpeed
Array: not permitted
Default: 0,0
nciMaxSendTimeNV15Maximum send time.:   The maximum period of time between consecutive transmissions of the current value. 
Member Number: 6
Base type:
SCPTmaxSendTime
Applies to nvoEngineTemp
Array: not permitted
Default: 0,0
nciMaxSendTimeNV16Maximum send time.:   The maximum period of time between consecutive transmissions of the current value. 
Member Number: 7
Base type:
SCPTmaxSendTime
Applies to nvoOilPressure
Array: not permitted
Default: 0,0
nciMaxSendTimeNV17Maximum send time.:   The maximum period of time between consecutive transmissions of the current value. 
Member Number: 8
Base type:
SCPTmaxSendTime
Applies to nvoBattery
Array: not permitted
Default: 0,0
nciMaxSendTimeNV19Maximum send time.:   The maximum period of time between consecutive transmissions of the current value. 
Member Number: 9
Base type:
SCPTmaxSendTime
Applies to nvoEngineRunTime
Array: not permitted
Default: 0,0