SFPThardwiredSafetyInstrumentedSystemSIS

Safety Instrumented System - SIS..  The hardwired Safety Instrumented System (SIS) profile is used to monitor a Safety Instrumented System input. 
 

Network Variables

Configuration Properties

nviHwSIS
nvoHwSISFb

cpAlarmTriggerState
cpMaxSendTime
cpReceiveHrtbt

nciLocation

 

Details:

Resource Set: Standard 00:00:00:00:00:00:00:00-0
Index: 107
Obsolete: no
Key: 4314
Inheriting: no


Mandatory Network Variables

nviHwSISSecurity Instrumented System Input.:   This input network variable is used to control the state of the equipment when a security alarm variable is received. 
Member Number: 1
Base type:
SNVT_switch
Direction: input
Service: any
nvoHwSISFbFull Ventilation Output.:   This output network variable is used to indicate that a security alarm has been received by the equipment and has been acted upon. 
Member Number: 2
Base type:
SNVT_switch
Direction: output
Service: acknowledged


Mandatory Configuration Properties

cpMaxSendTimeMaximum send time.:   The maximum period of time between consecutive transmissions of the current value. 
Member Number: 1
Base type:
SCPTmaxSendTime
Applies to nvoHwSISFb
Array: not permitted
Default: 30,0
cpReceiveHrtbtMaximum receive time.:   The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.  
Member Number: 2
Base type:
SCPTmaxRcvTime
Applies to nviHwSIS
Array: not permitted
Default: 30,0
cpAlarmTriggerStateAlarm Trigger state.:   This input configuration indicates the default state of the input signal. With this configuration property you could set if the alarm signal will be defected while ACTIVE HIGH or ACTIVE LOW.  
Member Number: 3
Base type:
SCPTdefltBehave
Applies to SFPThardwiredSafetyInstrumentedSystemSIS
Array: not permitted
Default: 100,0 1


Optional Configuration Properties

nciLocationLocation:   Provides descriptive physical location information related to the object. 
Member Number: 4
Base type:
SCPTlocation
Applies to SFPThardwiredSafetyInstrumentedSystemSIS
Array: not permitted
Default: 00*31