HVAC Temperature Sensor.. Temperature sensor designed for HVAC applications.
|
|
Network Variables | Configuration Properties |
nvoHVACTemp
nvoFixPtTemp nvoFloatTemp
| nciMaxSendTime nciMinDelta nciMinSendTime
nciTmpOffset
|
|
Details: |
Resource Set:
| Standard 00:00:00:00:00:00:00:00-0 |
Index:
| 9 |
Obsolete:
| no |
Key:
| 1040 |
Inheriting:
| no |
Principal Variable
| nvoHVACTemp |
Mandatory Network Variables |
nvoHVACTemp | Temperature: The temperature of the sensor using HVAC temperature data type.
|
Member Number:
| 1 |
Base type:
| | Direction:
| output | Service:
| any |
|
Optional Network Variables |
nvoFixPtTemp | Temperature: The temperature of the sensor using fixed point data type.
|
Member Number:
| 2 |
Base type:
| | Direction:
| output | Service:
| any |
|
nvoFloatTemp | Temperature: The temperature of the sensor using floating point data type.
|
Member Number:
| 3 |
Base type:
| | Direction:
| output | Service:
| any |
|
Mandatory Configuration Properties |
nciMaxSendTime | Maximum send time.: Controls the maximum period of time before the output values are transmitted.
|
Member Number:
| 1 |
Base type:
| |
Applies to
| SFPThvacTempSensor | Array:
| not permitted | Default:
| 300,0 |
|
nciMinSendTime | Minimum send time.: Controls the minimum period of time between output value transmissions.
|
|
nciMinDelta | Send on delta.: The minimum change required to force transmission of the output value.
|
Member Number:
| 3 |
Base type:
| |
Applies to
| nvoHVACTemp | Array:
| not permitted | Default:
| 0,30 |
|
Optional Configuration Properties |
nciTmpOffset | Temperature offset.: Used to calibrate external hardware with additive offset after transformation.
|
Member Number:
| 4 |
Base type:
| |
Applies to
| nvoHVACTemp | Array:
| not permitted |
|