SFPTlampActuator

Lamp Actuator..  Used within devices that can control the illumination level of a lamp. 
 

Network Variables

Configuration Properties

nviLampValue
nvoLampValueFb

nvoEnergyCnt
nvoRunHours

ncRunHrAlarm
nciDefault
nciEnergyCntInit
nciInFbDly
nciLocation
nciRunHrInit

 

Details:

Resource Set: Standard 00:00:00:00:00:00:00:00-0
Index: 16
Obsolete: no
Key: 3040
Inheriting: no
Principal Variable nviLampValue


Mandatory Network Variables

nviLampValueLamp input value.:   Permits another device to pass data to the Lamp Actuator. 
Member Number: 1
Base type:
SNVT_switch
Direction: input
Service: any
nvoLampValueFbLamp feedback output.:   State of the Lamp Actuator (ON or OFF) and the percentage level of intensity. 
Member Number: 2
Base type:
SNVT_switch
Direction: output
Service: any


Optional Network Variables

nvoRunHoursRunning hours output.:   Monitors the Lamp Actuator's running (ON) hours. 
Member Number: 3
Base type:
SNVT_elapsed_tm
Direction: output
Service: any
nvoEnergyCntEnergy counter output.:   Monitors the consumed energy in kiloWatt hours. 
Member Number: 4
Base type:
SNVT_elec_kwh
Direction: output
Service: any


Optional Configuration Properties

nciLocationLocation label.:   Provides descriptive physical location information related to the object. 
Member Number: 1
Base type:
SCPTlocation
Applies to SFPTlampActuator
Array: not permitted
nciInFbDlyInput-value feedback delay.:   The time period after the last update, in a succession of changes to the input, before the feedback output is updated. 
Member Number: 2
Base type:
SCPTinFbDly
Applies to nvoLampValueFb
Array: not permitted
Default: 0 0:0:0:300
nciDefaultDefault output.:   The level the sensor should adopt in certain default conditions. 
Member Number: 3
Base type:
SCPTdefOutput
Applies to nvoLampValueFb
Array: not permitted
nciRunHrInitInitialization of running hours counter.:    
Member Number: 4
Base type:
SCPTrunHrInit
Applies to nvoRunHours
Array: not permitted
ncRunHrAlarmAlarm threshold level for the running hours counter.:    
Member Number: 5
Base type:
SCPTrunHrAlarm
Applies to nvoRunHours
Array: not permitted
nciEnergyCntInitInitialization of energy counter.:    
Member Number: 6
Base type:
SCPTenergyCntInit
Applies to nvoEnergyCnt
Array: not permitted