Light Sensor.. Used within devices that can measure ambient light levels.
|
|
Network Variables | Configuration Properties |
nvoLuxLevel
| nciFieldCalibr nciLocation nciMaxSendT nciMinDelta nciMinSendT nciReflection
|
|
Details: |
Resource Set:
| Standard 00:00:00:00:00:00:00:00-0 |
Index:
| 15 |
Obsolete:
| no |
Key:
| 1010 |
Inheriting:
| no |
Principal Variable
| nvoLuxLevel |
Mandatory Network Variables |
nvoLuxLevel | Light level output.: Monitors the value of the hardware input.
|
Member Number:
| 1 |
Base type:
| | Direction:
| output | Service:
| any |
|
Optional Configuration Properties |
nciLocation | Location label.: Provides descriptive physical location information related to the object.
|
|
nciReflection | Reflection factor.: Adjusts the internal gain factor for the measured illumination level.
|
|
nciFieldCalibr | Ambient lux value for self-calibration.: Used by the light sensor to self-calibrate the hardware.
|
|
nciMinSendT | Minimum send time.: Minimum period between output NV transmissions (maximum transmission rate)
|
Member Number:
| 4 |
Base type:
| |
Applies to
| nvoLuxLevel | Array:
| not permitted | Default:
| 1,0 |
|
nciMaxSendT | Send heartbeat.: Maximum period of time that expires before the object automatically transmits the present value of the lux level output NV.
|
Member Number:
| 5 |
Base type:
| |
Applies to
| nvoLuxLevel | Array:
| not permitted | Default:
| 60,0 |
|
nciMinDelta | Minimum change before output.: Used to control the % amount by which the value must change before lux level output NV is transmitted.
|
Member Number:
| 6 |
Base type:
| |
Applies to
| nvoLuxLevel | Array:
| not permitted |
|