SFPTstairwellLightControl

Stairwell light control..   

A detailed description of the function profile with all inputs and outputs as well as the configuration parameters can be found at the VDI - Verein der Deutschen Ingineure. The Web Link is:

VDI - Room control functions (RA functions)
 

Network Variables

Configuration Properties

nviLightCtrl
nvoStairLighCtrl

cpHoldTime

cpOffPrewarning

 

Details:

Resource Set: Standard 00:00:00:00:00:00:00:00-0
Index: 133
Obsolete: no
Key: 16506
Inheriting: no


Mandatory Network Variables

nviLightCtrlSwitch:    
Member Number: 1
Base type:
SNVT_switch
Direction: input
Service: any
nvoStairLighCtrlStraiwell light control.:    
Member Number: 2
Base type:
SNVT_switch
Direction: output
Service: any


Mandatory Configuration Properties

cpHoldTimeHold time.:   Hold time for occupied state after there is no occupancy detected. 
Member Number: 1
Base type:
SCPTholdTime
Applies to SFPTstairwellLightControl
Array: not permitted
Minimum: 1,0
Default: 30,0


Optional Configuration Properties

cpOffPrewarningDelay time, default to scene.:   The delay time, default to scene. 
Member Number: 2
Base type:
SCPTdelayTime
Applies to SFPTstairwellLightControl
Array: not permitted
Default: 0,0