SCPTholdTime

Overview:

Hold time..  Hold time for occupied state after there is no occupancy detected. 

This configuration property sets the hold time for the occupied state. The hardware input to an occupancy sensor must indicate occupancy for longer than this time before the output value of the occupancy sensor device is changed to indicate occupancy. The purpose of the delay is to avoid unnecessary network traffic when the sensor is not detecting presence continuously. This is useful when passive infrared detectors are used.


Details:

Resource Set: Standard 00:00:00:00:00:00:00:00-0
Index: 91
Obsolete: no
Size: 2
Programmatic Name: SCPTholdTime
Minimum: 1,0
Default: 30,0
Neuron C Type:
SNVT_time_sec
Formats:

SCPTholdTime:  text("%f")

Used by:

SFPTautomaticLightController  SFPTentryExit  SFPTisiOccupancySensor  SFPToccupancyController  SFPTpresenceDetection  SFPTstairwellLightControl