Sunshade actuator..
A detailed description of the function profile with all inputs and outputs as well as the configuration parameters can be found at the VDI - Verein der Deutschen Ingineure.
The Web Link is: VDI - Room control functions (RA functions)
|
|
Network Variables | Configuration Properties |
nviSblndCtrl nvoSblndCtrlFb
| nciMaxReceiveTime
cpAngles cpMaxSendTime cpMinSendTime cpPwrUpSetting cpRunTime
|
|
Details: |
Resource Set:
| Standard 00:00:00:00:00:00:00:00-0 |
Index:
| 118 |
Obsolete:
| no |
Key:
| 16202 |
Inheriting:
| no |
Mandatory Network Variables |
nviSblndCtrl | Sunblind controll setting.:
|
Member Number:
| 1 |
Base type:
| | Direction:
| input | Service:
| any |
|
nvoSblndCtrlFb | Sunblind controll setting feedback.:
|
Member Number:
| 2 |
Base type:
| | Direction:
| output | Service:
| any |
|
Mandatory Configuration Properties |
nciMaxReceiveTime | Maximum receive time.:
The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.
|
Member Number:
| 1 |
Base type:
| |
Applies to
| nviSblndCtrl | Array:
| not permitted | Default:
| 60,0 |
|
Optional Configuration Properties |
cpMaxSendTime | Maximum send time.: The maximum period of time between consecutive transmissions of the current value.
|
Member Number:
| 2 |
Base type:
| |
Applies to
| nvoSblndCtrlFb | Array:
| not permitted | Minimum:
| 300,0 | Default:
| 0,0 |
|
cpMinSendTime | Minimum send time.: The minimum period of time between consecutive transmissions of the current value.
|
Member Number:
| 3 |
Base type:
| |
Applies to
| nvoSblndCtrlFb | Array:
| not permitted | Minimum:
| 60,0 | Default:
| 0,0 |
|
cpPwrUpSetting | default Setting.:
|
Member Number:
| 4 |
Base type:
| |
Applies to
| SFPTsunshadeActuator | Array:
| not permitted | Default:
| SET_OFF 0,0 0,00 |
|
cpRunTime | Runtime of sunshade.:
|
Member Number:
| 5 |
Base type:
| |
Applies to
| SFPTsunshadeActuator | Array:
| permitted with dimension 0..2 | Default:
| 150,0 |
|
cpAngles | Nominal angle.: The nominal angle for an actuator.
|
Member Number:
| 6 |
Base type:
| |
Applies to
| SFPTsunshadeActuator | Array:
| permitted with dimension 0..2 | Minimum:
| 0,00 | Maximum:
| 95,00 | Default:
| 90,00 |
|