SCPTdriveTime

Overview:

Drive time..  The transition time for a full 100% stroke (change from one extreme to the other) 

This configuration property sets the transition time for a full stroke (100%) of an actuator. Because improper usage may cause a non-functional device, the device manufacturer can disable write access. This configuration property does not affect airflow control actuators.


Details:

Resource Set: Standard 00:00:00:00:00:00:00:00-0
Index: 45
Obsolete: no
Size: 2
Programmatic Name: SCPTdriveTime
Default: 150,0
Neuron C Type:
SNVT_time_sec
Formats:

SCPTdriveTime:  text("%f")

Used by:

SFPTdamperActuator  SFPTfireSmokeDamperActuator  SFPThvacValvePositioner  SFPTsunshadeActuator