SFPTswitch

Switch.  Used for all type of switches, with or without specific hardware. 
 

Network Variables

Configuration Properties

nvoSwitch

nviSwitchFb
nvoSetting

nciLocation
nciMaxOut
nciMaxSendTime
nciMinSendTime
nciStepValue

 

Details:

Resource Set: Standard 00:00:00:00:00:00:00:00-0
Index: 17
Obsolete: no
Key: 3200
Inheriting: no
Principal Variable nvoSwitch


Mandatory Network Variables

nvoSwitchSwitch output value.:    
Member Number: 1
Base type:
SNVT_switch
Direction: output
Service: any


Optional Network Variables

nviSwitchFbSwitch feedback value.:    
Member Number: 2
Base type:
SNVT_switch
Direction: input
Service: any
nvoSettingSetting output value.:    
Member Number: 3
Base type:
SNVT_setting
Direction: output
Service: any


Optional Configuration Properties

nciLocationLocation label.:   Provides descriptive physical location information related to the object. 
Member Number: 1
Base type:
SCPTlocation
Applies to SFPTswitch
Array: not permitted
nciMinSendTimeMinimum send time.:   Minimum period between output NV transmissions (maximum transmission rate) 
Member Number: 2
Base type:
SCPTminSendTime
Applies to SFPTswitch
Array: not permitted
Minimum: 0,1
Maximum: 2,0
Default: 0,1
nciMaxSendTimeSend heartbeat.:   Maximum period of time that expires before the object automatically transmits the present value of the lux level output NV. 
Member Number: 3
Base type:
SCPTmaxSendTime
Applies to SFPTswitch
Array: not permitted
nciStepValueRamp step value.:   When up/down pushbuttons are used, this parameter can be used to adjust the total ramp time from 0 to 100%. 
Member Number: 4
Base type:
SCPTstepValue
Applies to SFPTswitch
Array: not permitted
nciMaxOutMaximum output value.:   Used to limit the maximum value of the Switch output. 
Member Number: 5
Base type:
SCPTmaxOut
Applies to SFPTswitch
Array: not permitted
Minimum: 0,0
Maximum: 100,0
Default: 100,0