SFPTelevatorFireSystemsPort

Elevator/Lift Fire-Systems Port..  Input for elevator/lift cars to accept fire-signal information from fire control panels. 
 

Network Variables

Configuration Properties

nviCommonAlarm
nviLobbyAlarm

nviMachRoomSmoke
nviOption1
nviOption2
nvoTrouble

nciReceiveHrtbt

nciLocation
nciObjMajVer
nciObjMinVer
nciTroubleHrtbt
nciZoneNumber

 

Details:

Resource Set: Standard 00:00:00:00:00:00:00:00-0
Index: 44
Obsolete: no
Key: 14041
Inheriting: no


Mandatory Network Variables

nviCommonAlarmPrimary fire-sensor input.:   Master fire signal to the elevator group controller. 
Member Number: 1
Base type:
SNVT_switch
Direction: input
Service: any
nviLobbyAlarmFire-in-lobby sensor.:   Reports fire in lobby, so alternate elevator action can be taken. 
Member Number: 2
Base type:
SNVT_switch
Direction: input
Service: any


Optional Network Variables

nviMachRoomSmokeMachine-room smoke sensor.:   Indicates smoke or fire in the elevator machine room. 
Member Number: 3
Base type:
SNVT_switch
Direction: input
Service: any
nviOption1Optional sensor 1.:   Optional input for installation/manufacturer-specific fire/smoke alarming connections. 
Member Number: 4
Base type:
SNVT_switch
Direction: input
Service: any
nviOption2Optional sensor 2.:   Optional input for installation/manufacturer-specific fire/smoke alarming connections. 
Member Number: 5
Base type:
SNVT_switch
Direction: input
Service: any
nvoTroubleElevator is unable to respond to fire sensors.:   value>0 and state=1 indicates trouble. 
Member Number: 6
Base type:
SNVT_switch
Direction: output
Service: any


Mandatory Configuration Properties

nciReceiveHrtbtMaximum receive time.:   The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.  
Member Number: 1
Base type:
SCPTmaxRcvTime
Applies to SFPTelevatorFireSystemsPort
Array: not permitted
Maximum: 3600,0


Optional Configuration Properties

nciLocationLocation:   Provides descriptive physical location information related to the object. 
Member Number: 2
Base type:
SCPTlocation
Applies to SFPTelevatorFireSystemsPort
Array: not permitted
nciObjMajVerObject major version number.:   The major version number for the object. 
Member Number: 3
Base type:
SCPTobjMajVer
Applies to SFPTelevatorFireSystemsPort
Flags: constant
Array: not permitted
Default: 1
nciObjMinVerObject minor version number.:   The minor version number for the object. 
Member Number: 4
Base type:
SCPTobjMinVer
Applies to SFPTelevatorFireSystemsPort
Flags: device specific, constant
Array: not permitted
nciTroubleHrtbtMaximum send time.:   The maximum period of time between consecutive transmissions of the current value. 
Member Number: 5
Base type:
SCPTmaxSendTime
Applies to nvoTrouble
Array: not permitted
Maximum: 3600,0
nciZoneNumberZone Number is for use by Fire System.:   The zone number for the device. 
Member Number: 6
Base type:
SCPTzoneNum
Applies to SFPTelevatorFireSystemsPort
Array: not permitted