SCPTzoneNum

Overview:

Zone number.  (zone number.) .  The zone number for the device. 

This configuration property sets the zone number for a device.


Details:

Resource Set: Standard 00:00:00:00:00:00:00:00-0
Index: 141
Obsolete: no
Size: 2
Programmatic Name: SCPTzoneNum
Default: 0
Neuron C Type:
unsigned long
Minimum: 0
Maximum: 65535
Invalid: 65535
Scaling (A,B,C): 1,  0,  0
Scaled value: 1 *10 0 *(Raw+0)
Resolution: 1
Formats:

SCPTzoneNum:  text("%d")

Used by:

SFPTaudibleFireIndicator  SFPTelevatorFireSystemsPort  SFPTfireSmokeDamperActuator  SFPTpullStationFireInitiator  SFPTsmokeFireInitiatorConvent  SFPTsmokeFireInitiatorIntelli  SFPTthermalFireInitiator  SFPTuniversalFireIndicator  SFPTuniversalFireInitiator  SFPTvisibleFireIndicator