SFPTentryExit

Entry / Exit Object..  An Entry / Exit device is a door, lock, sluice, or something that allows and prohibits entry of a physical unit in to and out of an area. 
 

Network Variables

Configuration Properties

nviEntryState
nvoEntryStatus

nviDirection
nviEntryOpMode
nviOpen
nviPositioned
nviSluiceLock
nviUpdateServ
nvoAftAlarm
nvoDirectionFb
nvoOpenFb
nvoPreAlarm
nvoServiceMsg
nvoSluiceLock

nciMaxRcvTime
nciMaxSendTime
nciMinSendTime

nciAftAlarmDly
nciDefaultOpMode
nciDefaultState
nciEmergencyCnfg
nciLocation
nciNetworkConfig
nciObjMajVer
nciObjMinVer
nciOpenTime
nciPreAlarmDly
nciSafExtCnfg
nciSluiceCnfg

 

Details:

Resource Set: Standard 00:00:00:00:00:00:00:00-0
Index: 40
Obsolete: no
Key: 5051
Inheriting: no


Mandatory Network Variables

nviEntryStateEntry state.:   Desired state for an entry object, e.g., a door, lock, sluice, or something that controls entry of an area. 
Member Number: 1
Base type:
SNVT_ent_state
Direction: input
Service: any
nvoEntryStatusEntry status.:   Status information from an entry object, e.g., a door, lock, sluice, or something that allows/prohits entry of an area. 
Member Number: 2
Base type:
SNVT_ent_status
Direction: output
Service: acknowledged


Optional Network Variables

nviEntryOpModeEntry operation mode.:   Operation-mode for an entry object, e.g., a door, lock, sluice, or something which allows/prohibits entry to an area. 
Member Number: 3
Base type:
SNVT_ent_opmode
Direction: input
Service: any
nvoPreAlarmWarning alarm.:   Warning alarm setting when the device has been unable to perform a requested command longer than the nciPreAlarmDly time, but not as long as the nciAftAlarmDly time.  
Member Number: 4
Base type:
SNVT_switch
Direction: output
Service: acknowledged
nviPositionedIn lockable position.:   Whether the mechanical equipment being subject to locking is in lockable position or not. Typically, this can be an open or closed door. 
Member Number: 5
Base type:
SNVT_switch
Direction: input
Service: any
nvoAftAlarmAfter-warning alarm.:   Alarm setting when the device has been unable to perform a requested command for more than the nciPreAlarmDly time. 
Member Number: 6
Base type:
SNVT_switch
Direction: output
Service: acknowledged
nviOpenDevice-open request.:   opens the device in any state but EM_BLOCKED or EM_MANUAL. After the open command is taken away, the device goes back to its previous state. 
Member Number: 7
Base type:
SNVT_switch
Direction: input
Service: any
nvoOpenFbDevice-open command feedback.:   Feedback of the nviOpen network variable input. 
Member Number: 8
Base type:
SNVT_switch
Direction: output
Service: acknowledged
nviDirectionDirection-flow control.:   Control the direction of persons/items/fluids through device. 
Member Number: 9
Base type:
SNVT_flow_dir
Direction: input
Service: any
nvoDirectionFbDirection-flow control feedback.:   Direction of persons/items/fluids through device. 
Member Number: 10
Base type:
SNVT_flow_dir
Direction: output
Service: acknowledged
nviUpdateServService-message update request.:   Request an update of an optional service-message output. 
Member Number: 11
Base type:
SNVT_switch
Direction: input
Service: any
nvoServiceMsgService message.:   Current service-message information. 
Member Number: 12
Base type:
SNVT_str_asc
Direction: output
Service: acknowledged
nviSluiceLockSluice token input.:   The sluice token input must be set to TOKEN to indicate that an opening cycle is legal in case of sluice operation. 
Member Number: 13
Base type:
SNVT_switch
Direction: input
Service: any
nvoSluiceLockSluice token feedback.:   Token feedback output in a sluice-lock configuration. 
Member Number: 14
Base type:
SNVT_switch
Direction: output
Service: any


Mandatory Configuration Properties

nciMaxRcvTimeMaximum receive time.:   The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.  
Member Number: 1
Base type:
SCPTmaxRcvTime
Applies to SFPTentryExit
Array: not permitted
Maximum: 3600,0
nciMaxSendTimeMaximum send time.:   The maximum period of time between consecutive transmissions of the current value. 
Member Number: 2
Base type:
SCPTmaxSendTime
Applies to nvoEntryStatus
Array: not permitted
Maximum: 3600,0
nciMinSendTimeMinimum send time.:   The minimum period of time between consecutive transmissions of the current value. 
Member Number: 3
Base type:
SCPTminSendTime
Applies to nvoEntryStatus
Array: not permitted
Maximum: 3600,0


Optional Configuration Properties

nciOpenTimeHold time.:   Used to control the time the device is in open state before it returns to its former state (closed, closed/locked, etc.) 
Member Number: 4
Base type:
SCPTholdTime
Applies to SFPTentryExit
Array: not permitted
Minimum: 1,0
Maximum: 6553,5
Default: 6553,5
nciDefaultStateDefault output.:   The position or level the actuator should adopt when updates are not received, or at power-on reset, or when overridden. 
Member Number: 5
Base type:
SCPTdefOutput
Applies to nviEntryState
Array: not permitted
nciDefaultOpModeDefault output.:   The position or level the actuator should adopt when updates are not received, or at power-on reset, or when overridden. 
Member Number: 6
Base type:
SCPTdefOutput
Applies to nviEntryOpMode
Array: not permitted
nciPreAlarmDlyDelay time, default to scene.:   Delay time before a pre-alarm (warning) is sent. 
Member Number: 7
Base type:
SCPTdelayTime
Applies to nvoPreAlarm
Array: not permitted
Maximum: 3600,0
nciAftAlarmDlyDelay time, default to scene.:   Delay time before an alarm is sent. 
Member Number: 8
Base type:
SCPTdelayTime
Applies to nvoAftAlarm
Array: not permitted
Maximum: 3600,0
nciSafExtCnfgSafety Mode.:   Mode that device must be brought to for safety external state of operation. 
Member Number: 9
Base type:
SCPTsafExtCnfg
Applies to nviEntryOpMode
Array: not permitted
Default: 00*3-02
nciEmergencyCnfgEmergency Mode.:   Mode that device must be brought to for emergency state of operation. 
Member Number: 10
Base type:
SCPTemergCnfg
Applies to nviEntryOpMode
Array: not permitted
Default: 00*3-02
nciLocationLocation:   Provides descriptive physical location information related to the object. 
Member Number: 11
Base type:
SCPTlocation
Applies to SFPTentryExit
Array: not permitted
nciObjMajVerObject major version number.:   The major version number for the object. 
Member Number: 12
Base type:
SCPTobjMajVer
Applies to SFPTentryExit
Flags: constant
Array: not permitted
Default: 1
nciObjMinVerObject minor version number.:   The minor version number for the object. 
Member Number: 13
Base type:
SCPTobjMinVer
Applies to SFPTentryExit
Flags: device specific, constant
Array: not permitted
Default: 0
nciNetworkConfigNetwork configuration source.:   The value of this field determines the source of the node's network configuration. 
Member Number: 14
Base type:
SCPTnwrkCnfg
Applies to SFPTentryExit
Flags: reset after modification
Array: not permitted
Default: CFG_LOCAL
nciSluiceCnfgMaster-slave control for sluice. A sluice is built with two or more entry/exit devices with interlock capability.:   Role of a device in a sluice operation. 
Member Number: 15
Base type:
SCPTsluiceCnfg
Applies to SFPTentryExit
Array: not permitted
Default: MSC_NUL