SFPTpumpController

Pump Controller for HVAC Applications..  Provides the primary force to distribute and circulate hot and chilled water in a variety of space-temperature and air-conditioning systems. 
 

Network Variables

Configuration Properties

nviPumpOpMode
nviPumpSetpoint
nvoControlMode
nvoEffOpMode
nvoPumpCapacity

nviOvdFlow
nviOvdPress
nviOvdSpeed
nviPumpOvdStop
nviRemoteFlow
nviRemotePress
nviRemoteTemp
nvoEnergyConsum
nvoFlow
nvoFluidTemp
nvoMaintenance
nvoPower
nvoPowerkilo
nvoPressure
nvoPumpFault
nvoPumpOverride
nvoPumpStatus
nvoRuntime
nvoSpeed

nciSndHrtBt
nroPumpChar

nciControlMode
nciFlowHighLim
nciFlowLowLim
nciLocation
nciMinOutTm
nciObjMajVer
nciObjMinVer
nciPressHighLim
nciPressLowLim
nciRcvHrtBt
nciRemMaxFlow
nciRemMaxPress
nciRemMaxTemp
nciRemMinFlow
nciRemMinPress
nciRemMinTemp

 

Details:

Resource Set: Standard 00:00:00:00:00:00:00:00-0
Index: 47
Obsolete: no
Key: 8120
Inheriting: no


Mandatory Network Variables

nviPumpSetpointPump setpoint for normal operation.:    
Member Number: 1
Base type:
SNVT_switch
Direction: input
Service: any
nviPumpOpModeRequested pump operating mode.:    
Member Number: 2
Base type:
SNVT_hvac_mode
Direction: input
Service: any
nvoPumpCapacityPump capacity in percent.:    
Member Number: 3
Base type:
SNVT_lev_percent
Direction: output
Service: any
nvoEffOpModeEffective operating mode.:    
Member Number: 4
Base type:
SNVT_hvac_mode
Direction: output
Service: any
nvoControlModeEffective device control mode.:    
Member Number: 5
Base type:
SNVT_dev_c_mode
Direction: output
Service: any


Optional Network Variables

nviPumpOvdStopPump override stop command.:    
Member Number: 6
Base type:
SNVT_switch
Direction: input
Service: any
nviOvdSpeedOverride speed in percent.:    
Member Number: 7
Base type:
SNVT_lev_percent
Direction: input
Service: any
nviOvdPressOverride setpoint for pressure.:    
Member Number: 8
Base type:
SNVT_press
Direction: input
Service: any
nviOvdFlowOverride setpoint for flow.:    
Member Number: 9
Base type:
SNVT_flow_p
Direction: input
Service: any
nviRemotePressRemote differential pressure sensor.:    
Member Number: 10
Base type:
SNVT_press
Direction: input
Service: any
nviRemoteFlowRemote flow sensor.:    
Member Number: 11
Base type:
SNVT_flow_p
Direction: input
Service: any
nviRemoteTempRemote temperature sensor.:    
Member Number: 12
Base type:
SNVT_temp_p
Direction: input
Service: any
nvoPumpStatusDevice status.:   Current status of the device. 
Member Number: 13
Base type:
SNVT_dev_status
Direction: output
Service: any
nvoPressurePump pressure.:    
Member Number: 14
Base type:
SNVT_press
Direction: output
Service: any
nvoFlowPump flow.:    
Member Number: 15
Base type:
SNVT_flow_p
Direction: output
Service: any
nvoSpeedPump speed.:    
Member Number: 16
Base type:
SNVT_rpm
Direction: output
Service: any
nvoPumpOverridePump override active.:    
Member Number: 17
Base type:
SNVT_switch
Direction: output
Service: any
nvoRuntimeRuntime:   Total running time for the pump in hours. After 65535 hours, the counter starts again at zero. 
Member Number: 18
Base type:
SNVT_time_hour
Direction: output
Service: any
nvoPumpFaultDevice fault states.:   Fault information for the device. 
Member Number: 19
Base type:
SNVT_dev_fault
Direction: output
Service: any
nvoMaintenanceDevice maintenance.:   Device-maintenance states. 
Member Number: 20
Base type:
SNVT_dev_maint
Direction: output
Service: any
nvoFluidTempFluid temperature.:    
Member Number: 21
Base type:
SNVT_temp_p
Direction: output
Service: any
nvoPowerElectrical power consumption in Watts.:    
Member Number: 22
Base type:
SNVT_power
Direction: output
Service: any
nvoPowerkiloElectrical power consumption in kiloWatts.:    
Member Number: 23
Base type:
SNVT_power_kilo
Direction: output
Service: any
nvoEnergyConsumTotal energy consumption of the pump.:    
Member Number: 24
Base type:
SNVT_elec_kwh
Direction: output
Service: any


Mandatory Configuration Properties

nciSndHrtBtSend heartbeat time.:    
Member Number: 1
Base type:
SCPTmaxSendTime
Applies to SFPTpumpController
Array: not permitted
nroPumpCharPump characteristics.:    
Member Number: 2
Base type:
SCPTpumpCharacteristic
Applies to SFPTpumpController
Flags: manufacturer specific
Array: not permitted


Optional Configuration Properties

nciLocationLocation label.:    
Member Number: 3
Base type:
SCPTlocation
Applies to SFPTpumpController
Array: not permitted
nciRcvHrtBtMaximum receive time.:    
Member Number: 4
Base type:
SCPTmaxRcvTime
Applies to SFPTpumpController
Array: not permitted
nciMinOutTmMinimum send time.:    
Member Number: 5
Base type:
SCPTminSendTime
Applies to SFPTpumpController
Array: not permitted
nciPressLowLimUser-defined operational-pressure low limit.:    
Member Number: 6
Base type:
SCPTminPressureSetpoint
Applies to SFPTpumpController
Array: not permitted
nciPressHighLimUser-defined operational-pressure high limit.:    
Member Number: 7
Base type:
SCPTmaxPressureSetpoint
Applies to SFPTpumpController
Array: not permitted
nciFlowLowLimUser-defined operational-flow low limit.:    
Member Number: 8
Base type:
SCPTminFlowSetpoint
Applies to SFPTpumpController
Array: not permitted
nciFlowHighLimUser-defined operational-flow high limit.:    
Member Number: 9
Base type:
SCPTmaxFlowSetpoint
Applies to SFPTpumpController
Array: not permitted
nciControlModeControl mode for normal operation.:    
Member Number: 10
Base type:
SCPTdeviceControlMode
Applies to SFPTpumpController
Array: not permitted
nciRemMinPressRemote pressure-sensor minimum value.:    
Member Number: 11
Base type:
SCPTminRemotePressureSetpoint
Applies to nviRemotePress
Array: not permitted
Default: 3276,7
nciRemMaxPressRemote pressure-sensor maximum value.:    
Member Number: 12
Base type:
SCPTmaxRemotePressureSetpoint
Applies to nviRemotePress
Array: not permitted
Default: 3276,7
nciRemMinFlowRemote flow-sensor minimum value.:    
Member Number: 13
Base type:
SCPTminRemoteFlowSetpoint
Applies to nviRemoteFlow
Array: not permitted
Default: 327,67
nciRemMaxFlowRemote flow-sensor maximum value.:    
Member Number: 14
Base type:
SCPTmaxRemoteFlowSetpoint
Applies to nviRemoteFlow
Array: not permitted
Default: 327,67
nciRemMinTempRemote temperature-sensor minimum value.:    
Member Number: 15
Base type:
SCPTminRemoteTempSetpoint
Applies to nviRemoteTemp
Array: not permitted
Default: 327,67
nciRemMaxTempRemote temperature-sensor maximum value.:    
Member Number: 16
Base type:
SCPTmaxRemoteTempSetpoint
Applies to nviRemoteTemp
Array: not permitted
Default: 327,67
nciObjMajVerObject major version number.:   The major version number for the object. 
Member Number: 17
Base type:
SCPTobjMajVer
Applies to SFPTpumpController
Flags: constant
Array: not permitted
Default: 1
nciObjMinVerObject minor version number.:   The minor version number for the object. 
Member Number: 18
Base type:
SCPTobjMinVer
Applies to SFPTpumpController
Flags: device specific, constant
Array: not permitted