SNVT_flow_p

Overview:

Flow volume.  (cubic meters/hour.) .   

Used for heating, ventilation, and air conditioning applications. The typical flow in this area is 0.01 to 650 m³/h.


Details:

Resource Set: Standard 00:00:00:00:00:00:00:00-0
Index: 161
Obsolete: no
Size: 2
Programmatic Name: SNVT_flow_p
Neuron C Type:
unsigned long
Minimum: 0
Maximum: 65535
Invalid: 65535
Scaling (A,B,C): 1,  -2,  0
Scaled value: 1 *10 -2 *(Raw+0)
Resolution: 0.01
Formats:

SNVT_flow_p#SI:  text("%f", *1+0(0:1408))

SNVT_flow_p#US:  text("%f", *0.588578+0(0:1405))

Used by:

SCPTmaxFlowSetpoint  SCPTmaxRemoteFlowSetpoint  SCPTminFlowSetpoint  SCPTminRemoteFlowSetpoint  SCPTpumpCharacteristic  SCPTvalveKvs  SFPTpumpController