SFPTrefrigDisplayCaseControllerThermostat

Refrigerated Display-Case Thermostat Controller..  Used to control the thermostatic functions of a refigerated display case. 
 

Network Variables

Configuration Properties

nvoAirTemp
nvoThermostatState

nviAirTemp1
nviAirTemp2
nviDayNight
nviDefrostState
nvoActuatorValve
nvoAlarmAirTemp
nvoCutoutTemp
nvoDifference
nvoDischargeTemp
nvoReturnTemp

nciMaxSendTime

nciAirTemp1PercentAlarm
nciAirTemp1PercentDay
nciAirTemp1PercentNight
nciCutoutValue
nciDayNightControl
nciDeltaNight
nciDifferenceNight
nciDifferenceValue
nciHighLimitDelay
nciHighLimitPdDly
nciHighLimitTemp
nciLocationLabel
nciLowLimitDelay
nciLowLimitTemp
nciThermostatMode

 

Details:

Resource Set: Standard 00:00:00:00:00:00:00:00-0
Index: 67
Obsolete: no
Key: 10012
Inheriting: no


Mandatory Network Variables

nvoAirTempCalculated Air Temperature.:   This NV is the calculated case air temperature. An error on the sensor is indicated with the error value for SNVT_temp_p (0x7fff). 
Member Number: 1
Base type:
SNVT_temp_p
Direction: output
Service: any
nvoThermostatStateThermostat State.:   This NV indicates the current state of the Thermostat Object. There are currently three different control methods supported by the Thermostat Object (See PDF) 
Member Number: 2
Base type:
SNVT_state
Direction: output
Service: any


Optional Network Variables

nviAirTemp1Measured Air Temperature 1.:   This NV is to be assigned to discharge or return air as required. An error on the sensor is indicated with the error value for SNVT_temp_p (0x7fff). 
Member Number: 3
Base type:
SNVT_temp_p
Direction: input
Service: any
nviDayNightDiscrete level.:   This SNVT is obsolete. Use SNVT_switch instead. 
Member Number: 4
Base type:
SNVT_lev_disc
Direction: input
Service: any
nvoCutoutTempCut out Temperature.:   This NV indicates the current cut out limit used by the thermostat object in its agorithms. 
Member Number: 5
Base type:
SNVT_temp_p
Direction: output
Service: any
nviAirTemp2Measured Air Temperature 2.:   This NV is to be assigned to discharge or return air as required. An error on the sensor is indicated with the error value for SNVT_temp_p (0x7fff). 
Member Number: 6
Base type:
SNVT_temp_p
Direction: input
Service: any
nvoDifferenceDifference Temperature.:   This NV indicates the value to be added to the nviCutoutTemp to get the thermostat cut in limit if cut in / out control is selected. 
Member Number: 7
Base type:
SNVT_temp_p
Direction: output
Service: any
nviDefrostStateDefrost state.:   This NV indicates the current state of the defrost object. 
Member Number: 8
Base type:
SNVT_defr_state
Direction: input
Service: any
nvoAlarmAirTempAlarm Air Temperature.:   The nvoAlarmAirTemp indicates the current air temperature used by the alarm section of the thermostat object. 
Member Number: 9
Base type:
SNVT_temp_p
Direction: output
Service: any
nvoDischargeTempDischarge Air Temperature.:   The nvoDischargeTemp indicates the current evaporator discharge air temperature used by the thermostat object. 
Member Number: 10
Base type:
SNVT_temp_p
Direction: output
Service: any
nvoReturnTempReturn Air Temperature.:   The nvoReturnTemp indicates the current evaporator return air temperature used by the thermostat object. 
Member Number: 11
Base type:
SNVT_temp_p
Direction: output
Service: any
nvoActuatorValveActuator Valve.:   This output can be used to drive a refrigeration valve or compressor. 
Member Number: 12
Base type:
SNVT_lev_disc
Direction: output
Service: any


Mandatory Configuration Properties

nciMaxSendTimeMaximum send time.:   The maximum period of time between consecutive transmissions of the current value. 
Member Number: 1
Base type:
SCPTmaxSendTime
Applies to SFPTrefrigDisplayCaseControllerThermostat
Array: not permitted
Default: 0,0


Optional Configuration Properties

nciLocationLabelLocation:   Provides descriptive physical location information related to the object. 
Member Number: 2
Base type:
SCPTlocation
Applies to SFPTrefrigDisplayCaseControllerThermostat
Array: not permitted
Default: 00*31
nciThermostatModeThermostat mode.:   The thermostat control strategy. 
Member Number: 3
Base type:
SCPTthermMode
Applies to SFPTrefrigDisplayCaseControllerThermostat
Array: not permitted
Default: THERM_NO_CONTROL
nciCutoutValueCut-out value.:   The cut-out limit. 
Member Number: 4
Base type:
SCPTcutOutValue
Applies to SFPTrefrigDisplayCaseControllerThermostat
Array: not permitted
Default: 10,00
nciDifferenceValueDifference value.:   The value to be added to the cut-out value to get the cut-in limit. 
Member Number: 5
Base type:
SCPTdiffValue
Applies to SFPTrefrigDisplayCaseControllerThermostat
Array: not permitted
Default: 0,00
nciDayNightControlDay/night control.:   Configures the day/night function. 
Member Number: 6
Base type:
SCPTdayNightCntrl
Applies to SFPTrefrigDisplayCaseControllerThermostat
Array: not permitted
Default: 0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0
nciAirTemp1PercentDayAir temperature 1 percent day.:   The air temperature weighting used during day control. 
Member Number: 7
Base type:
SCPTairTemp1Day
Applies to SFPTrefrigDisplayCaseControllerThermostat
Array: not permitted
Minimum: 0,000
Maximum: 100,000
Default: 100,000
nciAirTemp1PercentNightAir temperature 1 percent night.:   The air temperature weighting used during night control. 
Member Number: 8
Base type:
SCPTairTemp1Night
Applies to SFPTrefrigDisplayCaseControllerThermostat
Array: not permitted
Minimum: 0,000
Maximum: 100,000
Default: 100,000
nciDeltaNightDelta night.:   The value to be added to the cut-out value to get the cut-out limit during night control. 
Member Number: 9
Base type:
SCPTdeltaNight
Applies to SFPTrefrigDisplayCaseControllerThermostat
Array: not permitted
Default: 0,00
nciDifferenceNightDifference night.:   The value to be added to the cut-out value to get the cut-in limit during night control. 
Member Number: 10
Base type:
SCPTdiffNight
Applies to SFPTrefrigDisplayCaseControllerThermostat
Array: not permitted
Default: 0,00
nciAirTemp1PercentAlarmAir temperature 1 percent alarm.:   The weighting of the air temp 1 sensor when calculating the air temp alarm. 
Member Number: 11
Base type:
SCPTairTemp1Alrm
Applies to SFPTrefrigDisplayCaseControllerThermostat
Array: not permitted
Minimum: 0,000
Maximum: 100,000
Default: 100,000
nciHighLimitTempHigh limit temperature.:   The high alarm set point for the alarm air temp network variable. 
Member Number: 12
Base type:
SCPThighLimTemp
Applies to SFPTrefrigDisplayCaseControllerThermostat
Array: not permitted
Default: 0,00
nciLowLimitTempLow limit temperature.:   The low alarm set point for the alarm air temp network variable. 
Member Number: 13
Base type:
SCPTlowLimTemp
Applies to SFPTrefrigDisplayCaseControllerThermostat
Array: not permitted
Default: 0,00
nciHighLimitPdDlyHigh limit defrost delay.:   The time limit before high air temp alarm during pull-down. 
Member Number: 14
Base type:
SCPThighLimDefrDly
Applies to SFPTrefrigDisplayCaseControllerThermostat
Array: not permitted
Default: 0,0
nciLowLimitDelayLow limit delay.:   The time limit during normal operation before the alarm air temp low alarm is recognized. 
Member Number: 15
Base type:
SCPTlowLimDly
Applies to SFPTrefrigDisplayCaseControllerThermostat
Array: not permitted
Default: 0,0
nciHighLimitDelayHigh limit delay.:   The time limit during normal operation before the alarm air temp high alarm is recognized. 
Member Number: 16
Base type:
SCPThighLimDly
Applies to SFPTrefrigDisplayCaseControllerThermostat
Array: not permitted
Default: 0,0