SCPTdiffValue

Overview:

Difference value..  The value to be added to the cut-out value to get the cut-in limit. 

This configuration property sets the value to be added to the SCPTcutOutValue configuration property to get the cut in limit if cut in/out control is selected. If modulating thermostat control is selected, the target temperature is the SCPTcutOutValue limit + SCPTdiffValue / 2.


Details:

Resource Set: Standard 00:00:00:00:00:00:00:00-0
Index: 130
Obsolete: no
Size: 2
Programmatic Name: SCPTdiffValue
Default: 0,00
Neuron C Type:
SNVT_temp_p
Formats:

SCPTdiffValue#SI:  text("%f", *1+0(0:854))

SCPTdiffValue#US:  text("%f", *1.8+0(0:855))

Used by:

SFPTrefrigDisplayCaseControllerThermostat