SFPTsinglePhaseSubMeter

Single-Phase SubMeter..  The SubMeter is used to provide basic power metering and ON/OFF control of a load by a remote control of a relay (switch). 
 

Network Variables

Configuration Properties

nvoCurrentRms
nvoEngyActive
nvoLineFrequency
nvoPowerFactor
nvoVoltageRms

nviEngyActiveSet
nviSwitch
nvoPowerActive
nvoPowerApparent
nvoPowerReactive
nvoSwitchFb

cpMinSendTimeCurrentRms
cpMinSendTimeEngyActive
cpMinSendTimeLineLineFrequency
cpMinSendTimePowerFactor
cpMinSendTimeVoltageRms

cpDbhSwitchFb
cpLocation
cpMaxRcvTimeSwitch
cpMaxSendTimeCurrentRms
cpMaxSendTimeEngyActive
cpMaxSendTimeLineFrequency
cpMaxSendTimePowerActive
cpMaxSendTimePowerApparent
cpMaxSendTimePowerFactor
cpMaxSendTimePowerReactive
cpMaxSendTimeSwitchFb
cpMaxSendTimeVoltageRms
cpMinSendTimePowerActive
cpMinSendTimePowerApparent
cpMinSendTimePowerReactive
cpObjMajVer
cpObjMinVer
cpSendOnDeltaCurrentRms
cpSendOnDeltaEngyActive
cpSendOnDeltaLineFrequency
cpSendOnDeltaPowerActive
cpSendOnDeltaPowerApparent
cpSendOnDeltaPowerFactor
cpSendOnDeltaPowerReactive
cpSendOnDeltaVoltageRms

 

Details:

Resource Set: Standard 00:00:00:00:00:00:00:00-0
Index: 108
Obsolete: no
Key: 2161
Inheriting: no


Mandatory Network Variables

nvoEngyActiveActive Energy value output.:   This output network variable is used to send the Active Energy value of the Sub Meter. 
Member Number: 1
Base type:
SNVT_elec_kwh_l
Direction: output
Service: unacknowledged
nvoVoltageRmsVoltage RMS value output.:   This network variable contains the Instantaneous Voltage RMS Value of the Sub Meter. 
Member Number: 2
Base type:
SNVT_volt_f
Direction: output
Service: unacknowledged
nvoCurrentRmsCurrent RMS value output.:   This network variable contains the Instantaneous Current RMS Value of the Sub Meter. 
Member Number: 3
Base type:
SNVT_amp_f
Direction: output
Service: unacknowledged
nvoPowerFactorPower Factor value output.:   This network variable contains the Instantaneous Power Factor Value of the Sub Meter. 
Member Number: 4
Base type:
SNVT_pwr_fact_f
Direction: output
Service: unacknowledged
nvoLineFrequencyLine Frequency value output.:   This network variable contains the Instantaneous Line Frequency Value of the Sub Meter. 
Member Number: 5
Base type:
SNVT_freq_f
Direction: output
Service: unacknowledged


Optional Network Variables

nvoPowerActiveActive Power value output.:   This network variable contains the Instantaneous Active Power Value of the SubMeter. 
Member Number: 6
Base type:
SNVT_power_f
Direction: output
Service: unacknowledged
nvoPowerReactiveReactive Power value output.:   This network variable contains the Instantaneous Reactive Power Value of the SubMeter. 
Member Number: 7
Base type:
SNVT_power_f
Direction: output
Service: unacknowledged
nvoPowerApparentApparent Power value output.:   This network variable contains the Instantaneous Apparent Power Value of the SubMeter. 
Member Number: 8
Base type:
SNVT_power_f
Direction: output
Service: unacknowledged
nviEngyActiveSetSet and Reset Active Energy value input.:   This network variable contains the input value of the nviEngyActiveSet. 
Member Number: 9
Base type:
SNVT_elec_kwh_l
Direction: input
Service: any
nvoSwitchFbSwitch Feedback output.:   This output network variable provides the state of the switch actuator (ON or OFF) 
Member Number: 10
Base type:
SNVT_switch
Direction: output
Service: acknowledged
nviSwitchSwitch State input.:   This input network variable provides a way for another device to pass switch value to the switch actuator. 
Member Number: 11
Base type:
SNVT_switch
Direction: input
Service: any


Mandatory Configuration Properties

cpMinSendTimeEngyActiveMinimum send time.:   The minimum period of time between consecutive transmissions of the current value. 
Member Number: 1
Base type:
SCPTminSendTime
Applies to nvoEngyActive
Array: not permitted
Default: 10,0
cpMinSendTimeVoltageRmsMinimum send time.:   The minimum period of time between consecutive transmissions of the current value. 
Member Number: 2
Base type:
SCPTminSendTime
Applies to nvoVoltageRms
Array: not permitted
Default: 30,0
cpMinSendTimeCurrentRmsMinimum send time.:   The minimum period of time between consecutive transmissions of the current value. 
Member Number: 3
Base type:
SCPTminSendTime
Applies to nvoCurrentRms
Array: not permitted
Default: 30,0
cpMinSendTimePowerFactorMinimum send time.:   The minimum period of time between consecutive transmissions of the current value. 
Member Number: 4
Base type:
SCPTminSendTime
Applies to nvoPowerFactor
Array: not permitted
Default: 30,0
cpMinSendTimeLineLineFrequencyMinimum send time.:   The minimum period of time between consecutive transmissions of the current value. 
Member Number: 5
Base type:
SCPTminSendTime
Applies to nvoLineFrequency
Array: not permitted
Default: 30,0


Optional Configuration Properties

cpMinSendTimePowerActiveMinimum send time.:   The minimum period of time between consecutive transmissions of the current value. 
Member Number: 6
Base type:
SCPTminSendTime
Applies to nvoPowerActive
Array: not permitted
Default: 30,0
cpMinSendTimePowerReactiveMinimum send time.:   The minimum period of time between consecutive transmissions of the current value. 
Member Number: 7
Base type:
SCPTminSendTime
Applies to nvoPowerReactive
Array: not permitted
Default: 30,0
cpMinSendTimePowerApparentMinimum send time.:   The minimum period of time between consecutive transmissions of the current value. 
Member Number: 8
Base type:
SCPTminSendTime
Applies to nvoPowerApparent
Array: not permitted
Default: 30,0
cpMaxSendTimeEngyActiveMaximum send time.:   The maximum period of time between consecutive transmissions of the current value. 
Member Number: 9
Base type:
SCPTmaxSendTime
Applies to nvoEngyActive
Array: not permitted
Default: 300,0
cpMaxSendTimeVoltageRmsMaximum send time.:   The maximum period of time between consecutive transmissions of the current value. 
Member Number: 10
Base type:
SCPTmaxSendTime
Applies to nvoVoltageRms
Array: not permitted
Default: 0,0
cpMaxSendTimeCurrentRmsMaximum send time.:   The maximum period of time between consecutive transmissions of the current value. 
Member Number: 11
Base type:
SCPTmaxSendTime
Applies to nvoCurrentRms
Array: not permitted
Default: 0,0
cpMaxSendTimePowerFactorMaximum send time.:   The maximum period of time between consecutive transmissions of the current value. 
Member Number: 12
Base type:
SCPTmaxSendTime
Applies to nvoPowerFactor
Array: not permitted
Default: 0,0
cpMaxSendTimeLineFrequencyMaximum send time.:   The maximum period of time between consecutive transmissions of the current value. 
Member Number: 13
Base type:
SCPTmaxSendTime
Applies to nvoLineFrequency
Array: not permitted
Default: 0,0
cpMaxSendTimePowerActiveMaximum send time.:   The maximum period of time between consecutive transmissions of the current value. 
Member Number: 14
Base type:
SCPTmaxSendTime
Applies to nvoPowerActive
Array: not permitted
Default: 0,0
cpMaxSendTimePowerReactiveMaximum send time.:   The maximum period of time between consecutive transmissions of the current value. 
Member Number: 15
Base type:
SCPTmaxSendTime
Applies to nvoPowerReactive
Array: not permitted
Default: 0,0
cpMaxSendTimePowerApparentMaximum send time.:   The maximum period of time between consecutive transmissions of the current value. 
Member Number: 16
Base type:
SCPTmaxSendTime
Applies to nvoPowerApparent
Array: not permitted
Default: 0,0
cpSendOnDeltaEngyActiveSend on delta.:   The minimum change required to force transmission of the output value. 
Member Number: 18
Base type:
SCPTminDeltaLevel
Applies to nvoEngyActive
Array: not permitted
Default: 1,0
cpSendOnDeltaVoltageRmsSend on delta.:   The minimum change required to force transmission of the output value. 
Member Number: 19
Base type:
SCPTminDeltaLevel
Applies to nvoVoltageRms
Array: not permitted
Default: 5,0
cpSendOnDeltaCurrentRmsSend on delta.:   The minimum change required to force transmission of the output value. 
Member Number: 20
Base type:
SCPTminDeltaLevel
Applies to nvoCurrentRms
Array: not permitted
Default: 5,0
cpSendOnDeltaPowerFactorSend on delta.:   The minimum change required to force transmission of the output value. 
Member Number: 21
Base type:
SCPTminDeltaLevel
Applies to nvoPowerFactor
Array: not permitted
Default: 5,0
cpSendOnDeltaLineFrequencySend on delta.:   The minimum change required to force transmission of the output value. 
Member Number: 22
Base type:
SCPTminDeltaLevel
Applies to nvoLineFrequency
Array: not permitted
Default: 5,0
cpSendOnDeltaPowerActiveSend on delta.:   The minimum change required to force transmission of the output value. 
Member Number: 23
Base type:
SCPTminDeltaLevel
Applies to nvoPowerActive
Array: not permitted
Default: 1,0
cpSendOnDeltaPowerReactiveSend on delta.:   The minimum change required to force transmission of the output value. 
Member Number: 24
Base type:
SCPTminDeltaLevel
Applies to nvoPowerReactive
Array: not permitted
Default: 1,0
cpSendOnDeltaPowerApparentSend on delta.:   The minimum change required to force transmission of the output value. 
Member Number: 25
Base type:
SCPTminDeltaLevel
Applies to nvoPowerApparent
Array: not permitted
Default: 1,0
cpObjMajVerObject major version number.:   The major version number for the object. 
Member Number: 28
Base type:
SCPTobjMajVer
Applies to SFPTsinglePhaseSubMeter
Array: not permitted
Default: 1
cpObjMinVerObject minor version number.:   The minor version number for the object. 
Member Number: 29
Base type:
SCPTobjMinVer
Applies to SFPTsinglePhaseSubMeter
Array: not permitted
Default: 0
cpLocationLocation:   Provides descriptive physical location information related to the object. 
Member Number: 30
Base type:
SCPTlocation
Applies to SFPTsinglePhaseSubMeter
Array: not permitted
Default: 00*31
cpMaxSendTimeSwitchFbMaximum send time.:   The maximum period of time between consecutive transmissions of the current value. 
Member Number: 31
Base type:
SCPTmaxSendTime
Applies to nvoSwitchFb
Array: not permitted
Default: 300,0
cpMaxRcvTimeSwitchMaximum receive time.:   The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.  
Member Number: 32
Base type:
SCPTmaxRcvTime
Applies to nviSwitch
Array: not permitted
Default: 600,0
cpDbhSwitchFbDefault behavior.:   Selects which set of values will be used on power-up and communication failure, between the stated default values (0), or manufacturer-specified values (1) 
Member Number: 33
Base type:
SCPTdefltBehave
Applies to nvoSwitchFb
Array: not permitted
Default: 100,0 1