SNVT_elec_kwh_l

Overview:

Electric energy.  (kiloWatt-hours) .   

Used to communicate electricity-metering data to data-logging or energy management devices.

For new designs, SNVT_elec_kwh_l should be used instead of SNVT_elec_kwh.


Details:

Resource Set: Standard 00:00:00:00:00:00:00:00-0
Index: 146
Obsolete: no
Size: 4
Programmatic Name: SNVT_elec_kwh_l
Neuron C Type:
s32_type
Minimum: -2147483648
Maximum: 2147483647
Invalid: 2147483647
Scaling (A,B,C): 1,  -1,  0
Scaled value: 1 *10 -1 *(Raw+0)
Resolution: 0.1
Formats:

SNVT_elec_kwh_l:  text("%f")

Used by:

SFPToutdoorLuminairController  SFPTsinglePhaseSubMeter  SNVT_control_data  SNVT_environment  SNVT_stat_control