Smoke (Conventional) Fire Initiator.. Conventional (non-addressable) Smoke Fire Initiator object for fire-alarm notification and response functions.
|
|
Network Variables | Configuration Properties |
nviDeviceRequest nvoFireAlm nvoFireTrouble
nvoEmergMode
| nciMaxSendTime nciNodeLocation nciZoneNum
nciFireAlarm1 nciFireAlarm2 nciFireAlarm3 nciInstallDate nciMaintDate nciManufDate nciOEMLable
|
|
Details: |
Resource Set:
| Standard 00:00:00:00:00:00:00:00-0 |
Index:
| 60 |
Obsolete:
| no |
Key:
| 11003 |
Inheriting:
| no |
Mandatory Network Variables |
nvoFireAlm | Fire Alarm.: This outpur NV transmits fire information for use by simple Indicators.
|
Member Number:
| 1 |
Base type:
| | Direction:
| output | Service:
| acknowledged |
|
nvoFireTrouble | Fire Trouble.: This output NV transmitted initiator trouble information for use by simple Indicators.
|
Member Number:
| 2 |
Base type:
| | Direction:
| output | Service:
| acknowledged |
|
nviDeviceRequest | Device Request.: This input NV receives requests intended to perform smoke detector operations, initiated from operator.
|
Member Number:
| 3 |
Base type:
| | Direction:
| input | Service:
| any |
|
Optional Network Variables |
nvoEmergMode | HVAC emergency mode.:
|
Member Number:
| 4 |
Base type:
| | Direction:
| output | Service:
| any |
|
Mandatory Configuration Properties |
nciNodeLocation | Location: Provides descriptive physical location information related to the object.
|
|
nciMaxSendTime | Maximum send time.: The maximum period of time between consecutive transmissions of the current value.
|
Member Number:
| 2 |
Base type:
| |
Applies to
| nvoFireAlm | Array:
| not permitted | Default:
| 0,0 |
|
nciZoneNum | Zone number.: The zone number for the device.
|
|
Optional Configuration Properties |
nciOEMLable | OEM label.: The label, programmed by the OEM, to identify the unit name.
|
Member Number:
| 4 |
Base type:
| |
Applies to
| SFPTsmokeFireInitiatorConvent | Flags:
| manufacturer specific, constant | Array:
| not permitted | Minimum:
| 00*31 | Maximum:
| FF*16-00*15 | Default:
| 00*31 |
|
nciInstallDate | Installation date.: The date of installation for the device.
|
|
nciMaintDate | Maintenance date.: The date of last maintenance for the device.
|
|
nciManufDate | Manufacture date.: The date of manufacture for the device.
|
Member Number:
| 7 |
Base type:
| |
Applies to
| SFPTsmokeFireInitiatorConvent | Flags:
| manufacturer specific, constant | Array:
| not permitted | Default:
| 0/0/0 0:0:0 |
|
nciFireAlarm1 | Fire text information.: Text information relevant to fire conditions. A '>' at end of string indicates presence of fire text 2.
|
Member Number:
| 8 |
Base type:
| |
Applies to
| SFPTsmokeFireInitiatorConvent | Flags:
| modify when disabled | Array:
| not permitted | Minimum:
| 00*31 | Maximum:
| FF*30-00 | Default:
| 00*31 |
|
nciFireAlarm2 | Fire text information, continuation.: Continuation text information relevant to fire conditions. A '>' at end of string indicates presence of fire text 3.
|
Member Number:
| 9 |
Base type:
| |
Applies to
| SFPTsmokeFireInitiatorConvent | Flags:
| modify when disabled | Array:
| not permitted | Minimum:
| 00*31 | Maximum:
| FF*30-00 | Default:
| 00*31 |
|
nciFireAlarm3 | Fire text information, second continuation.: Second continuation text information relevant to fire conditions.
|
Member Number:
| 10 |
Base type:
| |
Applies to
| SFPTsmokeFireInitiatorConvent | Flags:
| modify when disabled | Array:
| not permitted | Minimum:
| 00*31 | Maximum:
| FF*30-00 | Default:
| 00*31 |
|