SFPTsmokeFireInitiatorConvent

Smoke (Conventional) Fire Initiator..  Conventional (non-addressable) Smoke Fire Initiator object for fire-alarm notification and response functions. 
 

Network Variables

Configuration Properties

nviDeviceRequest
nvoFireAlm
nvoFireTrouble

nvoEmergMode

nciMaxSendTime
nciNodeLocation
nciZoneNum

nciFireAlarm1
nciFireAlarm2
nciFireAlarm3
nciInstallDate
nciMaintDate
nciManufDate
nciOEMLable

 

Details:

Resource Set: Standard 00:00:00:00:00:00:00:00-0
Index: 60
Obsolete: no
Key: 11003
Inheriting: no


Mandatory Network Variables

nvoFireAlmFire Alarm.:   This outpur NV transmits fire information for use by simple Indicators. 
Member Number: 1
Base type:
SNVT_switch
Direction: output
Service: acknowledged
nvoFireTroubleFire Trouble.:   This output NV transmitted initiator trouble information for use by simple Indicators. 
Member Number: 2
Base type:
SNVT_switch
Direction: output
Service: acknowledged
nviDeviceRequestDevice Request.:   This input NV receives requests intended to perform smoke detector operations, initiated from operator. 
Member Number: 3
Base type:
SNVT_fire_test
Direction: input
Service: any


Optional Network Variables

nvoEmergModeHVAC emergency mode.:    
Member Number: 4
Base type:
SNVT_hvac_emerg
Direction: output
Service: any


Mandatory Configuration Properties

nciNodeLocationLocation:   Provides descriptive physical location information related to the object. 
Member Number: 1
Base type:
SCPTlocation
Applies to SFPTsmokeFireInitiatorConvent
Flags: modify when disabled
Array: not permitted
Default: 00*31
nciMaxSendTimeMaximum send time.:   The maximum period of time between consecutive transmissions of the current value. 
Member Number: 2
Base type:
SCPTmaxSendTime
Applies to nvoFireAlm
Array: not permitted
Default: 0,0
nciZoneNumZone number.:   The zone number for the device. 
Member Number: 3
Base type:
SCPTzoneNum
Applies to SFPTsmokeFireInitiatorConvent
Array: not permitted
Default: 0


Optional Configuration Properties

nciOEMLableOEM label.:   The label, programmed by the OEM, to identify the unit name. 
Member Number: 4
Base type:
SCPToemType
Applies to SFPTsmokeFireInitiatorConvent
Flags: manufacturer specific, constant
Array: not permitted
Minimum: 00*31
Maximum: FF*16-00*15
Default: 00*31
nciInstallDateInstallation date.:   The date of installation for the device. 
Member Number: 5
Base type:
SCPTinstallDate
Applies to SFPTsmokeFireInitiatorConvent
Flags: modify when disabled
Array: not permitted
Default: 0/0/0 0:0:0
nciMaintDateMaintenance date.:   The date of last maintenance for the device. 
Member Number: 6
Base type:
SCPTmaintDate
Applies to SFPTsmokeFireInitiatorConvent
Array: not permitted
Default: 0/0/0 0:0:0
nciManufDateManufacture date.:   The date of manufacture for the device. 
Member Number: 7
Base type:
SCPTmanfDate
Applies to SFPTsmokeFireInitiatorConvent
Flags: manufacturer specific, constant
Array: not permitted
Default: 0/0/0 0:0:0
nciFireAlarm1Fire text information.:   Text information relevant to fire conditions. A '>' at end of string indicates presence of fire text 2. 
Member Number: 8
Base type:
SCPTfireTxt1
Applies to SFPTsmokeFireInitiatorConvent
Flags: modify when disabled
Array: not permitted
Minimum: 00*31
Maximum: FF*30-00
Default: 00*31
nciFireAlarm2Fire text information, continuation.:   Continuation text information relevant to fire conditions. A '>' at end of string indicates presence of fire text 3. 
Member Number: 9
Base type:
SCPTfireTxt2
Applies to SFPTsmokeFireInitiatorConvent
Flags: modify when disabled
Array: not permitted
Minimum: 00*31
Maximum: FF*30-00
Default: 00*31
nciFireAlarm3Fire text information, second continuation.:   Second continuation text information relevant to fire conditions. 
Member Number: 10
Base type:
SCPTfireTxt3
Applies to SFPTsmokeFireInitiatorConvent
Flags: modify when disabled
Array: not permitted
Minimum: 00*31
Maximum: FF*30-00
Default: 00*31