Boiler Controller..  Can be used as an interface to a staged or a modulating boiler. 
 

Network Variables

Configuration Properties

nviBoilerEnable
nvoBoilerState
nvoEffectSetpt

nviApplicMode
nviBoilerCmd
nviOutdoorTemp
nviPumpSpeedCmd
nviReturnTemp
nviSetpoint
nviSupplyTemp
nvoBoilerLoad
nvoBypassValve
nvoLocalOATemp
nvoLocalRetTemp
nvoLocalSupTemp
nvoOutdoorTemp
nvoPumpSpeed
nvoReturnTemp
nvoSupplyTemp

nciHeatSetpt
nciSndHrtBt

nciLocation
nciMinOutTm
nciOffDelay
nciPowerUp
nciRcvHrtBt

 

Details:

Resource Set: Standard 00:00:00:00:00:00:00:00-0
Index: 22
Obsolete: no
Key: 8301
Inheriting: no


Mandatory Network Variables

nviBoilerEnableBoiler enable input.:   Used to disable (stop) boiler operation, or to enable (automatic, local, or remote) boiler operation. 
Member Number: 1
Base type:
SNVT_switch
Direction: input
Service: any
nvoBoilerStateBoiler state output.:   Boiler's present level of heat output, as well as the requested firing rate of a remote boiler. 
Member Number: 2
Base type:
SNVT_switch
Direction: output
Service: unacknowledged
nvoEffectSetptEffective setpoint output.:   Used to monitor the effective temperature setpoint. 
Member Number: 3
Base type:
SNVT_temp_p
Direction: output
Service: unacknowledged
Minimum: 0,00
Maximum: 150,00


Optional Network Variables

nviApplicModeApplication mode input.:   Used to coordinate the boiler controller node with any supervisory controller. 
Member Number: 4
Base type:
SNVT_hvac_mode
Direction: input
Service: any
nviPumpSpeedCmdPump speed command input.:   Used to connect an external pump control to the node or to allow an override of the pump speed. 
Member Number: 5
Base type:
SNVT_switch
Direction: input
Service: any
nviSupplyTempSupply temperature input.:   Used to connect an external supply temperature sensor to the node. 
Member Number: 6
Base type:
SNVT_temp_p
Direction: input
Service: any
Minimum: 0,00
Maximum: 150,00
nviOutdoorTempOutside air temperature input.:   Represents information from an outdoor air temperature sensor. 
Member Number: 7
Base type:
SNVT_temp_p
Direction: input
Service: any
Minimum: -40,00
Maximum: 50,00
nviReturnTempReturn temperature input.:   Used to connect an external return temperature sensor to the node. 
Member Number: 8
Base type:
SNVT_temp_p
Direction: input
Service: any
Minimum: 0,00
Maximum: 150,00
nviSetpointTemperature setpoint input (absolute):   Used to allow the heating setpoint for the boiler water temperature to be changed via the network. 
Member Number: 9
Base type:
SNVT_temp_p
Direction: input
Service: any
Minimum: 0,00
Maximum: 150,00
nviBoilerCmdBoiler command input.:   Used to command the boiler state and firing rate of the boiler controller (e.g., to disable the boiler, or allow automatic control) 
Member Number: 10
Base type:
SNVT_switch
Direction: input
Service: any
nvoBoilerLoadBoiler load output.:   Present heat/cool energy demand of the unit. Negative values indicate that heating energy is required (or in use) by the boiler controller. 
Member Number: 11
Base type:
SNVT_lev_percent
Direction: output
Service: unacknowledged
Maximum: 0,000
nvoSupplyTempSupply temperature output.:   Used to monitor the supply water temperature that the boiler controller is using for control. 
Member Number: 12
Base type:
SNVT_temp_p
Direction: output
Service: unacknowledged
Minimum: 0,00
Maximum: 150,00
nvoLocalSupTempLocal supply temperature output.:   Present value of a locally wired supply water temperature sensor. 
Member Number: 13
Base type:
SNVT_temp_p
Direction: output
Service: unacknowledged
Minimum: -40,00
Maximum: 70,00
nvoReturnTempReturn temperature output.:   Used to monitor the return water temperature that the boiler controller is using for control. 
Member Number: 14
Base type:
SNVT_temp_p
Direction: output
Service: unacknowledged
Minimum: 0,00
Maximum: 150,00
nvoLocalRetTempLocal return temperature output.:   Present value of a locally wired return water temperature sensor. 
Member Number: 15
Base type:
SNVT_temp_p
Direction: output
Service: unacknowledged
Minimum: -40,00
Maximum: 70,00
nvoPumpSpeedPump speed output.:   Actual pump speed of a local multi-speed pump, as well as the requested speed of a remote pump. 
Member Number: 16
Base type:
SNVT_switch
Direction: output
Service: unacknowledged
nvoBypassValveBypass valve output.:   Present value of the bypass control valve position (if hardwired) or can be used to control a remote bypass valve. 
Member Number: 17
Base type:
SNVT_lev_percent
Direction: output
Service: unacknowledged
Minimum: 0,000
Maximum: 100,000
nvoOutdoorTempOutdoor air temperature output.:   Used to monitor the outdoor air temperature that the boiler controller is using for control. 
Member Number: 18
Base type:
SNVT_temp_p
Direction: output
Service: unacknowledged
Minimum: -40,00
Maximum: 70,00
nvoLocalOATempLocal outdoor air temperature output.:   Present value of a locally wired outdoor air temperature sensor. 
Member Number: 19
Base type:
SNVT_temp_p
Direction: output
Service: unacknowledged
Minimum: -40,00
Maximum: 70,00


Mandatory Configuration Properties

nciSndHrtBtSend heartbeat.:   Maximum period of time that expires before the specified network variable outputs will automatically be updated. 
Member Number: 1
Base type:
SCPTmaxSendTime
Applies to SFPTboilerController
Array: not permitted
nciHeatSetptHeating setpoint.:   This applies to the setpoint NV input if one exists; otherwise, it applies to the hardwired input. 
Member Number: 4
Base type:
SCPTheatSetpt
Applies to SFPTboilerController
Array: not permitted
Minimum: 0,00
Maximum: 150,00
Default: 35,00


Optional Configuration Properties

nciPowerUpPower-up enable.:   Default power-up and restart modes of the boiler controller. 
Member Number: 2
Base type:
SCPTpwrUpState
Applies to SFPTboilerController
Array: not permitted
nciRcvHrtBtReceive heartbeat.:   Maximum time that elapses after the last update to a specified network variable input before the boiler controller starts to use its default values. 
Member Number: 3
Base type:
SCPTmaxRcvTime
Applies to SFPTboilerController
Array: not permitted
nciLocationLocation label.:   Provides descriptive physical location information related to the object. 
Member Number: 5
Base type:
SCPTlocation
Applies to SFPTboilerController
Array: not permitted
nciMinOutTmMinimum send time.:   Minimum period of time between automatic network variable output transmissions. 
Member Number: 6
Base type:
SCPTminSendTime
Applies to SFPTboilerController
Array: not permitted
nciOffDelayTurn-off delay time.:   Used to control the time delay that the pump remains "on" after a new command to turn the pump "off" is issued. 
Member Number: 7
Base type:
SCPTpumpDownDelay
Applies to SFPTboilerController
Array: not permitted