SCPTheatSetpt

Overview:

Heating setpoint..  The default setpoint for the leaving water temperature in heating mode when the default behavior selector is set to zero. 

This configuration property sets the default setpoint for the leaving water temperature when in heating mode. If the SCPTdefltBehave configuration property is set to one, the manufacturer-specified values are used instead.


Details:

Resource Set: Standard 00:00:00:00:00:00:00:00-0
Index: 78
Obsolete: no
Size: 2
Programmatic Name: SCPTheatSetpt
Minimum: -40,00
Maximum: 93,00
Default: 35,00
Neuron C Type:
SNVT_temp_p
Formats:

SCPTheatSetpt#SI:  text("%f", *1+0(0:854))

SCPTheatSetpt#US:  text("%f", *1.8+32(0:855))

Used by:

SFPTboilerController  SFPTchiller