Fire Smoke Damper Actuator.. Used to expell smoke or control fire-spread by manipulating the actuator position on a damper.
|
|
Network Variables | Configuration Properties |
nviActuDrive nvoActuPosn
nvoActuDriveFb
| nciDriveT nciRcvrHrtBt nciSafetyPosn nciTurnOffT nciZoneNum
nciActuLabel nciInstallDate nciLocation nciMaintDate nciManfDate nciMaxSendTime nciOEMLable
|
|
Details: |
Resource Set:
| Standard 00:00:00:00:00:00:00:00-0 |
Index:
| 59 |
Obsolete:
| no |
Key:
| 11001 |
Inheriting:
| no |
Mandatory Network Variables |
nviActuDrive | Actuator Drive.: Controls the actuator position.
|
Member Number:
| 1 |
Base type:
| | Direction:
| input | Service:
| any |
|
nvoActuPosn | HVAC emergency mode.:
|
Member Number:
| 2 |
Base type:
| | Direction:
| output | Service:
| acknowledged |
|
Optional Network Variables |
nvoActuDriveFb | Actuator Drive Feedback.: Reflects the actuator value of nviActuDrive. Used to synchronize source objects in multiple relationships.
|
Member Number:
| 3 |
Base type:
| | Direction:
| output | Service:
| acknowledged |
|
Mandatory Configuration Properties |
nciDriveT | Drive time.: The transition time for a full 100% stroke (change from one extreme to the other)
|
|
nciRcvrHrtBt | Maximum receive time.:
The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.
|
Member Number:
| 2 |
Base type:
| |
Applies to
| nviActuDrive | Array:
| not permitted | Default:
| 0,0 |
|
nciSafetyPosn | Direction / Safety position.: The actuator sense of rotation and safety position; bit 0 set => counterclockwise, bit 1 set => damper open.
|
Member Number:
| 3 |
Base type:
| |
Applies to
| SFPTfireSmokeDamperActuator | Array:
| not permitted | Default:
| 0,0,0,0,0,0,0,0,0,0,0,0,0,0,0,0 |
|
nciTurnOffT | Turn-off delay.: The length of time that the load remains energized after a change from ON to OFF has been received.
|
|
nciZoneNum | Zone number.: The zone number for the device.
|
|
Optional Configuration Properties |
nciActuLabel | Actuator label.: The identification of the exact actuator type or label.
|
|
nciInstallDate | Installation date.: The date of installation for the device.
|
|
nciLocation | Location: Provides descriptive physical location information related to the object.
|
|
nciMaintDate | Maintenance date.: The date of last maintenance for the device.
|
|
nciManfDate | Manufacture date.: The date of manufacture for the device.
|
Member Number:
| 10 |
Base type:
| |
Applies to
| SFPTfireSmokeDamperActuator | Flags:
| manufacturer specific | Array:
| not permitted | Default:
| 0/0/0 0:0:0 |
|
nciOEMLable | OEM label.: The label, programmed by the OEM, to identify the unit name.
|
Member Number:
| 11 |
Base type:
| |
Applies to
| SFPTfireSmokeDamperActuator | Flags:
| manufacturer specific | Array:
| not permitted | Minimum:
| 00*31 | Maximum:
| FF*16-00*15 | Default:
| 00*31 |
|
nciMaxSendTime | Maximum send time.: The maximum period of time between consecutive transmissions of the current value.
|
Member Number:
| 12 |
Base type:
| |
Applies to
| nvoActuDriveFb | Array:
| not permitted | Default:
| 0,0 |
|