SFPTthermostat

Thermostat.  Use to adjust HVAC setpoints for one or more heating/cooling units, and act upon temperature inputs for automated loop control. 
 

Network Variables

Configuration Properties

nviSetPoint
nvoCoolOutput
nvoHeatOutput
nvoSpaceTemp
nvoUnitStatus

nviApplicMode
nviEnergyHoldOff
nviOccCmd
nviSetPtOffset
nviSpaceTemp
nvoEffectSetPt
nvoEnergyHoldOff
nvoTerminalFan
nvoTerminalLoad

nciSetPnts
nciSndHrtBt

nciLocation
nciLrSPCool
nciLrSPHeat
nciMinDelta
nciRcvHrtBt
nciRcvHrtBtNV06
nciRcvHrtBtNV08
nciRcvHrtBtNV09
nciRcvHrtBtNV10
nciSndHrtBtNV02
nciSndHrtBtNV03
nciSndHrtBtNV04
nciSndHrtBtNV05
nciSndHrtBtNV12
nciSndHrtBtNV14
nciUpSPCool
nciUpSPHeat

 

Details:

Resource Set: Standard 00:00:00:00:00:00:00:00-0
Index: 74
Obsolete: no
Key: 8060
Inheriting: no


Mandatory Network Variables

nviSetPointTemperature Setpoint Input.:   This input network variable is used to allow the temperature setpoint for the occupied and standby mode being changed via the network. 
Member Number: 1
Base type:
SNVT_temp_p
Direction: input
Service: any
nvoHeatOutputHeat Control Output.:   This output network variable reflects the current position of the heat actuator and can be used as part of a control loop and for monitoring purposes. 
Member Number: 2
Base type:
SNVT_lev_percent
Direction: output
Service: unacknowledged
nvoCoolOutputCool Control Output.:   This output network variable reflects the current position of the cool actuator and can be used as part of a control loop and for monitoring purposes. 
Member Number: 3
Base type:
SNVT_lev_percent
Direction: output
Service: unacknowledged
nvoSpaceTempSpace Temperature Output.:   This output network variable is used to send the value of a locally connected space temperature sensor to other nodes. It is mandatory to the profile. 
Member Number: 4
Base type:
SNVT_temp_p
Direction: output
Service: unacknowledged
nvoUnitStatusUnit Status Output.:   This output network variable is available to report the object status. 
Member Number: 5
Base type:
SNVT_hvac_status
Direction: output
Service: unacknowledged


Optional Network Variables

nviSpaceTempSpace Temperature Input.:   This input network variable is used to connect an external space temperature sensor to the node. 
Member Number: 6
Base type:
SNVT_temp_p
Direction: input
Service: any
nviOccCmdOccupancy Input.:   This input network variable is used to command the thermostat object into different occupancy modes. 
Member Number: 7
Base type:
SNVT_occupancy
Direction: input
Service: any
nviApplicModeApplication Mode Input.:   This network variable input is used to coordinate the thermostat object with any supervisory controller providing the supply energy, e.g. hot or cold water. 
Member Number: 8
Base type:
SNVT_hvac_mode
Direction: input
Service: any
nviSetPtOffsetSetpoint Offset Input.:   This input network variable is used to shift the temperature setpoint via network by adding nviSetPtOffset to the current setpoint. 
Member Number: 9
Base type:
SNVT_temp_p
Direction: input
Service: any
nviEnergyHoldOffEnergy Hold Off Input.:   This input is from a device such as a door/window contact sensor. 
Member Number: 10
Base type:
SNVT_switch
Direction: input
Service: any
nvoTerminalLoadTerminal Load Output.:   This output network variable reflects the current heat/cool energy demand of the Thermostat Device which is typically bound to an energy providing node. 
Member Number: 11
Base type:
SNVT_lev_percent
Direction: output
Service: unacknowledged
nvoEffectSetPtEffective Setpoint Output.:   The output network variable is used to report the effective setpoint temperature when the setpoint is changed through nciSetPnts, nviSetPoint, nviSetPtOffset or by local means.  
Member Number: 12
Base type:
SNVT_temp_p
Direction: output
Service: unacknowledged
nvoTerminalFanTerminal Fan.:   This output network variable reflects the current fan speed of a multi-speed (n-speed) fan. It can be used as part of a control loop and for monitoring purposes.  
Member Number: 13
Base type:
SNVT_switch
Direction: output
Service: unacknowledged
nvoEnergyHoldOffEnergy Hold Off Output.:   This output is used to convey to other devices the state of an EnergyHoldOff device that is hardwired to the controller. Refer to EnergyHoldOff Input. 
Member Number: 14
Base type:
SNVT_switch
Direction: output
Service: unacknowledged


Mandatory Configuration Properties

nciSetPntsOccupancy temperature setpoints.:   The occupancy temperature setpoints for heat and cool mode. 
Member Number: 5
Base type:
SCPTsetPnts
Applies to SFPTthermostat
Array: not permitted
Minimum: -10,00,-10,00,-10,00,-10,00,-10,00,-10,00
Maximum: 35,00,35,00,35,00,35,00,35,00,35,00
Default: 23,00,25,00,28,00,21,00,19,00,16,00
nciSndHrtBtMaximum send time.:   The maximum period of time between consecutive transmissions of the current value. 
Member Number: 16
Base type:
SCPTmaxSendTime
Applies to SFPTthermostat
Array: not permitted
Default: 0,0


Optional Configuration Properties

nciRcvHrtBtNV06Maximum receive time.:   The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.  
Member Number: 6
Base type:
SCPTmaxRcvTime
Applies to nviSpaceTemp
Array: not permitted
Default: 0,0
nciRcvHrtBtNV08Maximum receive time.:   The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.  
Member Number: 7
Base type:
SCPTmaxRcvTime
Applies to nviApplicMode
Array: not permitted
Default: 0,0
nciRcvHrtBtNV09Maximum receive time.:   The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.  
Member Number: 8
Base type:
SCPTmaxRcvTime
Applies to nviSetPtOffset
Array: not permitted
Default: 0,0
nciRcvHrtBtNV10Maximum receive time.:   The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.  
Member Number: 9
Base type:
SCPTmaxRcvTime
Applies to nviEnergyHoldOff
Array: not permitted
Default: 0,0
nciMinDeltaMinimum delta temperature.:   The minimum change in temperature required to be treated as significant. 
Member Number: 10
Base type:
SCPTminDeltaTemp
Applies to SFPTthermostat
Array: not permitted
Minimum: 0,00
Default: 0,00
nciLocationLocation:   Provides descriptive physical location information related to the object. 
Member Number: 11
Base type:
SCPTlocation
Applies to SFPTthermostat
Array: not permitted
Default: 00*31
nciUpSPHeatHeating setpoint upper limit.:   Limits the upper extent of the permitted range for the heating setpoint. 
Member Number: 12
Base type:
SCPTheatUpperSP
Applies to SFPTthermostat
Array: not permitted
Minimum: 10,00
Maximum: 35,00
Default: 35,00
nciLrSPHeatHeating setpoint lower limit.:   Limits the lower extent of the permitted range for the heating setpoint. 
Member Number: 13
Base type:
SCPTheatLowerSP
Applies to SFPTthermostat
Array: not permitted
Minimum: 10,00
Maximum: 35,00
Default: 10,00
nciUpSPCoolCooling setpoint upper limit.:   Limits the upper extent of the permitted range for the cooling setpoint. 
Member Number: 14
Base type:
SCPTcoolUpperSP
Applies to SFPTthermostat
Array: not permitted
Minimum: 10,00
Maximum: 35,00
Default: 10,00
nciLrSPCoolCooling setpoint lower limit.:   Limits the lower extent of the permitted range for the cooling setpoint. 
Member Number: 15
Base type:
SCPTcoolLowerSP
Applies to SFPTthermostat
Array: not permitted
Minimum: 10,00
Maximum: 35,00
Default: 10,00
nciSndHrtBtNV02Maximum send time.:   The maximum period of time between consecutive transmissions of the current value. 
Member Number: 17
Base type:
SCPTmaxSendTime
Applies to nvoHeatOutput
Array: not permitted
Default: 0,0
nciSndHrtBtNV03Maximum send time.:   The maximum period of time between consecutive transmissions of the current value. 
Member Number: 18
Base type:
SCPTmaxSendTime
Applies to nvoCoolOutput
Array: not permitted
Default: 0,0
nciSndHrtBtNV04Maximum send time.:   The maximum period of time between consecutive transmissions of the current value. 
Member Number: 19
Base type:
SCPTmaxSendTime
Applies to nvoSpaceTemp
Array: not permitted
Default: 0,0
nciSndHrtBtNV05Maximum send time.:   The maximum period of time between consecutive transmissions of the current value. 
Member Number: 20
Base type:
SCPTmaxSendTime
Applies to nvoUnitStatus
Array: not permitted
Default: 0,0
nciRcvHrtBtMaximum receive time.:   The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.  
Member Number: 21
Base type:
SCPTmaxRcvTime
Applies to SFPTthermostat
Array: not permitted
Default: 0,0
nciSndHrtBtNV14Maximum send time.:   The maximum period of time between consecutive transmissions of the current value. 
Member Number: 22
Base type:
SCPTmaxSendTime
Applies to nvoEnergyHoldOff
Array: not permitted
Default: 0,0
nciSndHrtBtNV12Maximum send time.:   The maximum period of time between consecutive transmissions of the current value. 
Member Number: 23
Base type:
SCPTmaxSendTime
Applies to nvoEffectSetPt
Array: not permitted
Default: 0,0