SCPTsetPnts

Overview:

Occupancy temperature setpoints..  The occupancy temperature setpoints for heat and cool mode. 

This configuration property sets the occupancy temperature setpoints for heat and cool mode.


Details:

Resource Set: Standard 00:00:00:00:00:00:00:00-0
Index: 60
Obsolete: no
Size: 12
Programmatic Name: SCPTsetPnts
Minimum: -10,00,-10,00,-10,00,-10,00,-10,00,-10,00
Maximum: 35,00,35,00,35,00,35,00,35,00,35,00
Default: 23,00,25,00,28,00,21,00,19,00,16,00
Neuron C Type:
SNVT_temp_setpt
Formats:

SCPTsetPnts#SI:  text("%f,%f,%f,%f,%f,%f", occupied_cool, standby_cool, unoccupied_cool, occupied_heat, standby_heat, unoccupied_heat)

SCPTsetPnts#SI_LO:  text("%f|%f|%f|%f|%f|%f", occupied_cool, standby_cool, unoccupied_cool, occupied_heat, standby_heat, unoccupied_heat)

SCPTsetPnts#US:  text("%f,%f,%f,%f,%f,%f", occupied_cool*1.8+32(0:855), standby_cool*1.8+32(0:855), unoccupied_cool*1.8+32(0:855), occupied_heat*1.8+32(0:855), standby_heat*1.8+32(0:855), unoccupied_heat*1.8+32(0:855))

SCPTsetPnts#US_LO:  text("%f|%f|%f|%f|%f|%f", occupied_cool*1.8+32(0:855), standby_cool*1.8+32(0:855), unoccupied_cool*1.8+32(0:855), occupied_heat*1.8+32(0:855), standby_heat*1.8+32(0:855), unoccupied_heat*1.8+32(0:855))

Used by:

SFPTchilledCeilingController  SFPTdischargeAirController  SFPTfanCoilUnit  SFPTheatPump  SFPTroofTopUnit  SFPTsccAHU  SFPTsccChilledCeiling  SFPTsccCommandModule  SFPTsccFanCoil  SFPTsccHeatPump  SFPTsccRadiator  SFPTsccRooftop  SFPTsccSelfContained  SFPTsccUnitVentilator  SFPTsccVAV  SFPTspaceComfortController  SFPTthermostat  SFPTunitHeater  SFPTunitVentilatorController  SFPTvariableAirVolume  SFPTwallUnit