SFPThvacValvePositioner

Valve Positioner for HVAC Applications..  Also known as a Valve Actuator, it converts the output signal of a controller into a mechanical valve action. 
 

Network Variables

Configuration Properties

nviControlSignal
nviHvacOpMode
nvoControlSignFb
nvoHvacOpMode
nvoValveOpMode

nviEmergencyMode
nviOvrdCapacity
nviOvrdPosition
nviOvrdStop
nviValvePosition
nvoActValvePos
nvoDriveStatus
nvoEmergCount
nvoEmergencyMode
nvoMaintenance
nvoPosErrCount
nvoPwrFailCount
nvoRuntime
nvoStrokeCumul
nvoStrokeLength
nvoValveCapacity
nvoValveFault
nvoValveFlow
nvoValvePosition

nciControlSignal
nciDefPosition
nciMaxReceiveTimeNV01
nciMaxReceiveTimeNV02
nciMaxSendTimeNV03
nciMaxSendTimeNV04
nciMaxSendTimeNV05
nciMinSendTimeNV03
nciMinSendTimeNV04
nciMinSendTimeNV05

nciActTransTblX
nciActTransTblY
nciActuatorChar
nciAntiStickTime
nciCombFlowChar
nciCombTransTblX
nciCombTransTblY
nciDriveTime
nciEmergencyPos
nciFreeCoolPos
nciInstallDate
nciLocation
nciMaxPosition
nciMaxReceiveTimeNV09
nciMaxSendTimeNV11
nciMaxSendTimeNV24
nciMaxStroke
nciMinPosition
nciMinSendTimeNV11
nciMinSendTimeNV12
nciMinSendTimeNV13
nciMinSendTimeNV14
nciMinSendTimeNV15
nciMinSendTimeNV16
nciMinSendTimeNV17
nciMinSendTimeNV18
nciMinSendTimeNV19
nciMinSendTimeNV20
nciMinSendTimeNV21
nciMinSendTimeNV22
nciMinSendTimeNV23
nciMinSendTimeNV24
nciMinStroke
nciNightPurgePos
nciObjMajVer
nciObjMinVer
nciRunTimeAlarm
nciValeDescr
nciValvTransTblX
nciValvTransTblY
nciValveDateCode
nciValveKvs
nciValveNomSize
nciValveOpMode
nciValvePlugChar
nciValveStroke
nciValveType

 

Details:

Resource Set: Standard 00:00:00:00:00:00:00:00-0
Index: 79
Obsolete: no
Key: 8131
Inheriting: no
Principal Variable nvoControlSignFb


Mandatory Network Variables

nviControlSignalValve Control Signal.:   This input network variable provides a control setpoint. The setpoint is given as a percentage of the total required flow or heating/cooling energy. 
Member Number: 1
Base type:
SNVT_lev_percent
Direction: input
Service: any
nviHvacOpModeDesired HVAC Operating Mode.:   A supervisory controller typically uses this input network variable to set the valve operating mode. 
Member Number: 2
Base type:
SNVT_hvac_mode
Direction: input
Service: any
nvoControlSignFbValve-Control Signal Mirror.:   This output network variable mirrors the actual value of nviControlSignal. This can be used for multiple valve-positioner applications. 
Member Number: 3
Base type:
SNVT_lev_percent
Direction: output
Service: unacknowledged
nvoHvacOpModeEffective HVAC Operating Mode.:   This output network variable provides the actual HVAC operating mode. 
Member Number: 4
Base type:
SNVT_hvac_mode
Direction: output
Service: acknowledged
nvoValveOpModeEffective Valve Operating Mode.:   This output network variable provides the actual valve operating mode. 
Member Number: 5
Base type:
SNVT_valve_mode
Direction: output
Service: acknowledged


Optional Network Variables

nviOvrdStopOverride-Valve Stop.:   This input network variable provides a manual override function to stop the valve; typically from a supervisory device. 
Member Number: 6
Base type:
SNVT_switch
Direction: input
Service: any
nviOvrdCapacityOverride Valve Capacity.:   This input network variable provides an override request to the valve capacity; typically from a supervisory device. 
Member Number: 7
Base type:
SNVT_lev_percent
Direction: input
Service: any
nviOvrdPositionOverride Valve Position.:   This input network variable provides for both an override request and a position value relative to the maximum stroke; typically from a supervisory device. 
Member Number: 8
Base type:
SNVT_lev_percent
Direction: input
Service: any
nviEmergencyModeEmergency Mode Request.:   Mandatory for 01 /21: This input network variable is used when the positioner possesses a real emergency operation (for example: a spring-return drive). 
Member Number: 9
Base type:
SNVT_hvac_emerg
Direction: input
Service: any
nviValvePositionRead-Value Valve Position.:   This input network variable is used to connect an external position sensor for precise position control. 
Member Number: 10
Base type:
SNVT_lev_percent
Direction: input
Service: any
nvoValveCapacityValve Capacity.:   This output network variable provides the actual valve capacity as a percentage of the flow. 
Member Number: 11
Base type:
SNVT_lev_percent
Direction: output
Service: acknowledged
nvoValvePositionValve Position.:   This output network variable provides the calculated position relative to the maximum stroke length. 
Member Number: 12
Base type:
SNVT_lev_percent
Direction: output
Service: unacknowledged
nvoStrokeLengthStroke Length.:   This output network variable provides the calculated stroke as length in millimeters. 
Member Number: 13
Base type:
SNVT_length_mil
Direction: output
Service: unacknowledged
nvoActValvePosActual Valve Position.:   This output network variable provides the actual position relative to the maximum stroke length. 
Member Number: 14
Base type:
SNVT_lev_percent
Direction: output
Service: unacknowledged
nvoValveFlowValve Flow.:   This output network variable provides the calculated flow relative to the maximum flow of the valve. 
Member Number: 15
Base type:
SNVT_lev_percent
Direction: output
Service: unacknowledged
nvoDriveStatusDrive Status.:   This output network variable provides status/diagnostic information of the valve drive. 
Member Number: 16
Base type:
SNVT_dev_status
Direction: output
Service: unacknowledged
nvoValveFaultValve Fault.:   This output network variable provides fault information about the valve. 
Member Number: 17
Base type:
SNVT_dev_fault
Direction: output
Service: unacknowledged
nvoMaintenanceDevice maintenance.:   This output network variable provides maintenance information of the valve. 
Member Number: 18
Base type:
SNVT_dev_maint
Direction: output
Service: unacknowledged
nvoRuntimeRuntime:   This output network variable provides the total cumulative running time of the valve actuator. 
Member Number: 19
Base type:
SNVT_elapsed_tm
Direction: output
Service: unacknowledged
nvoStrokeCumulCumulative Stroke Distance.:   This output network variable provides the cumulative distance of all strokes of the valve as length in meters. 
Member Number: 20
Base type:
SNVT_length
Direction: output
Service: unacknowledged
nvoPosErrCountPosition-Error Count.:   This output network variable provides the count of positioning errors. 
Member Number: 21
Base type:
SNVT_count
Direction: output
Service: unacknowledged
nvoPwrFailCountPower-Failure Count.:   This output network variable provides the count of power failures and voltage dips. 
Member Number: 22
Base type:
SNVT_count
Direction: output
Service: unacknowledged
nvoEmergCountEmergency Count.:   This output network variable provides the count of emergency actions, as represented with the Emergency Mode State network variable. 
Member Number: 23
Base type:
SNVT_count
Direction: output
Service: unacknowledged
nvoEmergencyModeEmergency Mode State.:   Mandatory for 01 /21: This output network variable is only used in combination with the Emergency Mode Request input network variable. 
Member Number: 24
Base type:
SNVT_hvac_emerg
Direction: output
Service: unacknowledged


Mandatory Configuration Properties

nciMaxSendTimeNV03Maximum send time.:   The maximum period of time between consecutive transmissions of the current value. 
Member Number: 1
Base type:
SCPTmaxSendTime
Applies to nvoControlSignFb
Array: not permitted
Default: 0,0
nciMaxSendTimeNV04Maximum send time.:   The maximum period of time between consecutive transmissions of the current value. 
Member Number: 2
Base type:
SCPTmaxSendTime
Applies to nvoHvacOpMode
Array: not permitted
Default: 0,0
nciMaxSendTimeNV05Maximum send time.:   The maximum period of time between consecutive transmissions of the current value. 
Member Number: 3
Base type:
SCPTmaxSendTime
Applies to nvoValveOpMode
Array: not permitted
Default: 0,0
nciMaxReceiveTimeNV01Maximum receive time.:   The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.  
Member Number: 6
Base type:
SCPTmaxRcvTime
Applies to nviControlSignal
Array: not permitted
Default: 0,0
nciMaxReceiveTimeNV02Maximum receive time.:   The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.  
Member Number: 7
Base type:
SCPTmaxRcvTime
Applies to nviHvacOpMode
Array: not permitted
Default: 0,0
nciControlSignalControl signal.:   Start and end points (X,Y) for a transition. 
Member Number: 9
Base type:
SCPTcontrolSignal
Applies to SFPThvacValvePositioner
Array: not permitted
Minimum: 0,000 0,000 0,000 0,000
Default: 0,000 0,000 0,000 0,000
nciDefPositionDefault output.:   The position or level the sensor should adopt when updates are not received, or at power-on reset, or when overridden. 
Member Number: 10
Base type:
SCPTdefOutput
Applies to SFPThvacValvePositioner
Array: not permitted
Default: 00*4
nciMinSendTimeNV03Minimum send time.:   The minimum period of time between consecutive transmissions of the current value. 
Member Number: 11
Base type:
SCPTminSendTime
Applies to nvoControlSignFb
Array: not permitted
Default: 0,0
nciMinSendTimeNV04Minimum send time.:   The minimum period of time between consecutive transmissions of the current value. 
Member Number: 12
Base type:
SCPTminSendTime
Applies to nvoHvacOpMode
Array: not permitted
Default: 0,0
nciMinSendTimeNV05Minimum send time.:   The minimum period of time between consecutive transmissions of the current value. 
Member Number: 13
Base type:
SCPTminSendTime
Applies to nvoValveOpMode
Array: not permitted
Default: 0,0


Optional Configuration Properties

nciMaxSendTimeNV11Maximum send time.:   The maximum period of time between consecutive transmissions of the current value. 
Member Number: 4
Base type:
SCPTmaxSendTime
Applies to nvoValveCapacity
Array: not permitted
Default: 0,0
nciMaxSendTimeNV24Maximum send time.:   The maximum period of time between consecutive transmissions of the current value. 
Member Number: 5
Base type:
SCPTmaxSendTime
Applies to nvoEmergencyMode
Array: not permitted
Default: 0,0
nciMaxReceiveTimeNV09Maximum receive time.:   The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.  
Member Number: 8
Base type:
SCPTmaxRcvTime
Applies to nviEmergencyMode
Array: not permitted
Default: 0,0
nciMinSendTimeNV11Minimum send time.:   The minimum period of time between consecutive transmissions of the current value. 
Member Number: 14
Base type:
SCPTminSendTime
Applies to nvoValveCapacity
Array: not permitted
Default: 0,0
nciMinSendTimeNV12Minimum send time.:   The minimum period of time between consecutive transmissions of the current value. 
Member Number: 15
Base type:
SCPTminSendTime
Applies to nvoValvePosition
Array: not permitted
Default: 0,0
nciMinSendTimeNV13Minimum send time.:   The minimum period of time between consecutive transmissions of the current value. 
Member Number: 16
Base type:
SCPTminSendTime
Applies to nvoStrokeLength
Array: not permitted
Default: 0,0
nciMinSendTimeNV14Minimum send time.:   The minimum period of time between consecutive transmissions of the current value. 
Member Number: 17
Base type:
SCPTminSendTime
Applies to nvoActValvePos
Array: not permitted
Default: 0,0
nciMinSendTimeNV15Minimum send time.:   The minimum period of time between consecutive transmissions of the current value. 
Member Number: 18
Base type:
SCPTminSendTime
Applies to nvoValveFlow
Array: not permitted
Default: 0,0
nciMinSendTimeNV16Minimum send time.:   The minimum period of time between consecutive transmissions of the current value. 
Member Number: 19
Base type:
SCPTminSendTime
Applies to nvoDriveStatus
Array: not permitted
Default: 0,0
nciMinSendTimeNV17Minimum send time.:   The minimum period of time between consecutive transmissions of the current value. 
Member Number: 20
Base type:
SCPTminSendTime
Applies to nvoValveFault
Array: not permitted
Default: 0,0
nciMinSendTimeNV18Minimum send time.:   The minimum period of time between consecutive transmissions of the current value. 
Member Number: 21
Base type:
SCPTminSendTime
Applies to nvoMaintenance
Array: not permitted
Default: 0,0
nciMinSendTimeNV19Minimum send time.:   The minimum period of time between consecutive transmissions of the current value. 
Member Number: 22
Base type:
SCPTminSendTime
Applies to nvoRuntime
Array: not permitted
Default: 0,0
nciMinSendTimeNV20Minimum send time.:   The minimum period of time between consecutive transmissions of the current value. 
Member Number: 23
Base type:
SCPTminSendTime
Applies to nvoStrokeCumul
Array: not permitted
Default: 0,0
nciMinSendTimeNV21Minimum send time.:   The minimum period of time between consecutive transmissions of the current value. 
Member Number: 24
Base type:
SCPTminSendTime
Applies to nvoPosErrCount
Array: not permitted
Default: 0,0
nciMinSendTimeNV22Minimum send time.:   The minimum period of time between consecutive transmissions of the current value. 
Member Number: 25
Base type:
SCPTminSendTime
Applies to nvoPwrFailCount
Array: not permitted
Default: 0,0
nciMinSendTimeNV23Minimum send time.:   The minimum period of time between consecutive transmissions of the current value. 
Member Number: 26
Base type:
SCPTminSendTime
Applies to nvoEmergCount
Array: not permitted
Default: 0,0
nciMinSendTimeNV24Minimum send time.:   The minimum period of time between consecutive transmissions of the current value. 
Member Number: 27
Base type:
SCPTminSendTime
Applies to nvoEmergencyMode
Array: not permitted
Default: 0,0
nciLocationLocation:   Provides descriptive physical location information related to the object. 
Member Number: 28
Base type:
SCPTlocation
Applies to SFPThvacValvePositioner
Array: not permitted
Default: 00*31
nciMinPositionMinimum setpoint.:   The minimum setpoint, such as minimum angle of rotation or minimum air flow. 
Member Number: 29
Base type:
SCPTminSetpoint
Applies to SFPThvacValvePositioner
Flags: device specific, constant
Array: not permitted
Default: 0,000
nciMaxPositionMaximum setpoint.:   Either the maximum angle of rotation for an actuator or the maximum airflow for an actuator depending on actuator category. 
Member Number: 30
Base type:
SCPTmaxSetpoint
Applies to SFPThvacValvePositioner
Flags: device specific, constant
Array: not permitted
Default: 0,000
nciMinStrokeMinimum stroke.:   The minimum stroke limit. 
Member Number: 31
Base type:
SCPTminStroke
Applies to SFPThvacValvePositioner
Flags: device specific, constant
Array: not permitted
Default: 0,0
nciMaxStrokeMaximum stroke.:   The maximum stroke limit. 
Member Number: 32
Base type:
SCPTmaxStroke
Applies to SFPThvacValvePositioner
Flags: device specific, constant
Array: not permitted
Default: 0,0
nciValveOpModeValve operating mode.:   The normal operating mode of the valve. 
Member Number: 33
Base type:
SCPTvalveOperatingMode
Applies to SFPThvacValvePositioner
Array: not permitted
Default: VALVE_NORMAL
nciNightPurgePosNight purge valve position.:   Valve position in percent open for night purge. 
Member Number: 34
Base type:
SCPTnightPurgePosition
Applies to SFPThvacValvePositioner
Array: not permitted
Minimum: 0,000
Default: 0,000
nciFreeCoolPosFree cooling valve position.:   Valve position in percent open for free cooling HVAC mode. 
Member Number: 35
Base type:
SCPTfreeCoolPosition
Applies to SFPThvacValvePositioner
Array: not permitted
Minimum: 0,000
Default: 0,000
nciEmergencyPosEmergency position.:   Position in percent of full scale (open) for emergency operation. 
Member Number: 36
Base type:
SCPTemergencyPosition
Applies to SFPThvacValvePositioner
Array: not permitted
Minimum: 0,000
Maximum: 100,000
Default: 100,000
nciDriveTimeDrive time.:   The transition time for a full 100% stroke (change from one extreme to the other) 
Member Number: 37
Base type:
SCPTdriveTime
Applies to SFPThvacValvePositioner
Flags: device specific, constant
Array: not permitted
Default: 150,0
nciValveStroke:    
Member Number: 38
Base type:
SCPTvalveStroke
Applies to SFPThvacValvePositioner
Flags: device specific, constant
Array: not permitted
Default: 0
nciValveNomSize:    
Member Number: 39
Base type:
SCPTvalveNominalSize
Applies to SFPThvacValvePositioner
Array: not permitted
Default: 0
nciValveKvs:    
Member Number: 40
Base type:
SCPTvalveKvs
Applies to SFPThvacValvePositioner
Array: not permitted
Default: 0
nciValveType:    
Member Number: 41
Base type:
SCPTvalveType
Applies to SFPThvacValvePositioner
Array: not permitted
Default: 0
nciValveDateCodeManufacture date.:   The date of manufacture for the device. 
Member Number: 42
Base type:
SCPTmanfDate
Applies to SFPThvacValvePositioner
Array: not permitted
Default: 0/0/0 0:0:0
nciInstallDateInstallation date.:   The date of installation for the device. 
Member Number: 43
Base type:
SCPTinstallDate
Applies to SFPThvacValvePositioner
Array: not permitted
Default: 0/0/0 0:0:0
nciValeDescrActuator label.:   The identification of the exact actuator type or label. 
Member Number: 44
Base type:
SCPTactuatorType
Applies to SFPThvacValvePositioner
Flags: device specific, constant
Array: not permitted
Default: 00*31
nciActuatorChar:    
Member Number: 45
Base type:
SCPTactuatorCharacteristic
Applies to SFPThvacValvePositioner
Flags: device specific, constant
Array: not permitted
Default: DCM_SPEED_CONST
nciActTransTblXTranslation table X.:   Used in conjunction with Translation table Y to scale and linearize a value. 
Member Number: 46
Base type:
SCPTtrnsTblX
Applies to SFPThvacValvePositioner
Array: not permitted
Default: 0 0 0 0 0 0 0 0 0 0 0 0 0 0
nciActTransTblYTranslation table Y.:   Used in conjunction with Translation table X to scale and linearize a value. 
Member Number: 47
Base type:
SCPTtrnsTblY
Applies to SFPThvacValvePositioner
Array: not permitted
Default: 0 0 0 0 0 0 0 0 0 0 0 0 0 0
nciValvePlugCharValve flow characteristic.:   Actual flow characteristic of the valve. 
Member Number: 48
Base type:
SCPTvalveFlowCharacteristic
Applies to SFPThvacValvePositioner
Flags: device specific, constant
Array: not permitted
Minimum: DCM_QUICK_OPEN
Maximum: DCM_FREE_DEFINED
Default: DCM_QUICK_OPEN
nciValvTransTblX:    
Member Number: 49
Base type:
SCPTtrnsTblX2
Applies to SFPThvacValvePositioner
Array: not permitted
Default: 0 0 0 0 0 0 0 0 0 0 0 0 0 0
nciValvTransTblY:    
Member Number: 50
Base type:
SCPTtrnsTblY2
Applies to SFPThvacValvePositioner
Array: not permitted
Default: 0 0 0 0 0 0 0 0 0 0 0 0 0 0
nciCombFlowChar:    
Member Number: 51
Base type:
SCPTcombFlowCharacteristic
Applies to SFPThvacValvePositioner
Array: not permitted
Default: DCM_SPEED_CONST
nciCombTransTblX:    
Member Number: 52
Base type:
SCPTtrnsTblX3
Applies to SFPThvacValvePositioner
Array: not permitted
Default: 0 0 0 0 0 0 0 0 0 0 0 0 0 0
nciCombTransTblY:    
Member Number: 53
Base type:
SCPTtrnsTblY3
Applies to SFPThvacValvePositioner
Array: not permitted
Default: 0 0 0 0 0 0 0 0 0 0 0 0 0 0
nciAntiStickTimeMinimum time for movement.:   The minimum time in hours for movement to prevent blocking. 
Member Number: 54
Base type:
SCPTblockProtectionTime
Applies to SFPThvacValvePositioner
Array: not permitted
Default: 0
nciRunTimeAlarm:    
Member Number: 55
Base type:
SCPTrunTimeAlarm
Applies to SFPThvacValvePositioner
Array: not permitted
Default: 0 0 0 0 0
nciObjMajVerObject major version number.:   The major version number for the object. 
Member Number: 56
Base type:
SCPTobjMajVer
Applies to SFPThvacValvePositioner
Flags: constant
Array: not permitted
Default: 1
nciObjMinVerObject minor version number.:   The minor version number for the object. 
Member Number: 57
Base type:
SCPTobjMinVer
Applies to SFPThvacValvePositioner
Flags: device specific, constant
Array: not permitted
Default: 0