SCPTtrnsTblX

Overview:

Translation table X..  Used in conjunction with Translation table Y to scale and linearize a value. 

This configuration property is used in conjunction with the Translation Table Y configuration property to create a translation table that determines how to scale and linearize the raw input signal as received from a hardware device such as a sensor, or how to scale or linearize actuator movement with respect to an input network variable.

There may be an unlimited number of table entries (up to the maximum number of configuration properties). A Translation Table Y value must be specified for each Translation Table X value. The default is manufacturer-defined. See SNVT_trans_table for invalid value (3) in each bitfield.


Details:

Resource Set: Standard 00:00:00:00:00:00:00:00-0
Index: 28
Obsolete: no
Size: 30
Programmatic Name: SCPTtrnsTblX
Default: 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Neuron C Type:
SNVT_trans_table
Formats:

SCPTtrnsTblX:  text("%f %f %f %f %f %f %f %d %d %d %d %d %d %d", point[0], point[1], point[2], point[3], point[4], point[5], point[6], interp_pts_0_to_1, interp_pts_1_to_2, interp_pts_2_to_3, interp_pts_3_to_4, interp_pts_4_to_5, interp_pts_5_to_6, interp_pts_6_to_0)

Used by:

SFPTclosedLoopActuator  SFPTclosedLoopSensor  SFPThvacValvePositioner  SFPTopenLoopActuator  SFPTopenLoopSensor