SCPTmaxSetpoint

Overview:

Maximum setpoint..  Either the maximum angle of rotation for an actuator or the maximum airflow for an actuator depending on actuator category. 

This configuration property sets the maximum angle of rotation or the maximum fluid flow for an actuator. Its value has to be greater than or equal to the SCPTminSetpoint value, if any.


Details:

Resource Set: Standard 00:00:00:00:00:00:00:00-0
Index: 50
Obsolete: no
Size: 2
Programmatic Name: SCPTmaxSetpoint
Default: 0,000
Neuron C Type:
SNVT_lev_percent
Formats:

SCPTmaxSetpoint:  text("%f")

Used by:

SFPThvacValvePositioner  SFPTsetpointCalculation  SFPTvariableSpeedMotorDrive