SFPTchilledCeilingController

Chilled-Ceiling Controller..  Used to control an HVAC chilled-ceiling space-conditioning unit. 
 

Network Variables

Configuration Properties

nviSpaceTemp
nvoSpaceTemp
nvoUnitStatus

nviApplicMode
nviCoolPriSlave
nviCoolSecSlave
nviCoolSrcTemp
nviEnergyHoldOff
nviHeatCool
nviHeatPriSlave
nviHeatSecSlave
nviHeatSrcTemp
nviOccManCmd
nviOccSchedule
nviOccSensor
nviOutdoorDewPt
nviSetpoint
nviSetptOffset
nviSetptShift
nviSourceTemp
nviSpaceDewPt
nviSpaceRH
nviValveOverride
nvoCoolPrimary
nvoCoolSecondary
nvoEffectOccup
nvoEffectSetpt
nvoEnergyHoldOff
nvoHeatCool
nvoHeatPrimary
nvoHeatSecondary
nvoLoadAbs
nvoSetpoint
nvoSetptShift
nvoSpaceDewPt
nvoSpaceRH
nvoTerminalLoad

nciSetpoints
nciSndHrtBt

nciBypassTime
nciLocation
nciManualTime
nciMinOutTm
nciRcvHrtBt
nciRcvHrtBtNV01
nciRcvHrtBtNV03
nciRcvHrtBtNV04
nciRcvHrtBtNV05
nciRcvHrtBtNV07
nciRcvHrtBtNV08
nciRcvHrtBtNV09
nciRcvHrtBtNV10
nciRcvHrtBtNV12
nciRcvHrtBtNV13
nciRcvHrtBtNV14
nciRcvHrtBtNV15
nciRcvHrtBtNV16
nciRcvHrtBtNV17
nciRcvHrtBtNV18
nciRcvHrtBtNV19
nciRcvHrtBtNV20
nciRcvHrtBtNV21
nciSndHrtBtNV22
nciSndHrtBtNV23
nciSndHrtBtNV24
nciSndHrtBtNV26
nciSndHrtBtNV28
nciSndHrtBtNV30
nciSndHrtBtNV31
nciSndHrtBtNV32
nciSndHrtBtNV33
nciSndHrtBtNV34
nciSndHrtBtNV35
nciSndHrtBtNV36
nciSndHrtBtNV37

 

Details:

Resource Set: Standard 00:00:00:00:00:00:00:00-0
Index: 75
Obsolete: no
Key: 8070
Inheriting: no


Mandatory Network Variables

nviSpaceTempSpace Temperature Input.:   This input network variable is used to connect an external space temperature sensor to the node. 
Member Number: 1
Base type:
SNVT_temp_p
Direction: input
Service: any
nvoSpaceTempEffective Space Temperature Output.:   This output network variable is used to monitor the effective space temperature that the Chilled Ceiling Controller is using for control. 
Member Number: 22
Base type:
SNVT_temp_p
Direction: output
Service: unacknowledged
nvoUnitStatusUnit Status Output.:   This output network variable is available to report the Chilled Ceiling Controller status. 
Member Number: 23
Base type:
SNVT_hvac_status
Direction: output
Service: unacknowledged


Optional Network Variables

nviSetpointTemperature Setpoint Input (absolute):   This input network variable is used to allow the temperature setpoints for the occupied and standby modes to be changed via the network. 
Member Number: 2
Base type:
SNVT_temp_p
Direction: input
Service: any
nviSetptOffsetSetpoint Offset Input.:   This input network variable is used to shift the effective occupied and standby temperature setpoints by adding nviSetptOffset to the current setpoints. 
Member Number: 3
Base type:
SNVT_temp_p
Direction: input
Service: any
nviSetptShiftSetpoint Shift Input.:   This input network variable is used to shift the effective heat/cool setpoints by adding the corresponding value in nviSetptShift to the current setpoints. 
Member Number: 4
Base type:
SNVT_temp_setpt
Direction: input
Service: any
nviOccScheduleOccupancy Scheduler Input.:   This input network variable is used to command the Chilled Ceiling Controller into different occupancy modes. 
Member Number: 5
Base type:
SNVT_tod_event
Direction: input
Service: any
nviOccManCmdOccupancy Override Input.:   This input network variable is used to command the Chilled Ceiling Controller into different occupancy modes. 
Member Number: 6
Base type:
SNVT_occupancy
Direction: input
Service: any
nviOccSensorOccupancy Sensor Input.:   This input network variable is used to indicate the presence of occupants in the controlled space. 
Member Number: 7
Base type:
SNVT_occupancy
Direction: input
Service: any
nviApplicModeApplication Mode Input.:   This network variable input is used to coordinate the Chilled Ceiling Controller with any supervisory controller. 
Member Number: 8
Base type:
SNVT_hvac_mode
Direction: input
Service: any
nviHeatCoolHeat/Cool Mode Input.:   This network variable input is used to coordinate the Chilled Ceiling Controller with any node that may need to control the heat/cool changeover of the unit. 
Member Number: 9
Base type:
SNVT_hvac_mode
Direction: input
Service: any
nviEnergyHoldOffEnergy Hold Off Input.:   This input is used to stop heating and cooling while allowing the unit to protect the space from temperature extremes. 
Member Number: 10
Base type:
SNVT_switch
Direction: input
Service: any
nviValveOverrideWater Valve Override Input.:   This input network variable is used for commanding the controller into a manual mode for overriding water valves controlled by the unit. 
Member Number: 11
Base type:
SNVT_hvac_overid
Direction: input
Service: any
nviSourceTempSource Temperature Input.:   This input network variable is used to indicate the temperature of the air or water being supplied to the unit for heating and/or cooling capacity. 
Member Number: 12
Base type:
SNVT_temp_p
Direction: input
Service: any
nviHeatSrcTempHeat Source Temperature Input.:   This input network variable is used to indicate the temperature of the air or water being supplied to the unit for heating capacity. 
Member Number: 13
Base type:
SNVT_temp_p
Direction: input
Service: any
nviCoolSrcTempCool Source Temperature Input.:   This input network variable is used to indicate the temperature of the air or water being supplied to the unit for cooling capacity. 
Member Number: 14
Base type:
SNVT_temp_p
Direction: input
Service: any
nviSpaceRHSpace Humidity Input.:   This input network variable is the measured space humidity in percent. This input is typically sent from a communicating humidity sensor. 
Member Number: 15
Base type:
SNVT_lev_percent
Direction: input
Service: any
nviSpaceDewPtSpace Dew Point Temperature Input.:   This input network variable is the measured space dew point temperature. 
Member Number: 16
Base type:
SNVT_temp_p
Direction: input
Service: any
nviOutdoorDewPtOutdoor Air Dew Point Temp. Input.:   This input network variable is the measured outdoor dew point temperature. 
Member Number: 17
Base type:
SNVT_temp_p
Direction: input
Service: any
nviHeatPriSlavePrimary Heat Input for Slave Operation.:   This input network variable is intended for slave operation. 
Member Number: 18
Base type:
SNVT_lev_percent
Direction: input
Service: any
nviHeatSecSlaveSecondary Heat Input for Slave Operation.:   This input network variable is intended for slave operation. 
Member Number: 19
Base type:
SNVT_lev_percent
Direction: input
Service: any
nviCoolPriSlavePrimary Cool Input for Slave Operation.:   This input network variable is intended for slave operation. 
Member Number: 20
Base type:
SNVT_lev_percent
Direction: input
Service: any
nviCoolSecSlaveSecondary Cool Input for Slave Operation.:   This input network variable is intended for slave operation. 
Member Number: 21
Base type:
SNVT_lev_percent
Direction: input
Service: any
nvoEffectSetptEffective Setpoint Output.:   This output network variable is used to monitor the effective temperature setpoint. 
Member Number: 24
Base type:
SNVT_temp_p
Direction: output
Service: unacknowledged
nvoEffectOccupEffective Occupancy Output.:   This output network variable is used to indicate the actual occupancy mode of the unit. 
Member Number: 25
Base type:
SNVT_occupancy
Direction: output
Service: unacknowledged
nvoHeatCoolEffective Heat/Cool Output.:   This output network variable is used to indicate the actual heat/cool mode of the unit. 
Member Number: 26
Base type:
SNVT_hvac_mode
Direction: output
Service: unacknowledged
nvoSetpointLocal Setpoint Output.:   This output network variable is used to monitor the space temperature setpoint if a setpoint device is locally wired. 
Member Number: 27
Base type:
SNVT_temp_p
Direction: output
Service: unacknowledged
nvoSetptShiftLocal Setpoint Shift Output.:   This output network variable is used to report a locally-determined shift of the effective heat/cool setpoints. 
Member Number: 28
Base type:
SNVT_temp_setpt
Direction: output
Service: unacknowledged
nvoLoadAbsAbsolute Power Consumption Output.:   This output network variable can used to indicate the current power consumption of the unit. 
Member Number: 29
Base type:
SNVT_power
Direction: output
Service: unacknowledged
nvoTerminalLoadTerminal Load Output.:   This output indicates the current heat/cool energy demand of the unit. 
Member Number: 30
Base type:
SNVT_lev_percent
Direction: output
Service: unacknowledged
nvoHeatPrimaryPrimary Heat Output.:   This output network variable reflects the current level of the primary heat output or can be used to control a remote primary heat source. 
Member Number: 31
Base type:
SNVT_lev_percent
Direction: output
Service: unacknowledged
nvoHeatSecondarySecondary Heat Output.:   This output network variable reflects the current level of the secondary heat output or can be used to control a remote secondary heat source. 
Member Number: 32
Base type:
SNVT_lev_percent
Direction: output
Service: unacknowledged
nvoCoolPrimaryPrimary Cool Output.:   This output network variable reflects the current level of the primary mechanical cooling output or can be used to control a remote mechanical cooling source. 
Member Number: 33
Base type:
SNVT_lev_percent
Direction: output
Service: unacknowledged
nvoCoolSecondarySecondary Cool Output.:   This output network variable reflects the current level of the secondary mechanical cooling output or can be used to control a remote mechanical cooling source. 
Member Number: 34
Base type:
SNVT_lev_percent
Direction: output
Service: unacknowledged
nvoSpaceRHSpace Humidity Output.:   This output network variable indicates the space humidity in percent, if the Chilled Ceiling Controller Device has a locally wired humidity sensor. 
Member Number: 35
Base type:
SNVT_lev_percent
Direction: output
Service: unacknowledged
nvoSpaceDewPtSpace Dewpoint Temperature Output.:   This output network variable indicates the space dew point temperature. This value can be measured or calculated by the Chilled Ceiling Controller. 
Member Number: 36
Base type:
SNVT_temp_p
Direction: output
Service: unacknowledged
nvoEnergyHoldOffEnergy Hold Off Output.:   This output indicates the state of an Energy Hold Off device that is hardwired to the controller. 
Member Number: 37
Base type:
SNVT_switch
Direction: output
Service: unacknowledged


Mandatory Configuration Properties

nciSetpointsOccupancy temperature setpoints.:   The occupancy temperature setpoints for heat and cool mode. 
Member Number: 32
Base type:
SCPTsetPnts
Applies to SFPTchilledCeilingController
Array: not permitted
Minimum: -10,00,-10,00,-10,00,-10,00,-10,00,-10,00
Maximum: 35,00,35,00,35,00,35,00,35,00,35,00
Default: 23,00,25,00,28,00,21,00,19,00,16,00
nciSndHrtBtMaximum send time.:   The maximum period of time between consecutive transmissions of the current value. 
Member Number: 37
Base type:
SCPTmaxSendTime
Applies to SFPTchilledCeilingController
Array: not permitted
Default: 0,0


Optional Configuration Properties

nciSndHrtBtNV24Maximum send time.:   The maximum period of time between consecutive transmissions of the current value. 
Member Number: 3
Base type:
SCPTmaxSendTime
Applies to nvoEffectSetpt
Array: not permitted
Default: 0,0
nciSndHrtBtNV26Maximum send time.:   The maximum period of time between consecutive transmissions of the current value. 
Member Number: 4
Base type:
SCPTmaxSendTime
Applies to nvoHeatCool
Array: not permitted
Default: 0,0
nciSndHrtBtNV28Maximum send time.:   The maximum period of time between consecutive transmissions of the current value. 
Member Number: 5
Base type:
SCPTmaxSendTime
Applies to nvoSetptShift
Array: not permitted
Default: 0,0
nciSndHrtBtNV30Maximum send time.:   The maximum period of time between consecutive transmissions of the current value. 
Member Number: 6
Base type:
SCPTmaxSendTime
Applies to nvoTerminalLoad
Array: not permitted
Default: 0,0
nciSndHrtBtNV31Maximum send time.:   The maximum period of time between consecutive transmissions of the current value. 
Member Number: 7
Base type:
SCPTmaxSendTime
Applies to nvoHeatPrimary
Array: not permitted
Default: 0,0
nciSndHrtBtNV32Maximum send time.:   The maximum period of time between consecutive transmissions of the current value. 
Member Number: 8
Base type:
SCPTmaxSendTime
Applies to nvoHeatSecondary
Array: not permitted
Default: 0,0
nciSndHrtBtNV33Maximum send time.:   The maximum period of time between consecutive transmissions of the current value. 
Member Number: 9
Base type:
SCPTmaxSendTime
Applies to nvoCoolPrimary
Array: not permitted
Default: 0,0
nciSndHrtBtNV34Maximum send time.:   The maximum period of time between consecutive transmissions of the current value. 
Member Number: 10
Base type:
SCPTmaxSendTime
Applies to nvoCoolSecondary
Array: not permitted
Default: 0,0
nciSndHrtBtNV35Maximum send time.:   The maximum period of time between consecutive transmissions of the current value. 
Member Number: 11
Base type:
SCPTmaxSendTime
Applies to nvoSpaceRH
Array: not permitted
Default: 0,0
nciSndHrtBtNV36Maximum send time.:   The maximum period of time between consecutive transmissions of the current value. 
Member Number: 12
Base type:
SCPTmaxSendTime
Applies to nvoSpaceDewPt
Array: not permitted
Default: 0,0
nciSndHrtBtNV37Maximum send time.:   The maximum period of time between consecutive transmissions of the current value. 
Member Number: 13
Base type:
SCPTmaxSendTime
Applies to nvoEnergyHoldOff
Array: not permitted
Default: 0,0
nciRcvHrtBtNV01Maximum receive time.:   The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.  
Member Number: 14
Base type:
SCPTmaxRcvTime
Applies to nviSpaceTemp
Array: not permitted
Default: 0,0
nciRcvHrtBtNV03Maximum receive time.:   The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.  
Member Number: 15
Base type:
SCPTmaxRcvTime
Applies to nviSetptOffset
Array: not permitted
Default: 0,0
nciRcvHrtBtNV04Maximum receive time.:   The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.  
Member Number: 16
Base type:
SCPTmaxRcvTime
Applies to nviSetptShift
Array: not permitted
Default: 0,0
nciRcvHrtBtNV05Maximum receive time.:   The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.  
Member Number: 17
Base type:
SCPTmaxRcvTime
Applies to nviOccSchedule
Array: not permitted
Default: 0,0
nciRcvHrtBtNV07Maximum receive time.:   The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.  
Member Number: 18
Base type:
SCPTmaxRcvTime
Applies to nviOccSensor
Array: not permitted
Default: 0,0
nciRcvHrtBtNV08Maximum receive time.:   The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.  
Member Number: 19
Base type:
SCPTmaxRcvTime
Applies to nviApplicMode
Array: not permitted
Default: 0,0
nciRcvHrtBtNV09Maximum receive time.:   The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.  
Member Number: 20
Base type:
SCPTmaxRcvTime
Applies to nviHeatCool
Array: not permitted
Default: 0,0
nciRcvHrtBtNV10Maximum receive time.:   The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.  
Member Number: 21
Base type:
SCPTmaxRcvTime
Applies to nviEnergyHoldOff
Array: not permitted
Default: 0,0
nciRcvHrtBtNV12Maximum receive time.:   The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.  
Member Number: 22
Base type:
SCPTmaxRcvTime
Applies to nviSourceTemp
Array: not permitted
Default: 0,0
nciRcvHrtBtNV13Maximum receive time.:   The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.  
Member Number: 23
Base type:
SCPTmaxRcvTime
Applies to nviHeatSrcTemp
Array: not permitted
Default: 0,0
nciRcvHrtBtNV14Maximum receive time.:   The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.  
Member Number: 24
Base type:
SCPTmaxRcvTime
Applies to nviCoolSrcTemp
Array: not permitted
Default: 0,0
nciRcvHrtBtNV15Maximum receive time.:   The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.  
Member Number: 25
Base type:
SCPTmaxRcvTime
Applies to nviSpaceRH
Array: not permitted
Default: 0,0
nciRcvHrtBtNV16Maximum receive time.:   The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.  
Member Number: 26
Base type:
SCPTmaxRcvTime
Applies to nviSpaceDewPt
Array: not permitted
Default: 0,0
nciRcvHrtBtNV17Maximum receive time.:   The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.  
Member Number: 27
Base type:
SCPTmaxRcvTime
Applies to nviOutdoorDewPt
Array: not permitted
Default: 0,0
nciRcvHrtBtNV18Maximum receive time.:   The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.  
Member Number: 28
Base type:
SCPTmaxRcvTime
Applies to nviHeatPriSlave
Array: not permitted
Default: 0,0
nciRcvHrtBtNV19Maximum receive time.:   The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.  
Member Number: 29
Base type:
SCPTmaxRcvTime
Applies to nviHeatSecSlave
Array: not permitted
Default: 0,0
nciRcvHrtBtNV20Maximum receive time.:   The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.  
Member Number: 30
Base type:
SCPTmaxRcvTime
Applies to nviCoolPriSlave
Array: not permitted
Default: 0,0
nciRcvHrtBtNV21Maximum receive time.:   The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.  
Member Number: 31
Base type:
SCPTmaxRcvTime
Applies to nviCoolSecSlave
Array: not permitted
Default: 0,0
nciMinOutTmMinimum send time.:   The minimum period of time between consecutive transmissions of the current value. 
Member Number: 33
Base type:
SCPTminSendTime
Applies to SFPTchilledCeilingController
Array: not permitted
Default: 0,0
nciLocationLocation:   Provides descriptive physical location information related to the object. 
Member Number: 34
Base type:
SCPTlocation
Applies to SFPTchilledCeilingController
Array: not permitted
Default: 00*31
nciBypassTimeBypass time.:   The maximum amount of time that the controller can be in the bypass (occupancy) mode following the last bypass request. Zero disables the timer. 
Member Number: 35
Base type:
SCPTbypassTime
Applies to SFPTchilledCeilingController
Array: not permitted
Default: 0
nciManualTimeManual override time.:   The maximum time that the controller will stay in a manual mode following the last request by a network variable input. Zero disables the timer. 
Member Number: 36
Base type:
SCPTmanOvrTime
Applies to SFPTchilledCeilingController
Array: not permitted
Default: 0
nciSndHrtBtNV23Maximum send time.:   The maximum period of time between consecutive transmissions of the current value. 
Member Number: 39
Base type:
SCPTmaxSendTime
Applies to nvoUnitStatus
Array: not permitted
Default: 0,0
nciSndHrtBtNV22Maximum send time.:   The maximum period of time between consecutive transmissions of the current value. 
Member Number: 40
Base type:
SCPTmaxSendTime
Applies to nvoSpaceTemp
Array: not permitted
Default: 0,0
nciRcvHrtBtMaximum receive time.:   The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.  
Member Number: 38
Base type:
SCPTmaxRcvTime
Applies to SFPTchilledCeilingController
Array: not permitted
Default: 0,0