SNVT_hvac_overid

Overview:

HVAC override.  (state, pct, flow.) .   

Used for heating, ventilation, and air-conditioning applications.


Details:

Resource Set: Standard 00:00:00:00:00:00:00:00-0
Index: 111
Obsolete: no
Size: 5
Programmatic Name: SNVT_hvac_overid
Neuron C Type:
Structure
stateHVAC override state.  (override state names.) .   
 
hvac_overid_t
percentPercent  (% of full scale.) .  Position or flow override value. 
 
signed long
Minimum: -32768
Maximum: 32767
Invalid: 32767
Scaling (A,B,C): 5,  -3,  0
Scaled value: 5 *10 -3 *(Raw+0)
Resolution: 0.005
flowFlow  (liters/second) .   
 
unsigned long
Minimum: 0
Maximum: 65535
Invalid: 65535
Scaling (A,B,C): 1,  0,  0
Scaled value: 1 *10 0 *(Raw+0)
Resolution: 1
Formats:

SNVT_hvac_overid#SI:  text("%m,%f,%f", state, percent, flow)

SNVT_hvac_overid#SI_LO:  text("%m|%f|%f", state, percent, flow)

SNVT_hvac_overid#US:  text("%m,%f,%f", state, percent, flow*2.1189+0(0:966))

SNVT_hvac_overid#US_LO:  text("%m|%f|%f", state, percent, flow*2.1189+0(0:966))

Used by:

SFPTchilledCeilingController  SFPTdamperActuator  SFPTsccAHU  SFPTsccChilledCeiling  SFPTsccFanCoil  SFPTsccHeatPump  SFPTsccRadiator  SFPTsccRooftop  SFPTsccSelfContained  SFPTsccUnitVentilator  SFPTsccVAV  SFPTspaceComfortController  SFPTunitVentilatorController  SFPTvariableAirVolume