SFPTdischargeAirController

Discharge-Air Controller (DAC).  Used to control duct static pressure and discharge-air temperature. 
 

Network Variables

Configuration Properties

nviOccSchedule
nvoDischAirTemp
nvoUnitStatus

nviApplicMode
nviBldgStatPress
nviBldgStaticSP
nviCWFlow
nviCWTemp
nviDAClSP
nviDADewPointSP
nviDAHtSP
nviDehumEnable
nviDuctStatPress
nviDuctStaticSP
nviEconEnable
nviEmergOverride
nviExhFanCap
nviFanDiffSP
nviHumEnable
nviMATSP
nviMinOAFlowSP
nviOAEnthalpy
nviOAMinPos
nviOccManCmd
nviOutdoorRH
nviOutdoorTemp
nviPriCoolEnable
nviPriHeatEnable
nviRATemp
nviRetFanCap
nviSpaceDehumSP
nviSpaceEnthalpy
nviSpaceHumSP
nviSpaceRH
nviSpaceTemp
nviSupFanCap
nvoApplicMode
nvoBldgStatPress
nvoCWFlow
nvoCWPump
nvoCWTemp
nvoCondCap
nvoCoolPrimary
nvoDADewPoint
nvoDehumidifier
nvoDuctStatPress
nvoEconEnabled
nvoEffDADewPtSP
nvoEffDATempSP
nvoEffDuctStatSP
nvoEffSpaceDHSP
nvoEffSpaceHumSP
nvoEffectOccup
nvoExhDamper
nvoExhFanCap
nvoExhFanOnOff
nvoExhFanStatus
nvoHeatCool
nvoHeatPrimary
nvoHumidifier
nvoLocalCWTemp
nvoLocalOARH
nvoLocalOATemp
nvoMATemp
nvoOADamper
nvoOAEnthalpy
nvoOAFlow
nvoOutdoorRH
nvoOutdoorTemp
nvoRATemp
nvoRetFanCap
nvoRetFanOnOff
nvoRetFanPress
nvoRetFanStatus
nvoSpaceEnthalpy
nvoSpaceRH
nvoSpaceTemp
nvoSupFanCap
nvoSupFanOnOff
nvoSupFanStatus

nciDAClSP
nciDAHtSP
nciSndHrtBt

nciBldgStaticSP
nciBypassTime
nciCoolLockout
nciCoolResetEn
nciDADewPointSP
nciDuctStatLim
nciDuctStatSP
nciExhStartPos
nciFanDiffSP
nciHeatLockout
nciHeatResetEn
nciLocation
nciMALowLimitSP
nciMATSP
nciMaxDAClSP
nciMaxDAHtSP
nciMaxDuctStatSP
nciMaxREFanCap
nciMaxSupFanCap
nciMinDAClSP
nciMinDAHtSP
nciMinDuctStatSP
nciMinOAFlowSP
nciMinOutTm
nciMinREFanCap
nciMinSupFanCap
nciOAEnthSP
nciOAFlowCalib
nciOAInletArea
nciOAMinPos
nciOATSP
nciRcvHrtBt
nciRetFanPressSP
nciSetpoints
nciSpaceDehumSP
nciSpaceHumSP
nciTempDiff

 

Details:

Resource Set: Standard 00:00:00:00:00:00:00:00-0
Index: 12
Obsolete: no
Key: 8610
Inheriting: no


Mandatory Network Variables

nviOccScheduleOccupancy scheduler input.:   Commands the Discharge-Air Controller into different occupancy modes typically sent by scheduler or supervisory node. 
Member Number: 1
Base type:
SNVT_tod_event
Direction: input
Service: any
nvoDischAirTempDischarge air temperature output.:   Monitors discharge-air temperature measured by a hardwired sensor. 
Member Number: 35
Base type:
SNVT_temp_p
Direction: output
Service: unacknowledged
nvoUnitStatusUnit status output.:   Reports the Discharge-Air Controller status. 
Member Number: 36
Base type:
SNVT_hvac_status
Direction: output
Service: unacknowledged


Optional Network Variables

nviOccManCmdOccupancy override input.:   Commands the Discharge-Air Controller into different occupancy modes. 
Member Number: 2
Base type:
SNVT_occupancy
Direction: input
Service: any
nviApplicModeApplication mode input.:   Coordinates the Discharge-Air Controller with any supervisory controller. 
Member Number: 3
Base type:
SNVT_hvac_mode
Direction: input
Service: any
nviEmergOverrideEmergency override input.:   Commands the device into different emergency modes. 
Member Number: 4
Base type:
SNVT_hvac_emerg
Direction: input
Service: any
nviDuctStatPressDuct static pressure input.:   Connects a duct static pressure sensor or network output from another controller. 
Member Number: 5
Base type:
SNVT_press_p
Direction: input
Service: any
Minimum: 0
Maximum: 1250
nviDuctStaticSPDuct static pressure setpoint input.:   Sets duct static pressure setpoint of the controller via the network. 
Member Number: 6
Base type:
SNVT_press_p
Direction: input
Service: any
Minimum: 0
Maximum: 1250
nviDAClSPDischarge air cooling setpoint input.:   Sets discharge-air cooling setpoint of the controller via the network. 
Member Number: 7
Base type:
SNVT_temp_p
Direction: input
Service: any
Minimum: 0,00
Maximum: 30,00
nviDAHtSPDischarge-Air heating setpoint input.:   Sets discharge-air heating setpoint of the controller via the network. 
Member Number: 8
Base type:
SNVT_temp_p
Direction: input
Service: any
Minimum: 0,00
Maximum: 70,00
nviSupFanCapSupply fan capacity input.:   Commands override of the supply fan capacity from another controller. 
Member Number: 9
Base type:
SNVT_lev_percent
Direction: input
Service: any
Minimum: 0,000
Maximum: 100,000
nviExhFanCapExhaust fan capacity input.:   Connects network output from another controller to override the local exhaust fan capacity control. 
Member Number: 10
Base type:
SNVT_lev_percent
Direction: input
Service: any
Minimum: 0,000
Maximum: 100,000
nviRetFanCapReturn fan capacity input.:   Commands an override of return fan capacity from another controller. 
Member Number: 11
Base type:
SNVT_lev_percent
Direction: input
Service: any
Minimum: 0,000
Maximum: 100,000
nviFanDiffSPFan differential setpoint input.:   Setpoint for the percent capacity difference between the supply and return fans. 
Member Number: 12
Base type:
SNVT_lev_percent
Direction: input
Service: any
Minimum: 0,000
Maximum: 50,000
nviBldgStatPressBuilding static pressure input.:   Connects network building static pressure sensor or network output from another controller. 
Member Number: 13
Base type:
SNVT_press_p
Direction: input
Service: any
Minimum: -125
Maximum: 125
nviBldgStaticSPBuilding static pressure setpoint input.:   Connects network output from another controller to provide the building static pressure setpoint. 
Member Number: 14
Base type:
SNVT_press_p
Direction: input
Service: any
Minimum: -100
Maximum: 100
nviPriCoolEnablePrimary cool enable input.:   Connect network output from another controller to enable/disable the primary cooling output of the unit. 
Member Number: 15
Base type:
SNVT_switch
Direction: input
Service: any
nviPriHeatEnablePrimary heat enable input.:   Connects network output from another controller to enable/disable the primary heating outputs of the unit. 
Member Number: 16
Base type:
SNVT_switch
Direction: input
Service: any
nviEconEnableEconomizer enable input.:   Enables and disables economizer operation. 
Member Number: 17
Base type:
SNVT_switch
Direction: input
Service: any
nviOAMinPosOutdoor air minimum position input.:   Sets minimum outdoor air damper position of controller via the network. 
Member Number: 18
Base type:
SNVT_lev_percent
Direction: input
Service: any
Minimum: 0,000
Maximum: 100,000
nviMinOAFlowSPMinimum outdoor airflow setpoint input.:   Commands a minimum outdoor airflow rate setpoint from the network. 
Member Number: 19
Base type:
SNVT_flow
Direction: input
Service: any
Minimum: 0
Maximum: 50000
nviOutdoorTempOutdoor air temperature input.:   Measured outdoor air dry bulb temperature. 
Member Number: 20
Base type:
SNVT_temp_p
Direction: input
Service: any
Minimum: -40,00
Maximum: 50,00
nviOutdoorRHOutdoor air humidity input.:   Measured outdoor air humidity in percent. 
Member Number: 21
Base type:
SNVT_lev_percent
Direction: input
Service: any
Minimum: 0,000
Maximum: 100,000
nviOAEnthalpyOutdoor air enthalpy input.:   Connects a network outdoor air enthalpy sensor or network controller output. 
Member Number: 22
Base type:
SNVT_enthalpy
Direction: input
Service: any
Minimum: 20,00
Maximum: 100,00
nviMATSPMixed air temperature setpoint input.:   Commands a mixed air temperature setpoint from the network. 
Member Number: 23
Base type:
SNVT_temp_p
Direction: input
Service: any
Minimum: -10,00
Maximum: 50,00
nviRATempReturn air temperature input.:   Connects a network return air temperature sensor or network output from another controller. 
Member Number: 24
Base type:
SNVT_temp_p
Direction: input
Service: any
Minimum: -10,00
Maximum: 50,00
nviSpaceEnthalpySpace enthalpy input.:   Connects a network return air or space enthalpy sensor or network output from another controller. 
Member Number: 25
Base type:
SNVT_enthalpy
Direction: input
Service: any
Minimum: 20,00
Maximum: 100,00
nviSpaceTempSpace temperature input.:   Connects a network space temperature sensor or network output from another controller. 
Member Number: 26
Base type:
SNVT_temp_p
Direction: input
Service: any
Minimum: -10,00
Maximum: 50,00
nviSpaceRHSpace humidity input.:   Connects a network return air or space relative humidity sensor or network output from another controller. 
Member Number: 27
Base type:
SNVT_lev_percent
Direction: input
Service: any
Minimum: 0,000
Maximum: 100,000
nviHumEnableHumidification enable input.:   Enables humidification function in the controller. 
Member Number: 28
Base type:
SNVT_switch
Direction: input
Service: any
nviSpaceHumSPSpace humidification setpoint input.:   Connects a network space humidity setpoint or network output from another controller. 
Member Number: 29
Base type:
SNVT_lev_percent
Direction: input
Service: any
Minimum: 0,000
Maximum: 100,000
nviDehumEnableDehumidification enable input.:   Enables dehumidification function in the controller. 
Member Number: 30
Base type:
SNVT_switch
Direction: input
Service: any
nviSpaceDehumSPSpace dehumidification setpoint input.:   Connects a network space dehumidification setpoint or network output from another controller. 
Member Number: 31
Base type:
SNVT_lev_percent
Direction: input
Service: any
Minimum: 0,000
Maximum: 100,000
nviDADewPointSPDischarge air dewpoint setpoint input.:   Commands a discharge-air dewpoint setpoint from the network. 
Member Number: 32
Base type:
SNVT_temp_p
Direction: input
Service: any
Minimum: -20,00
Maximum: 30,00
nviCWTempCondenser water temperature input.:   Connects a network condenser water temperature sensor or network output from another controller. 
Member Number: 33
Base type:
SNVT_temp_p
Direction: input
Service: any
Minimum: -10,00
Maximum: 50,00
nviCWFlowCondenser water flow input.:   System condenser flow status. 
Member Number: 34
Base type:
SNVT_switch
Direction: input
Service: any
nvoEffDATempSPEffective discharge-air temperature setpoint output.:   Monitors the effective discharge-air temperature setpoint the Discharge-Air Controller is using for control. 
Member Number: 37
Base type:
SNVT_temp_p
Direction: output
Service: unacknowledged
nvoDuctStatPressDuct static pressure output.:   Monitors the effective duct static pressure the controller is using for control. 
Member Number: 38
Base type:
SNVT_press_p
Direction: output
Service: unacknowledged
nvoEffDuctStatSPEffective duct static pressure setpoint output.:   Monitors the effective duct static pressure setpoint the Discharge-Air Controller is using for control. 
Member Number: 39
Base type:
SNVT_press_p
Direction: output
Service: unacknowledged
nvoHeatCoolEffective heat/cool output.:   Actual heat/cool mode of the unit. 
Member Number: 40
Base type:
SNVT_hvac_mode
Direction: output
Service: unacknowledged
nvoApplicModeApplication mode output.:   Used to control the mode of other controllers such as a VAV box controller. 
Member Number: 41
Base type:
SNVT_hvac_mode
Direction: output
Service: unacknowledged
nvoEffectOccupEffective occupancy output.:   Transmits the current occupancy mode of the Discharge-Air Controller for monitoring. 
Member Number: 42
Base type:
SNVT_occupancy
Direction: output
Service: unacknowledged
nvoSupFanStatusSupply fan status output.:   Actual status of the supply fan for monitoring. 
Member Number: 43
Base type:
SNVT_switch
Direction: output
Service: unacknowledged
nvoSupFanOnOffSupply fan on/off control output.:   Used to start and stop the supply fan. 
Member Number: 44
Base type:
SNVT_switch
Direction: output
Service: unacknowledged
nvoSupFanCapSupply fan capacity output.:   Used to command the supply fan speed or capacity. 
Member Number: 45
Base type:
SNVT_lev_percent
Direction: output
Service: unacknowledged
Minimum: 0,000
Maximum: 100,000
nvoExhFanStatusExhaust fan status output.:   Actual status of the exhaust fan for monitoring. 
Member Number: 46
Base type:
SNVT_switch
Direction: output
Service: unacknowledged
nvoExhFanOnOffExhaust fan on/off control output.:   Used to start and stop the exhaust fan. 
Member Number: 47
Base type:
SNVT_switch
Direction: output
Service: unacknowledged
nvoExhFanCapExhaust fan capacity output.:   Used to command the exhaust fan speed or capacity. 
Member Number: 48
Base type:
SNVT_lev_percent
Direction: output
Service: unacknowledged
Minimum: 0,000
Maximum: 100,000
nvoExhDamperExhaust damper control output.:   Present status of Exhaust Damper output for monitoring or control. 
Member Number: 49
Base type:
SNVT_lev_percent
Direction: output
Service: unacknowledged
Minimum: 0,000
Maximum: 100,000
nvoRetFanStatusReturn fan status output.:   Actual status of the return fan for monitoring. 
Member Number: 50
Base type:
SNVT_switch
Direction: output
Service: unacknowledged
nvoRetFanOnOffReturn fan on/off control output.:   Used to start and stop the return fan. 
Member Number: 51
Base type:
SNVT_switch
Direction: output
Service: unacknowledged
nvoRetFanCapReturn fan capacity output.:   Used to command the return fan speed or capacity. 
Member Number: 52
Base type:
SNVT_lev_percent
Direction: output
Service: unacknowledged
Minimum: 0,000
Maximum: 100,000
nvoRetFanPressReturn fan pressure output.:   Present value of return fan static pressure for monitoring. 
Member Number: 53
Base type:
SNVT_press_p
Direction: output
Service: unacknowledged
nvoBldgStatPressBuilding static pressure output.:   Present value of the building static pressure for monitoring. 
Member Number: 54
Base type:
SNVT_press_p
Direction: output
Service: unacknowledged
nvoEconEnabledEconomizer enabled output.:   Present enable/disable status of economizer for monitoring. 
Member Number: 55
Base type:
SNVT_switch
Direction: output
Service: unacknowledged
nvoOADamperOutdoor air damper output.:   Present level of the outdoor air damper or injection fan capacity output for monitoring or control. 
Member Number: 56
Base type:
SNVT_lev_percent
Direction: output
Service: unacknowledged
Minimum: 0,000
Maximum: 100,000
nvoOAFlowOutdoor airflow output.:   Present value of the outdoor airflow for monitoring. 
Member Number: 57
Base type:
SNVT_flow
Direction: output
Service: unacknowledged
nvoLocalOATempLocal outdoor air temperature output.:   Indicates value of a hardwired outdoor air temperature sensor. 
Member Number: 58
Base type:
SNVT_temp_p
Direction: output
Service: unacknowledged
nvoOutdoorTempOutdoor air temperature output.:   Present value of outdoor air temperature for monitoring. 
Member Number: 59
Base type:
SNVT_temp_p
Direction: output
Service: unacknowledged
nvoLocalOARHLocal outdoor air humidity output.:   Indicates value of hardwired outdoor air relative humidity sensor. 
Member Number: 60
Base type:
SNVT_lev_percent
Direction: output
Service: unacknowledged
Minimum: 0,000
Maximum: 100,000
nvoOutdoorRHOutdoor air humidity output.:   Present value of outdoor air humidity for monitoring. 
Member Number: 61
Base type:
SNVT_lev_percent
Direction: output
Service: unacknowledged
Minimum: 0,000
Maximum: 100,000
nvoOAEnthalpyOutdoor air enthalpy output.:   Present value of the outdoor air enthalpy. 
Member Number: 62
Base type:
SNVT_enthalpy
Direction: output
Service: unacknowledged
nvoCoolPrimaryPrimary Cooling Output.:   Present level of the primary cooling capacity. 
Member Number: 63
Base type:
SNVT_lev_percent
Direction: output
Service: unacknowledged
Minimum: 0,000
Maximum: 100,000
nvoHeatPrimaryPrimary heating output.:   Present value of the primary heating capacity. 
Member Number: 64
Base type:
SNVT_lev_percent
Direction: output
Service: unacknowledged
Minimum: 0,000
Maximum: 100,000
nvoMATempMixed air temperature output.:   Present value of the mixed air dry bulb temperature. 
Member Number: 65
Base type:
SNVT_temp_p
Direction: output
Service: unacknowledged
nvoSpaceTempSpace temperature output.:   Present value of the space temperature for monitoring. 
Member Number: 66
Base type:
SNVT_temp_p
Direction: output
Service: unacknowledged
nvoRATempReturn air temperature output.:   Present value of return air temperature for monitoring. 
Member Number: 67
Base type:
SNVT_temp_p
Direction: output
Service: unacknowledged
nvoSpaceRHSpace humidity output.:   Present value of the space relative humidity for monitoring. 
Member Number: 68
Base type:
SNVT_lev_percent
Direction: output
Service: unacknowledged
Minimum: 0,000
Maximum: 100,000
nvoSpaceEnthalpySpace enthalpy output.:   Present value of the space enthalpy. 
Member Number: 69
Base type:
SNVT_enthalpy
Direction: output
Service: unacknowledged
nvoEffSpaceHumSPEffective space humidification setpoint output.:   Effective space low limit humidity setpoint for monitoring. 
Member Number: 70
Base type:
SNVT_lev_percent
Direction: output
Service: unacknowledged
Minimum: 0,000
Maximum: 100,000
nvoHumidifierHumidification status output.:   Present level of the humidifier output for monitoring. 
Member Number: 71
Base type:
SNVT_lev_percent
Direction: output
Service: unacknowledged
Minimum: 0,000
Maximum: 100,000
nvoEffSpaceDHSPEffective space dehumidification setpoint output.:   Effective space high limit humidity setpoint for monitoring. 
Member Number: 72
Base type:
SNVT_lev_percent
Direction: output
Service: unacknowledged
Minimum: 0,000
Maximum: 100,000
nvoDehumidifierDehumidification status output.:   Present status of dehumidification control for monitoring. 
Member Number: 73
Base type:
SNVT_switch
Direction: output
Service: unacknowledged
nvoEffDADewPtSPEffective discharge-air dewpoint setpoint output.:   Monitors the effective discharge-air dewpoint setpoint that the discharge-air controller is using for control. 
Member Number: 74
Base type:
SNVT_temp_p
Direction: output
Service: unacknowledged
nvoDADewPointDischarge air dewpoint temperature output.:   Present value of the discharge-air dewpoint temperature. 
Member Number: 75
Base type:
SNVT_temp_p
Direction: output
Service: unacknowledged
nvoCondCapCondenser capacity output.:   Present value of the condenser capacity control output for monitoring. 
Member Number: 76
Base type:
SNVT_lev_percent
Direction: output
Service: unacknowledged
Minimum: 0,000
Maximum: 100,000
nvoLocalCWTempLocal condenser water temperature output.:   Transmits value of hardwired condenser water temperature sensor. 
Member Number: 77
Base type:
SNVT_temp_p
Direction: output
Service: unacknowledged
nvoCWTempCondenser water temperature output.:   Present value of condenser water temperature for monitoring. 
Member Number: 78
Base type:
SNVT_temp_p
Direction: output
Service: unacknowledged
nvoCWFlowCondenser water flow output.:   Transmits current status of condenser water flow sensor for monitoring. 
Member Number: 79
Base type:
SNVT_switch
Direction: output
Service: unacknowledged
nvoCWPumpCondenser water pump output.:   Transmits the current state of condenser water pump output for monitoring or control. 
Member Number: 80
Base type:
SNVT_switch
Direction: output
Service: unacknowledged


Mandatory Configuration Properties

nciSndHrtBtSend heartbeat.:   Maximum period of time that expires before specified NV outputs will be automatically updated. 
Member Number: 1
Base type:
SCPTmaxSendTime
Applies to SFPTdischargeAirController
Array: not permitted
nciDAClSPDischarge air cooling setpoint.:   Default discharge-air cooling setpoint for the Discharge-Air Controller. 
Member Number: 2
Base type:
SCPTdischargeAirCoolingSetpoint
Applies to SFPTdischargeAirController
Array: not permitted
nciDAHtSPDischarge air heating setpoint.:   Default discharge-air heating setpoint for the Discharge-Air Controller. 
Member Number: 3
Base type:
SCPTdischargeAirHeatingSetpoint
Applies to SFPTdischargeAirController
Array: not permitted


Optional Configuration Properties

nciSetpointsOccupancy temperature setpoints.:   Space temperature setpoints for various heat, cool and occupancy modes. 
Member Number: 4
Base type:
SCPTsetPnts
Applies to SFPTdischargeAirController
Array: not permitted
nciMinOutTmMinimum send time.:   Minimum time between automatic NV output transmissions. 
Member Number: 5
Base type:
SCPTminSendTime
Applies to SFPTdischargeAirController
Array: not permitted
nciRcvHrtBtReceive heartbeat.:   Controls maximum time after last update before default values are used. 
Member Number: 6
Base type:
SCPTmaxRcvTime
Applies to SFPTdischargeAirController
Array: not permitted
nciLocationLocation label.:   Provides descriptive physical location information related to the object. 
Member Number: 7
Base type:
SCPTlocation
Applies to SFPTdischargeAirController
Array: not permitted
nciBypassTimeLocal bypass time.:   Maximum time the controller can be in bypass mode following request. 
Member Number: 8
Base type:
SCPTbypassTime
Applies to SFPTdischargeAirController
Array: not permitted
nciMaxSupFanCapMaximum supply fan capacity.:   Maximum supply fan capacity setpoint for the Discharge-Air Controller. 
Member Number: 9
Base type:
SCPTmaxSupplyFanCapacity
Applies to SFPTdischargeAirController
Array: not permitted
Minimum: 0,000
Maximum: 100,000
nciMinSupFanCapMinimum supply fan capacity.:   Minimum supply fan capacity setpoint for the Discharge-Air Controller. 
Member Number: 10
Base type:
SCPTminSupplyFanCapacity
Applies to SFPTdischargeAirController
Array: not permitted
Minimum: 0,000
Maximum: 100,000
nciMaxREFanCapMaximum return/exhaust fan capacity.:   Maximum return/exhaust fan capacity setpoint for the Discharge-Air Controller. 
Member Number: 11
Base type:
SCPTmaxReturnExhaustFanCapacity
Applies to SFPTdischargeAirController
Array: not permitted
Minimum: 0,000
Maximum: 100,000
nciMinREFanCapMinimum return/exhaust fan capacity.:   Minimum return/exhaust fan capacity setpoint for the Discharge-Air Controller. 
Member Number: 12
Base type:
SCPTminReturnExhaustFanCapacity
Applies to SFPTdischargeAirController
Array: not permitted
Minimum: 0,000
Maximum: 100,000
nciDuctStatSPDuct static pressure setpoint.:   Default duct static pressure setpoint for the Discharge-Air Controller. 
Member Number: 13
Base type:
SCPTductStaticPressureSetpoint
Applies to SFPTdischargeAirController
Array: not permitted
nciMaxDuctStatSPMaximum duct static pressure setpoint.:   Maximum duct static pressure setpoint for the Discharge-Air Controller. 
Member Number: 14
Base type:
SCPTmaxDuctStaticPressureSetpoint
Applies to SFPTdischargeAirController
Array: not permitted
nciMinDuctStatSPMinimum duct static pressure setpoint.:   Minimum duct static pressure setpoint for the Discharge-Air Controller. 
Member Number: 15
Base type:
SCPTminDuctStaticPressureSetpoint
Applies to SFPTdischargeAirController
Array: not permitted
nciDuctStatLimDuct static pressure limit.:   Duct static pressure limit, used for equipment protection. 
Member Number: 16
Base type:
SCPTductStaticPressureLimit
Applies to SFPTdischargeAirController
Array: not permitted
nciBldgStaticSPBuilding static pressure setpoint.:   Default building static pressure setpoint for the Discharge-Air Controller. 
Member Number: 17
Base type:
SCPTbuildingStaticPressureSetpoint
Applies to SFPTdischargeAirController
Array: not permitted
nciRetFanPressSPReturn fan pressure setpoint.:   Return fan static pressure setpoint for the Discharge-Air Controller. 
Member Number: 18
Base type:
SCPTreturnFanStaticPressureSetpoint
Applies to SFPTdischargeAirController
Array: not permitted
nciFanDiffSPFan differential setpoint.:   Default for percent capacity difference between supply and return fans. 
Member Number: 19
Base type:
SCPTfanDifferentialSetpoint
Applies to SFPTdischargeAirController
Array: not permitted
nciMALowLimitSPMixed air low limit setpoint.:   Mixed air low limit setpoint for the Discharge-Air Controller. 
Member Number: 20
Base type:
SCPTmixedAirLowLimitSetpoint
Applies to SFPTdischargeAirController
Array: not permitted
nciMATSPMixed air temperature setpoint.:   Default mixed air temperature setpoint for the Discharge-Air Controller. 
Member Number: 21
Base type:
SCPTmixedAirTempSetpoint
Applies to SFPTdischargeAirController
Array: not permitted
nciOAMinPosOutdoor air damper minimum position.:   Default minimum outdoor air damper position setpoint for the Discharge-Air Controller. 
Member Number: 22
Base type:
SCPTminRnge
Applies to nvoOADamper
Array: not permitted
nciMinOAFlowSPMinimum outdoor airflow setpoint.:   Default minimum outdoor airflow setpoint for the Discharge-Air Controller. 
Member Number: 23
Base type:
SCPTminOutdoorAirFlowSetpoint
Applies to SFPTdischargeAirController
Array: not permitted
nciOAFlowCalibOutdoor airflow calibration.:   Gain for the outdoor airflow calibration for the Discharge-Air Controller. 
Member Number: 24
Base type:
SCPTsensConstVAV
Applies to SFPTdischargeAirController
Array: not permitted
nciOAInletAreaOutdoor air inlet area.:   Area of the outdoor air inlet for the Discharge-Air Controller. 
Member Number: 25
Base type:
SCPTductArea
Applies to SFPTdischargeAirController
Array: not permitted
nciOATSPOutdoor air temperature setpoint.:   Airside economizer outdoor air temperature enable setpoint for the Discharge-Air Controller. 
Member Number: 26
Base type:
SCPToutdoorAirTempSetpoint
Applies to SFPTdischargeAirController
Array: not permitted
nciOAEnthSPOutdoor air enthalpy setpoint.:   Default airside economizer outdoor air enthalpy enable setpoint for the Discharge-Air Controller. 
Member Number: 27
Base type:
SCPToutdoorAirEnthalpySetpoint
Applies to SFPTdischargeAirController
Array: not permitted
nciTempDiffEconomizer enable differential temperature setpoint.:   Differential between entering air temp and entering condenser water temp to enable economizer operation. 
Member Number: 28
Base type:
SCPTdiffTempSetpoint
Applies to SFPTdischargeAirController
Array: not permitted
nciExhStartPosExhaust enable position.:   Exhaust enable outdoor air damper position setpoint for the Discharge-Air Controller. 
Member Number: 29
Base type:
SCPTexhaustEnablePosition
Applies to SFPTdischargeAirController
Array: not permitted
nciSpaceHumSPSpace humidification setpoint.:   Default space humidification setpoint for the Discharge-Air Controller. 
Member Number: 30
Base type:
SCPTspaceHumSetpoint
Applies to SFPTdischargeAirController
Array: not permitted
Minimum: 0,000
Maximum: 100,000
nciSpaceDehumSPSpace dehumidification setpoint.:   Default space dehumidification setpoint for the Discharge-Air Controller. 
Member Number: 31
Base type:
SCPThumSetpt
Applies to SFPTdischargeAirController
Array: not permitted
Minimum: 0,000
Maximum: 100,000
nciDADewPointSPDischarge air dewpoint setpoint.:   Default discharge-air dewpoint setpoint for the Discharge-Air Controller. 
Member Number: 32
Base type:
SCPTdischargeAirDewpointSetpoint
Applies to SFPTdischargeAirController
Array: not permitted
nciMaxDAClSPMaximum discharge air cooling setpoint.:   Maximum discharge-air cooling setpoint for the Discharge-Air Controller. 
Member Number: 33
Base type:
SCPTmaxDischargeAirCoolingSetpoint
Applies to SFPTdischargeAirController
Array: not permitted
nciMinDAClSPMinimum discharge air cooling setpoint.:   Minimum discharge-air cooling setpoint for the Discharge-Air Controller. 
Member Number: 34
Base type:
SCPTminDischargeAirCoolingSetpoint
Applies to SFPTdischargeAirController
Array: not permitted
nciMaxDAHtSPMaximum discharge air heating setpoint.:   Maximum discharge heating setpoint for the Discharge-Air Controller. 
Member Number: 35
Base type:
SCPTmaxDischargeAirHeatingSetpoint
Applies to SFPTdischargeAirController
Array: not permitted
nciMinDAHtSPMinimum discharge air heating setpoint.:   Minimum discharge heating setpoint for the Discharge-Air Controller. 
Member Number: 36
Base type:
SCPTminDischargeAirHeatingSetpoint
Applies to SFPTdischargeAirController
Array: not permitted
nciCoolLockoutCooling lockout temperature setpoint.:   Outdoor air temperature cooling lockout setpoint for the Discharge-Air Controller. 
Member Number: 37
Base type:
SCPTcoolingLockout
Applies to SFPTdischargeAirController
Array: not permitted
nciHeatLockoutHeating lockout temperature setpoint.:   Outdoor air temperature heating lockout setpoint for the Discharge-Air Controller. 
Member Number: 38
Base type:
SCPTheatingLockout
Applies to SFPTdischargeAirController
Array: not permitted
nciCoolResetEnCooling reset enable.:   Enables/disables the discharge-air temperature cooling reset control for the Discharge-Air Controller. 
Member Number: 39
Base type:
SCPTcoolingResetEnable
Applies to SFPTdischargeAirController
Array: not permitted
nciHeatResetEnHeating reset enable.:   Enables/disables the discharge-air temperature heating reset control for the Discharge-Air Controller. 
Member Number: 40
Base type:
SCPTheatingResetEnable
Applies to SFPTdischargeAirController
Array: not permitted