Closed-Loop Sensor (CLS). A basic object with feedback, used with any form of sensor.
|
|
Network Variables | Configuration Properties |
nviValueFb nvoValue
nviPresetFb nvoPreset nvoRawHwData
| nciAlarmClearT1 nciAlarmClearT2 nciAlarmSetT1 nciAlarmSetT2 nciDefault nciGain nciHighLim1 nciHighLim2 nciInvert nciLimHystHi1 nciLimHystHi2 nciLimHystLow1 nciLimHystLow2 nciLocation nciLowLim1 nciLowLim2 nciMaxRng nciMaxSendT nciMinDelta nciMinRng nciMinSendT nciOffset nciOutInhT nciOverBehave nciOverValue nciTransTblX nciTransTblY
|
|
Details: |
Resource Set:
| Standard 00:00:00:00:00:00:00:00-0 |
Index:
| 3 |
Obsolete:
| no |
Key:
| 2 |
Inheriting:
| no |
Principal Variable
| nvoValue |
Mandatory Network Variables |
nviValueFb | Value feedback input.: Used to synchronize closed loop sensor objects when connected in multiple relationships.
|
Member Number:
| 1 |
Base type:
| | Direction:
| input | Service:
| any |
|
nvoValue | Value output.: Transmits the value from the sensor after conversion to correct units.
|
Member Number:
| 2 |
Base type:
| | Direction:
| output | Service:
| any |
|
Optional Network Variables |
nviPresetFb | Preset input feedback.: Receives preset function feedback information used to synchronize multiple source objects.
|
Member Number:
| 3 |
Base type:
| | Direction:
| input | Service:
| any |
|
nvoRawHwData | Raw hardware data output.: Transmits the value obtained from the sensor prior to any transformation.
|
Member Number:
| 4 |
Base type:
| | Direction:
| output | Service:
| any |
|
nvoPreset | Preset output.: Used to program or control the preset of a destination object.
|
Member Number:
| 5 |
Base type:
| | Direction:
| output | Service:
| any |
|
Optional Configuration Properties |
nciLocation | Location label.: Provides descriptive physical location information related to the object.
|
|
nciGain | Gain: Used to calibrate external hardware via a multiplication factor.
|
|
nciOffset | Offset: Used to calibrate external hardware with additive offset after transformation.
|
|
nciMaxRng | Maximum range.: The maximum value limit of the output.
|
Member Number:
| 4 |
Base type:
| |
Applies to
| nvoValue | Array:
| not permitted |
|
nciMinRng | Minimum range.: The minimum value limit of the output.
|
Member Number:
| 5 |
Base type:
| |
Applies to
| nvoValue | Array:
| not permitted |
|
nciMinDelta | Send on delta.: The minimum change required to force transmission of the output value.
|
Member Number:
| 6 |
Base type:
| |
Applies to
| nvoValue | Array:
| not permitted |
|
nciMaxSendT | Maximum send time.: The maximum period of time before a retransmission of value.
|
Member Number:
| 7 |
Base type:
| |
Applies to
| nvoValue | Array:
| not permitted |
|
nciMinSendT | Minimum send time.: The minimum period of time between retransmissions of value.
|
Member Number:
| 8 |
Base type:
| |
Applies to
| nvoValue | Array:
| not permitted |
|
nciInvert | Invert output.: Used to invert active polarity if the hardware sensor is a switch.
|
Member Number:
| 9 |
Base type:
| |
Applies to
| nvoValue | Array:
| not permitted |
|
nciTransTblX | Translation table X.: Used in conjunction with Translation table Y to create a linearization table.
|
|
nciTransTblY | Translation table Y.: Used in conjunction with Translation table X to create a linearization table.
|
|
nciHighLim1 | High limit 1.: Used to remotely set the alarm high limit 1.
|
Member Number:
| 12 |
Base type:
| |
Applies to
| nvoValue | Array:
| not permitted |
|
nciHighLim2 | High limit 2.: Used to remotely set the alarm high limit 2.
|
Member Number:
| 13 |
Base type:
| |
Applies to
| nvoValue | Array:
| not permitted |
|
nciLowLim1 | Low limit 1.: Used to remotely set the alarm low limit 1.
|
Member Number:
| 14 |
Base type:
| |
Applies to
| nvoValue | Array:
| not permitted |
|
nciLowLim2 | Low limit 2.: Used to remotely set the alarm low limit 2.
|
Member Number:
| 15 |
Base type:
| |
Applies to
| nvoValue | Array:
| not permitted |
|
nciAlarmSetT1 | Alarm set time 1.: The time period that an alarm 1 condition must exist before it is regarded as a valid alarm.
|
Member Number:
| 16 |
Base type:
| |
Applies to
| nvoValue | Array:
| not permitted |
|
nciAlarmSetT2 | Alarm set time 2.: The time period that an alarm 2 condition must exist before it is regarded as a valid alarm.
|
Member Number:
| 17 |
Base type:
| |
Applies to
| nvoValue | Array:
| not permitted |
|
nciAlarmClearT1 | Alarm clear time 1.: The time period that an alarm 1 condition must not exist before it is regarded as a valid cleared alarm.
|
Member Number:
| 18 |
Base type:
| |
Applies to
| nvoValue | Array:
| not permitted |
|
nciAlarmClearT2 | Alarm clear time 2.: The time period that an alarm 2 condition must not exist before it is regarded as a valid cleared alarm.
|
Member Number:
| 19 |
Base type:
| |
Applies to
| nvoValue | Array:
| not permitted |
|
nciLimHystHi1 | Hysteresis high 1.: The hysteresis level for the value field of the alarm high 1 comparison threshold.
|
Member Number:
| 20 |
Base type:
| |
Applies to
| nvoValue | Array:
| not permitted |
|
nciLimHystHi2 | Hysteresis high 2.: The hysteresis level for the value field of the alarm high 2 comparison threshold.
|
Member Number:
| 21 |
Base type:
| |
Applies to
| nvoValue | Array:
| not permitted |
|
nciLimHystLow1 | Hysteresis low 1.: The hysteresis level for the value field of the alarm low 1 comparison threshold.
|
Member Number:
| 22 |
Base type:
| |
Applies to
| nvoValue | Array:
| not permitted |
|
nciLimHystLow2 | Hysteresis low 2.: The hysteresis level for the value field of the alarm low 2 comparison threshold.
|
Member Number:
| 23 |
Base type:
| |
Applies to
| nvoValue | Array:
| not permitted |
|
nciOutInhT | Alarm output inhibit time.: Time period for which alarms are inhibited after enabling, node reset, or node is put on line.
|
Member Number:
| 24 |
Base type:
| |
Applies to
| nvoValue | Array:
| not permitted |
|
nciDefault | Default output.: The level the sensor should adopt in certain default conditions.
|
Member Number:
| 25 |
Base type:
| |
Applies to
| nvoValue | Array:
| not permitted |
|
nciOverBehave | Override behavior.: The behavior of a sensor when an override request is received.
|
|
nciOverValue | Override value.: Sets the value a sensor should adopt when an object is overridden and behavior is OV_SPECIFIED.
|
Member Number:
| 27 |
Base type:
| |
Applies to
| nvoValue | Array:
| not permitted |
|