SCPTalrmSetT2

Overview:

Alarm set time 2..  The time period that an alarm 2 condition must exist before it is regarded as a valid alarm. 

This configuration property is used to determine the time period that an alarm 2 condition must exist before it is regarded as a valid alarm.


Details:

Resource Set: Standard 00:00:00:00:00:00:00:00-0
Index: 6
Obsolete: no
Size: 7
Programmatic Name: SCPTalrmSetT2
Maximum: 0 0:0:59:999
Default: 0 0:0:0:0
Neuron C Type:
SNVT_elapsed_tm
Formats:

SCPTalrmSetT2:  text("%d %d:%d:%d:%d", day, hour, minute, second, millisecond)

SCPTalrmSetT2#LO:  text(("%d ", day), time(hour, minute, second, millisecond))

Used by:

SFPTclosedLoopActuator  SFPTclosedLoopSensor  SFPTopenLoopActuator  SFPTopenLoopSensor