SFPTactuateTemperatureSetpoint

Actuate temperature setpoint..   

A detailed description of the function profile with all inputs and outputs as well as the configuration parameters can be found at the VDI - Verein der Deutschen Ingineure. The Web Link is:

VDI - Room control functions (RA functions)
 

Network Variables

Configuration Properties

nviSyncTempStpt
nvoManTempStpt

cpLowerSetptLimit
cpUpperSetptLimit

 

Details:

Resource Set: Standard 00:00:00:00:00:00:00:00-0
Index: 125
Obsolete: no
Key: 16405
Inheriting: no


Mandatory Network Variables

nviSyncTempStptSynchronize temperature setpoint.:   Display of current setpoint (relative or absolute) 
Member Number: 1
Base type:
SNVT_temp_p
Direction: input
Service: any
nvoManTempStptManipulated temperature setpoint.:    
Member Number: 2
Base type:
SNVT_temp_p
Direction: output
Service: any


Mandatory Configuration Properties

cpUpperSetptLimitHigh limit temperature.:   The high alarm set point for the alarm air temp network variable. 
Member Number: 1
Base type:
SCPThighLimTemp
Applies to SFPTactuateTemperatureSetpoint
Array: not permitted
Default: 0,00
cpLowerSetptLimitLow limit temperature.:   The low alarm set point for the alarm air temp network variable. 
Member Number: 2
Base type:
SCPTlowLimTemp
Applies to SFPTactuateTemperatureSetpoint
Array: not permitted
Default: 0,00