CO2 Sensor.. Carbon Dioxide (CO2) Sensor.
|
| |
Network Variables | Configuration Properties |
nvoCO2ppm
nvofloatCO2
| nciCO2MinDelta nciMaxSendTime nciMinSendTime
nciCO2Offset
|
| |
Details: |
| Resource Set:
| Standard 00:00:00:00:00:00:00:00-0 |
| Index:
| 10 |
| Obsolete:
| no |
| Key:
| 1070 |
|
Inheriting:
| no |
|
Principal Variable
| nvoCO2ppm |
Mandatory Network Variables |
| nvoCO2ppm | CO2 level.: The CO2 level in parts-per-million.
|
| Member Number:
| 1 | |
Base type:
| | | Direction:
| output | | Service:
| any |
|
Optional Network Variables |
| nvofloatCO2 | Temperature: The CO2 level in parts-per-million using floating point data type.
|
| Member Number:
| 2 | |
Base type:
| | | Direction:
| output | | Service:
| any |
|
Mandatory Configuration Properties |
| nciMaxSendTime | Maximum send time.: Controls the maximum period of time before the output values are transmitted.
|
| Member Number:
| 1 | |
Base type:
| | |
Applies to
| SFPTco2Sensor | | Array:
| not permitted | | Default:
| 300,0 |
|
| nciMinSendTime | Minimum send time.: Controls the minimum period of time between output value transmissions.
|
| Member Number:
| 2 | |
Base type:
| | |
Applies to
| SFPTco2Sensor | | Array:
| not permitted | | Default:
| 5,0 |
|
| nciCO2MinDelta | Send on delta.: The minimum change required to force transmission of the output value.
|
| Member Number:
| 3 | |
Base type:
| | |
Applies to
| nvoCO2ppm | | Array:
| not permitted | | Default:
| 10 |
|
Optional Configuration Properties |
| nciCO2Offset | CO2 level offset.: Used to calibrate external hardware with additive offset after transformation.
|
| Member Number:
| 4 | |
Base type:
| | |
Applies to
| nvoCO2ppm | | Array:
| not permitted |
|