Control drive actuator..
A detailed description of the function profile with all inputs and outputs as well as the configuration parameters can be found at the VDI - Verein der Deutschen Ingineure.
The Web Link is: VDI - Room control functions (RA functions)
|
| |
Network Variables | Configuration Properties |
nviDrivePos nvoDrivePosFb
| cpFailurePosition cpMaxReceiveTime cpMaxSendTime cpMinSendTime
|
| |
Details: |
| Resource Set:
| Standard 00:00:00:00:00:00:00:00-0 |
| Index:
| 119 |
| Obsolete:
| no |
| Key:
| 16203 |
|
Inheriting:
| no |
Mandatory Network Variables |
| nviDrivePos | Drive position.:
|
| Member Number:
| 1 | |
Base type:
| | | Direction:
| input | | Service:
| any |
|
| nvoDrivePosFb | Drive position feedback.:
|
| Member Number:
| 2 | |
Base type:
| | | Direction:
| output | | Service:
| any |
|
Optional Configuration Properties |
| cpFailurePosition | Default output.: The position or level the sensor should adopt when updates are not received, or at power-on reset, or when overridden.
|
| Member Number:
| 3 | |
Base type:
| | |
Applies to
| nviDrivePos | | Array:
| not permitted | | Default:
| 00*4 |
|
| cpMaxReceiveTime | Maximum receive time.:
The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.
|
| Member Number:
| 4 | |
Base type:
| | |
Applies to
| nviDrivePos | | Array:
| not permitted | | Default:
| 900,0 |
|
| cpMaxSendTime | Maximum send time.: The maximum period of time between consecutive transmissions of the current value.
|
| Member Number:
| 5 | |
Base type:
| | |
Applies to
| nvoDrivePosFb | | Array:
| not permitted | | Default:
| 300,0 |
|
| cpMinSendTime | Minimum send time.: The minimum period of time between consecutive transmissions of the current value.
|
| Member Number:
| 6 | |
Base type:
| | |
Applies to
| nvoDrivePosFb | | Array:
| not permitted | | Default:
| 60,0 |
|