SFPTcontrolDriveActuatorFan

Control drive actuator fan..   

A detailed description of the function profile with all inputs and outputs as well as the configuration parameters can be found at the VDI - Verein der Deutschen Ingineure. The Web Link is:

VDI - Room control functions (RA functions)
 

Network Variables

Configuration Properties

nviFanSpeed
nvoFanSpeedFb

cpFailureCtrl
cpMaxReceiveTime
cpMaxSendTime
cpMinSendTime

 

Details:

Resource Set: Standard 00:00:00:00:00:00:00:00-0
Index: 120
Obsolete: no
Key: 16204
Inheriting: no


Mandatory Network Variables

nviFanSpeedFanspeed:    
Member Number: 1
Base type:
SNVT_switch
Direction: input
Service: any
nvoFanSpeedFbFanspeed feedback.:    
Member Number: 2
Base type:
SNVT_switch
Direction: output
Service: any


Optional Configuration Properties

cpFailureCtrlDefault output.:   The position or level the sensor should adopt when updates are not received, or at power-on reset, or when overridden. 
Member Number: 1
Base type:
SCPTdefOutput
Applies to nviFanSpeed
Array: not permitted
Default: 00*4
cpMaxReceiveTimeMaximum receive time.:   The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.  
Member Number: 2
Base type:
SCPTmaxRcvTime
Applies to nviFanSpeed
Array: not permitted
Default: 900,0
cpMaxSendTimeMaximum send time.:   The maximum period of time between consecutive transmissions of the current value. 
Member Number: 3
Base type:
SCPTmaxSendTime
Applies to nvoFanSpeedFb
Array: not permitted
Default: 300,0
cpMinSendTimeMinimum send time.:   The minimum period of time between consecutive transmissions of the current value. 
Member Number: 4
Base type:
SCPTminSendTime
Applies to nvoFanSpeedFb
Array: not permitted
Default: 60,0