SFPTfanControl

Fan control..   

A detailed description of the function profile with all inputs and outputs as well as the configuration parameters can be found at the VDI - Verein der Deutschen Ingineure. The Web Link is:

VDI - Room control functions (RA functions)
 

Network Variables

Configuration Properties

nviCalcCtrlFunc
nviCalcEnergMode
nviCalcTempStpts
nviManFanSpeed
nviRoomTemp
nvoCalcFanSpeed

cpFanControl
cpFanEnable
cpMaxReceiveTime
cpMaxSendTime

 

Details:

Resource Set: Standard 00:00:00:00:00:00:00:00-0
Index: 151
Obsolete: no
Key: 16525
Inheriting: no


Mandatory Network Variables

nviCalcCtrlFuncCalculated control function.:    
Member Number: 1
Base type:
SNVT_hvac_mode
Direction: input
Service: any
nviCalcEnergModeCalculated energy mode.:    
Member Number: 2
Base type:
SNVT_occupancy
Direction: input
Service: any
nviRoomTempTemperature:    
Member Number: 3
Base type:
SNVT_temp_p
Direction: input
Service: any
nviCalcTempStptsCalculated temperture setpoints.:    
Member Number: 4
Base type:
SNVT_temp_setpt_2
Direction: input
Service: any
nviManFanSpeedManual fan speed.:    
Member Number: 5
Base type:
SNVT_switch
Direction: input
Service: any
nvoCalcFanSpeedCalculated fan speed.:    
Member Number: 6
Base type:
SNVT_switch
Direction: output
Service: any


Mandatory Configuration Properties

cpFanEnable:    
Member Number: 1
Base type:
SCPTfanEnable
Applies to SFPTfanControl
Array: not permitted
Default: 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
cpFanControl:    
Member Number: 2
Base type:
SCPTfanControl
Applies to SFPTfanControl
Array: not permitted
Default: 0,0 0,00
cpMaxSendTimeMaximum send time.:   The maximum period of time between consecutive transmissions of the current value. 
Member Number: 3
Base type:
SCPTmaxSendTime
Applies to nvoCalcFanSpeed
Array: not permitted
Default: 900,0
cpMaxReceiveTimeMaximum receive time.:   The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.  
Member Number: 4
Base type:
SCPTmaxRcvTime
Applies to nviRoomTemp
Array: not permitted
Default: 10,0