SFPTweatherProtection

Weather protection..   

A detailed description of the function profile with all inputs and outputs as well as the configuration parameters can be found at the VDI - Verein der Deutschen Ingineure. The Web Link is:

VDI - Room control functions (RA functions)
 

Network Variables

Configuration Properties

nviSensOutTemp
nviSensPrecip
nviSensWindSpeed
nvoProtSblndCtrl

cpDeIceTime
cpMaxSendTime
cpProtectivePos
cpTempLimitIce
cpWindVelocityThreshold

cpMaxReceiveTimeOutTemp
cpMaxReceiveTimeSenPre
cpMaxReceiveTimeWindSp

 

Details:

Resource Set: Standard 00:00:00:00:00:00:00:00-0
Index: 144
Obsolete: no
Key: 16517
Inheriting: no


Mandatory Network Variables

nviSensWindSpeedSensor windspeed.:    
Member Number: 1
Base type:
SNVT_speed
Direction: input
Service: any
nviSensOutTempSensor outdoor temperature.:    
Member Number: 2
Base type:
SNVT_temp_p
Direction: input
Service: any
nviSensPrecipSensor precipitation.:    
Member Number: 3
Base type:
SNVT_switch
Direction: input
Service: any
nvoProtSblndCtrlProdection sunblind control.:    
Member Number: 4
Base type:
SNVT_setting
Direction: output
Service: any


Mandatory Configuration Properties

cpWindVelocityThreshold:    
Member Number: 1
Base type:
SCPTwindSpeedLimit
Applies to SFPTweatherProtection
Array: not permitted
Default: 0,0
cpTempLimitIceDefrost stop temperature.:   The temperature at which to terminate defrost for objects set to terminate on temperature. 
Member Number: 2
Base type:
SCPTmaxDefrstTemp
Applies to SFPTweatherProtection
Array: not permitted
Default: 0,00
cpDeIceTimeMaximum defrost time.:   The maximum defrost time for defrost objects set to terminate on temperature. 
Member Number: 3
Base type:
SCPTmaxDefrstTime
Applies to SFPTweatherProtection
Array: not permitted
Default: 3600,0
cpProtectivePosdefault Setting.:    
Member Number: 4
Base type:
SCPTdefaultSetting
Applies to SFPTweatherProtection
Array: not permitted
Default: SET_OFF 0,0 0,00
cpMaxSendTimeMaximum send time.:   The maximum period of time between consecutive transmissions of the current value. 
Member Number: 5
Base type:
SCPTmaxSendTime
Applies to nvoProtSblndCtrl
Array: not permitted
Default: 300,0


Optional Configuration Properties

cpMaxReceiveTimeWindSpMaximum receive time.:   The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.  
Member Number: 6
Base type:
SCPTmaxRcvTime
Applies to nviSensWindSpeed
Array: not permitted
Default: 900,0
cpMaxReceiveTimeOutTempMaximum receive time.:   The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.  
Member Number: 7
Base type:
SCPTmaxRcvTime
Applies to nviSensOutTemp
Array: not permitted
Default: 900,0
cpMaxReceiveTimeSenPreMaximum receive time.:   The maximum period of time that may expire with no updates on the associated input network variables before the object goes into heartbeat failure mode. A zero value disables the mechanism.  
Member Number: 8
Base type:
SCPTmaxRcvTime
Applies to nviSensPrecip
Array: not permitted
Default: 60,0