SNVT_turbidity

Overview:

Turbidity  (nephelometric turbidity units.) .   

Used to communicate with water-clarity measuring devices (turbidimeters). SNVT_turbidity can be used to represent ranges associated with drinking water. Units of this variable are NTU (Nephelometric Turbidity Units), which are 1-to-1 equivalent to FNU (Formazin Nephelometric Units), and FTU (Formazin Turbidity Units).


Details:

Resource Set: Standard 00:00:00:00:00:00:00:00-0
Index: 143
Obsolete: no
Size: 2
Programmatic Name: SNVT_turbidity
Neuron C Type:
unsigned long
Minimum: 0
Maximum: 65535
Invalid: 65535
Scaling (A,B,C): 1,  -3,  0
Scaled value: 1 *10 -3 *(Raw+0)
Resolution: 0.001
Formats:

SNVT_turbidity:  text("%f")